Plan Review Details - Permit 13090825
Plan Review Stops For Permit 13090825
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-02-20 Cont ID  
Sent By jwitmer Date 2014-02-20 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2014-02-20 Time 06:33 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-12-05 Cont ID  
Sent By jwitmer Date 2013-12-05 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2013-12-05 Time 10:05 Sent To  
Notes
2013-12-05 10:18:06BUILDING PLAN REVIEW
 PERMIT: 13090825
 ADD: 1155 BELVEDERE RD
 CONT: TO BE DETERMINED/ FRITZ MASSON
 TEL: (954)710-1118
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURSDAY DEC. 05/ 2013
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA
 THE PLANS HAVE BEEN UPDATED TO THE CORRECT BUILDING
 CATEGORY II WITH ASSOCIATED WIND DESIGN OF 170 MPH, 3
 SECOND GUST BUT THE EXPOSURE HAS CHANGED FROM THE FIRST
 REVIEW EXPOSURE "C" TO A EXPOSURE "B". THE CORRECT
 EXPOSURE IS A "C" EXPOSURE THAT WILL AFFECT THE
 PRESSURES AND PRODUCT APPROVALS. PLEASE REVIEW AND
 UPDATE POSITIVE AND NEGATIVE PRESSURES ACCORDINGLY,
 NOTE THERE IS A MULTIPLIER TO BE USED WITH A "C"
 EXPOSURE.
  
  
  
 2) 2ND REQUEST. UPDATE THE WIND LOAD/ PRESSURE CHART,
 THIS CHART DOES NOT INDICATE IF THE AREA AFFECTED IS 10
 SF, 20, 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS.
 2010 FBC-B TABLE 1609.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PRESSURES WILL BE AFFECTED BY THE C EXPOSURE, AGAIN
 THE COMMENT # 2 WAS NOT ADDRESSED THIS PORTION OF THE
 REVIEW CAN NOT HAPPEN WITH OUT THE PRESSURES BROKE OUT
 TO 10, 20, 50 OR 100 SQ FT. 2 010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) COMPLIED..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-19 Cont ID  
Sent By jwitmer Date 2013-10-19 Time 12:03 Rev Time 0.00
Received By jwitmer Date 2013-10-19 Time 10:30 Sent To  
Notes
2013-10-19 12:03:28BUILDING PLAN REVIEW
 PERMIT: 13090825
 ADD: 1155 BELVEDERE RD
 CONT: TO BE DETERMINED/ FRITZ MASSON
 TEL: (954)710-1118
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SATURDAY OCT. 19/ 2013
 ACTION: DENIED
  
 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA
 INDICATES A BUILDING RISK CATEGORY I WITH WIND AT VULT
 155 MPH/ 3 SECOND GUST. PLEASE REFER TO THE 2010 FBC-B
 TABLE 1604.5 RISK CATEGORY I BUILDINGS INCLUDE MINOR
 STORAGE FACILITIES, SHEDS, AGRICULTURAL FACILITIES &
 SCREEN ENCLOSURES. PLEASE UPDATE WIND DESIGN CRITEIA
 AND ASSOCIATED PRESSURES.
  
 1604.5.1 MULTIPLE OCCUPANCIES.
 WHERE A BUILDING OR STRUCTURE IS OCCUPIED BY TWO OR
 MORE OCCUPANCIES NOT INCLUDED IN THE SAME RISK
 CATEGORY, IT SHALL BE ASSIGNED THE CLASSIFICATION OF
 THE HIGHEST RISK CATEGORY CORRESPONDING TO THE VARIOUS
 OCCUPANCIES. WHERE BUILDINGS OR STRUCTURES HAVE TWO OR
 MORE PORTIONS THAT ARE STRUCTURALLY SEPARATED, EACH
 PORTION SHALL BE SEPARATELY CLASSIFIED. WHERE A
 SEPARATED PORTION OF A BUILDING OR STRUCTURE PROVIDES
 REQUIRED ACCESS TO, REQUIRED EGRESS FROM OR SHARES LIFE
 SAFETY COMPONENTS WITH ANOTHER PORTION HAVING A HIGHER
 RISK CATEGORY, BOTH PORTIONS SHALL BE ASSIGNED TO THE
 HIGHER RISK CATEGORY.
  
