Plan Review Details - Permit 13090832
Plan Review Stops For Permit 13090832 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-10-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2013-10-21 |
Time |
19:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2013-10-21 |
Time |
19:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-11 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-11 |
Time |
08:50 |
Sent To |
|
|
Notes |
2013-10-11 08:51:13 | REVIEWED BY WDS. | | | | NEED TO COMPLY WITH FBC 1603.1.4 FOR WIND DDSIGN DATA | | ON CONSTRUCTION DOCUMENTS. | | | | 1) PROVIDE ULTIMATE DESIGN WIND SPEED AND NORMAL DESIGN | | WIND SPEED AS DETERMINED IN ACCORDANCE WITH FBC SECTION | | 1609.3.1. | | 2) PROVIDE RISK CATEGORY FROM TABLE 1604.5 OR TABLE | | 1.5-1 OF ASCE 7. | | 3) WIND EXPOSURE. | | 4) APPLICABLE ENCLOSURE CLASSIFICATION. | | 5) COMPONETS AND CLADDING DESIGN PRESSURES. | | | | REVIEWED BY WDS. | | LEFT MESSAGE ON VOICE MAIL WITH EMILY LOPEZ. | | DENIED SENT TO CONTRACTOR (I). | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-10-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-10-23 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-23 |
Time |
16:26 |
Sent To |
|
|
Notes |
2013-10-23 16:26:12 | PER RB - ELECTRICAL WORK FOR THIS SIGN TO BE INCLUDED | | WITH SITE LIGHTING PERMIT 13070442 (REVISION REQUIRED | | TO INCLUDE SIGNAGE) | | | | OR | | | | SEPARATE ELECTRICAL PERMIT REQUIRED (SUBMIT APPLICATION | | AND PLANS FOR REVIEW) | | | | A REVISION TO 13070442 OR SEPARATE ELECTRICAL PERMIT IS | | REQUIRED PRIOR TO COMMENCEMENT OF ANY ELECTRICAL WORK. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-11 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-11 |
Time |
08:39 |
Sent To |
|
|
Notes |
2013-10-11 08:49:04 | PROVIDE ALL ELECTRICAL DATA FOR A COMPLETE SIGN | | ELECTRIC. INCLUDE-- CIRCUITRY WITH CONDUIT AND | | CONDUCTOR SIZING, VOLTAGE DROP CALCS, WIND LOAD PER SE | | FLORIDA ENGINEERING, DISCONNECT LOCATIONS, UL LISTINGS, | | ETC....... | | REVIEWED BY WDS | | LEFT MESSAGE ON VOICE MAIL WITH EMILY LOPEZ. | | SET TO DENIED CONTRACTOR (I). |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-10-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2013-10-11 |
Time |
19:52 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2013-09-26 |
Time |
19:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2013-10-10 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2013-10-10 |
Time |
15:13 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2013-10-10 |
Time |
15:13 |
Sent To |
E |
|
Notes |
2013-10-10 15:15:26 | PALM BEACH OUTLETS SIGN TYPE 5 | | | | PERMITTED SIGN AREA PER FACE: 200 SQ. FT. | | PROPOSED SIGN AREA PER FACE: 183.33 SQ. FT. |
|
|
|