 2) UPDATE THE WIND LOAD/ PRESSURE CHART, THIS CHART
 DOES NOT INDICATE IF THE AREA AFFECTED IS 10 SF, 20,
 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS. 2010
 FBC-B TABLE 1609.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2 010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) SHEET S2.01 DETAIL # 14 TOWER DETAIL INDICATES THE
 STEEL STUD WALL SECTION BEING TIED DOWN TO THE 2X
 SOLLID BLOCKING BETWEEN THE JOIST BUT NO TIE DOEN TO
 THE CONCRETE WALL BENEATH, PART OF THE MWFRT, MAIN WIND
 FORCE RESISTING SYSSTEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-20 Cont ID  
Sent By skennedy Date 2013-12-20 Time 10:57 Rev Time 0.00
Received By skennedy Date 2013-12-20 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-19 Cont ID  
Sent By skennedy Date 2013-11-19 Time 11:22 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 11:22 Sent To  
Notes
2013-11-19 11:25:57PLEASE ADDRESS THE ITEMS NOTED BELOW:
 PER FBC 107.3.5.1.2 ELECTRICAL PROVIDE AN ELECTRICAL
 PLAN DEMONSTRATING THE FOLLOWING: 1. ELECTRICAL WIRING,
 SERVICES, FEEDERS AND BRANCH CIRCUITS, OVERCURRENT
 PROTECTION,GROUNDING,WIRING METHODS AND MATERIALS,
 GFCIS; 2. EQUIPMENT; 3. SPECIAL OCCUPANCIES; 4.
 EMERGENCY SYSTEMS; 5. COMMUNICATION SYSTEMS; 6. LOW
 VOLTAGE; 7. LOAD CALCULATIONS
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By scaldero Date 2013-12-12 Time 13:52 Rev Time 0.00
Received By scaldero Date 2013-12-12 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-07 Cont ID  
Sent By pleduc Date 2013-10-07 Time 14:53 Rev Time 0.00
Received By pleduc Date 2013-10-07 Time 14:46 Sent To  
Notes
2013-10-07 14:53:35THIS PLAN IS APPROVED WITH COMMENTS.
  
 THE EXIT SIGNS AND EMRGENCY LIGHTING LOCATIONS ARE NOT
 CLEARLY INDICATED ON THE PLAN.
  
 PER NFPA 101 LL ED. EXIT LIGHTS AND EMERGENCY LIGHTS
 ARE REQUIRED, CHAPTER 42.2.8.1 & 42.2.2.9.
  
 ANY FIRE ALARM OR FIRE SPRINKLER SYSTEM
 ALTERATIONS/ADDITIONS SHALL BECOMPLETED BY A CERTIFIED
 CONTRACTOR AND UNDER SEPARATE SHOP DRAWING PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-17 Cont ID  
Sent By jwitmer Date 2014-03-17 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2014-02-18 Time 10:21 Sent To  
Notes
2014-02-19 10:22:37RESUBMITTAL SENT TO J. WITMER'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-14 Cont ID  
Sent By eschneid Date 2014-01-14 Time 14:03 Rev Time 0.00
Received By eschneid Date 2013-11-27 Time 10:01 Sent To  
Notes
2013-12-02 10:03:13C25
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-19 Cont ID  
Sent By skennedy Date 2013-11-19 Time 11:31 Rev Time 0.00
Received By skennedy Date 2013-09-25 Time 18:08 Sent To  
Notes
2013-09-26 18:10:21C27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-19 Cont ID  
Sent By shill Date 2013-12-19 Time 15:11 Rev Time 0.00
Received By hmoser Date 2013-12-19 Time 15:11 Sent To  
Notes
2013-12-19 17:31:49REVIEW BY J SAEZ
 PX 1328
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-11-19 Cont ID  
Sent By skennedy Date 2013-11-19 Time 11:26 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 11:26 Sent To  
Notes
2013-11-19 11:30:58PLEASE PROVIDE A MECHANICAL PLAN SHOWING EXISTING OR
 PROPOSED MECHANICAL IMPROVEMENTS, PURSUANT TO:
 FBC 107.3.5.1.4 MECHANICAL, SHOW:
 EXHAUST SYSTEMS, EQUIPMENT & LOCATION. MAKE-UP AIR
 .ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS. VENTILATION,
 ETC.
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By lwagner Date 2013-12-10 Time 15:32 Rev Time 0.00
Received By lwagner Date 2013-12-09 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-30 Cont ID  
Sent By lwagner Date 2013-09-30 Time 13:19 Rev Time 0.00
Received By lwagner Date 2013-09-30 Time 12:45 Sent To  
Notes
2013-09-30 13:19:20FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 A1.01 SHOWS WHAT APPEARS TO BE NEW PLUMBING FIXTURES.
 IF THESE ARE NOT EXISTING FIXTURES, THEN A PLUMBING ISO
 DRAWINGS WILL BE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 3 Status P Date 2014-03-14 Cont ID  
Sent By eschneid Date 2014-03-14 Time 13:47 Rev Time 1.00
Received By eschneid Date 2014-03-14 Time 13:47 Sent To PC
Notes
2014-03-14 13:59:28PASSED W/PROVISO
  
 1) PRIOR TO THE ISSUANCE OF A FINAL (104) FOR THE
 BUILDING, THE APPLICANT SHALL PROVIDE THE PLANNING
 DIVISION WITH THE FINAL MINOR AMENDMENT PLANS ON A DISC
 IN .PDF FORMAT.
  
 2) PLEASE NOTE THAT SIGNAGE AND THE FENCES/GATES
 REQUIRES SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-01-14 Cont ID  
Sent By eschneid Date 2014-01-14 Time 11:26 Rev Time 0.00
Received By jwitmer Date 2014-02-20 Time 06:30 Sent To  
Notes
2014-01-14 11:39:07FAILED
  
 1) THIS PROPERTY IS ZONED COMMERCIAL PLANNED
 DEVELOPMENT, SO ANY CHANGES TO THE EXTERIOR OF THE SITE
 REQUIRE A PLANNED DEVELOPMENT AMENDMENT. THE MINOR
 AMENDMENT COMMENTS HAVE NOT BEEN SUFFICIENTLY ADDRESSED
 TO ISSUE AN APPROVAL LETTER OR FOR ZONING TO APPROVE
 THIS PERMIT APPLICATION.
  
 2) PERMIT NO. 13090825 IS ONLY FOR THE RENOVATION TO
 THE EXISTING BUILDINGS. AS STATED IN PREVIOUS COMMENTS,
 THE CITY DOES NOT REVIEW ALL OF THE WORK DESCRIBED,
 INCLUDING THE SITE WORK, PARKING, FENCING AND
 LANDSCAPING PLANS, ON THE SAME PERMIT AS THE WORK ON
 THE BUILDINGS. THE PLANS FOR THIS WORK HAVE BEEN
 REMOVED FROM THE PLANS SUBMITTED FOR PERMIT NO.
 13090825 FOR RETURN TO THE CONTRACTOR. SEPARATE PERMITS
 WITH PLANS, EACH WITH THE VALUE OF THE WORK APPLIED
 SEPARATELY, ARE REQUIRED FOR THE FOLLOWING:
  
 A. PARKING LOT, TO INCLUDE THE STRIPING.
 B. LANDSCAPE WORK. NOTE ANY TREE REMOVAL OR RELOCATION
 REQUIRES A TREE ALTERATION PERMIT.
 C. SIGNAGE
 D. FENCES AND GATES.
 E. TRASH ENCLOSURES.
 F. IRRIGATION.
 G. EXTERIOR SITE DEMOLITION
  
 THE ZONING REVIEW WILL BE CHANGED TO "PASS" WITH THE
 SUBMITTAL OF THE PERMITS FOR THE ITEMS IN LISTED IN 2)
 A, B, F AND G. THE COMMENTS LISTED BELOW RELATE TO THE
 EXTERIOR SITE IMPROVEMENTS THAT SHALL BE ADDRESSED AS
 PART OF THE INDIVIDUAL PERMITS LISTED IN 2) A. THROUGH
 G. PLEASE NOTE THAT MORE COMMENTS MAY BE GENERATED UPON
 SUBMITTAL OF THE INDIVIDUAL PERMITS.
  
 3) WHEN SUBMITTED, THE PERMITS FOR EXTERIOR WORK WILL
 REQUIRE THE SUBMITTAL OF TWO COPIES OF A RECENT SIGNED
 AND SEALED SURVEY, LESS THAN ONE YEAR OLD, SHOWING THE
 EXTERIOR FEATURES ON THE SITE. THE EXISTING CONDITIONS
 PLAN IS NOT A SURVEY. WHILE IT MAY INCLUDE THE BASE
 INFORMATION FROM A SURVEY, THE SURVEY SHALL BE
 SUBMITTED FOR VERIFICATION PURPOSES.
  
 4) THE PORTION OF THE PARKING LOT ALONG THE SOUTH
 PROPERTY LINE WHERE PAVEMENT IS BEING REMOVED SHALL BE
 REPLACED WITH LANDSCAPE IN ACCORDANCE WITH THE CITY'S
 LANDSCAPE REQUIREMENTS. THE PORTION IN THE RIGHT-OF-WAY
 SHALL BE REPLACED WITH SOD. THIS IS NOT CLEARLY SHOWN
 ON THE SUBMITTED LANDSCAPE SHEETS.
  
 5) THE PAVING AND GRADING PLAN STILL INCLUDES A TAG
 LINE WITH ?MILLING/OVERLAY LIMITS? WHICH SHALL BE
 REMOVED ON THE PARKING LOT PERMITS IF IT IS NOT TO
 OCCUR.
  
 6) THE AREAS WHERE THE PARKING LOT IS MODIFIED, TO
 INCLUDE THE NORTHWEST AREA REQUIRES COMPLIANCE WITH THE
 CITY?S LANDSCAPE REGULATIONS. THE LANDSCAPE PLAN WILL
 BE FULLY REVIEWED AS PART OF THE REQUIRED LANDSCAPE
 PERMIT. PLEASE NOTE THE FOLLOWING REPEAT COMMENTS:
  
 A) THE PLANS SHOW SABAL PALMS USED AS A PARKING LOT
 ISLAND TREE, WHICH REQUIRES A GROUPING OF THREE PALM
 TREES, NOT TWO PALM TREES. IF THREE SABAL PALMS DO NOT
 FIT, AND THUS ARE INAPPROPRIATE, USE A DIFFERENT PALM
 SPECIES WHICH COMPLIES WITH THE CITY?S REQUIREMENTS OR
 USE A SMALL SHADE TREE SUCH AS A DAHOON HOLLY.
  
 B) THE TREE PLANTING DIAGRAM SHALL CLEARLY INDICATE
 THAT THE TOP OF THE ROOTBALL SHALL BE ABOVE THE
 FINISHED GRADE. NO NOTE WAS ADDED TO THE TREE PLANTING
 DIAGRAM TO CALL THIS OUT (THE PALM PLANTING DIAGRAM
 DOES INCLUDE THE NOTE).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-12-05 15:36:4212/5/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By eschnied Date 2013-10-21 Time 14:56 Rev Time 2.00
Received By eschneid Date 2013-10-21 Time 14:56 Sent To  
Notes
2013-10-21 16:37:53FAILED
  
 1) IT IS UNCLEAR WHAT THE SCOPE OF WORK IS FOR THIS
 PERMIT. THE EXISTING CONDITIONS AND DEMOLITION PLAN
 SHOW FEATURES REMAINING THAT ARE NOT SHOWN ON THE OTHER
 PLANS. THE APPLICATION IS FOR "INTERIOR REMIX AND
 RENOVATION, EXTERIOR RENOVATION". THE CITY DOES NOT
 PERMIT ALL OF THE WORK DESCRIBED, INCLUDING THE SITE
 WORK, PARKING, FENCING AND LANDSCAPING PLANS, ON THE
 SAME PERMIT AS THE WORK ON THE BUILDINGS. SEPARATE
 PERMITS WITH PLANS, EACH WITH THE VALUE OF THE WORK
 APPLIED SEPARATELY, ARE REQUIRED FOR THE FOLLOWING:
  
 A. PARKING LOT, TO INCLUDE THE STRIPING.
 B. LANDSCAPE WORK. NOTE ANY TREE REMOVAL OR RELOCATION
 REQUIRES A TREE ALTERATION PERMIT.
 C. SIGNAGE
 D. FENCES AND GATES.
 E. TRASH ENCLOSURES.
 F. IRRIGATION.
  
 2) THE PERMITS FOR EXTERIOR WORK WILL REQUIRE THE
 SUBMITTAL OF TWO COPIES OF A RECENT SIGNED AND SEALED
 SURVEY, LESS THAN ONE YEAR OLD, SHOWING THE EXTERIOR
 FEATURES ON THE SITE.
  
 3) THIS PROPERTY IS ZONED COMMERCIAL PLANNED
 DEVELOPMENT, SO ANY CHANGES TO THE EXTERIOR OF THE SITE
 REQUIRE A PLANNED DEVELOPMENT AMENDMENT. WHILE AN
 AMENDMENT WAS FILED ON FEBRUARY 28, 2013, NONE OF THE
 COMMENTS ISSUED AT THE TIME WERE ADDRESSED. THIS PERMIT
 APPEARS TO SHOW DIFFERENT CONDITIONS FROM THE PLAN AT
 THE TIME OF THE AMENDMENT APPLICATION.
  
 4) THE PORTION OF THE PARKING LOT ALONG THE SOUTH
 PROPERTY LINE WHERE PAVEMENT IS BEING REMOVED WITHIN
 THE FIVE (5) FOOT WIDE LANDSCAPE BUFFER AREA MAY NOT BE
 FILLED IN WITH PAVEMENT, BUT RATHER SHALL COMPLY WITH
 THE CITY'S LANDSCAPE REQUIREMENTS.
  
 5) THE PAVING AND GRADING PLAN SHOWS AREAS OF THE
 PARKING LOT PROPOSED FOR MILLING AND OVERLAY. PLEASE
 CLEARLY DESIGNATE THESE AREAS ON THE PLANS. THESE AREAS
 ARE CONSIDERED NEW PARKING LOTS AND SHALL HAVE ALL THE
 REQUIRED LANDSCAPE INSTALLED IN COMPLIANCE WITH THE
 ZONING AND LAND DEVELOPMENT REGULATIONS. PLEASE NOTE
 THAT ANY AREAS WHERE THE PARKING LOT IS MODIFIED, TO
 INCLUDE THE NORTHWEST AREA REQUIRES LANDSCAPE
 COMPLIANCE AS WELL. THE LANDSCAPE PLAN SHALL VERIFY
 COMPLIANCE BY GRAPHIC AND TABULAR MEANS, NOT JUST
 "EXISTING LANDSCAPE TO REMAIN". THE LANDSCAPE PLAN WILL
 BE FULLY REVIEWED AS PART OF THE REQUIRED LANDSCAPE
 PERMIT.
  
 6) THE GENERAL NOTES ON THE LANDSCAPE PLAN REFER TO
 APPROVALS FROM NEW SMYRNA BEACH WHICH IS THE INCORRECT
 JURISDICTION.
  
 7) THE PARKING TABLE SHOWS THE CORRECT PARKING
 REQUIREMENTS, BUT THE PARKING HAS BEEN INCORRECTLY
 CALCULATED. PROVIDE A BREAKDOWN OF THE WAREHOUSE AND
 OFFICE SPACE ON THE PLANS..
  
 9) THE PARKING SPACE STRIPING DETAIL DOES NOT COMPLY
 WITH THE CITY STANDARDS. THERE SHALL BE TWO (2) FEET
 FROM THE BACK OF THE WHEEL STOP TO THE END OF THE
 PARKING SPACE. ADDITIONALLY, THE CITY REQUIRES THAT THE
 PARKING LOT STRIPES SHALL BE FOUR (4) INCHES WIDE AND
 SEPARATED BY 12 INCHES. THIS SHALL BE SHOW ON THE
 PARKING STRIPING DETAIL.
  
 10) THE PLANS SHOW SABAL PALMS USED AS A PARKING LOT
 ISLAND TREE, WHICH REQUIRES A GROUPING OF THREE PALM
 TREES, NOT TWO PALM TREES.
  
 11) THE TREE PLANTING DIAGRAM SHALL CLEARLY INDICATE
 THAT THE TOP OF THE ROOTBALL SHALL BE ABOVE THE
 FINISHED GRADE.
  
 12) THE TRASH ENCLOSURES DOES NOT COMPLY WITH THE
 CITY'S STANDARD DEPTH. PLEASE VERIFY THE ENCLOSURE SIZE
 WITH THE CITY'S SANITATION DIVISION.
  
 13) THE TRASH ENCLOSURE SHALL HAVE THE OPAQUE PANELS ON
 THE GATE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-09-30 10:46:189/30/13