Plan Review Details - Permit 13090825
Plan Review Stops For Permit 13090825 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2014-02-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-02-20 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-02-20 |
Time |
06:33 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2013-12-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2013-12-05 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2013-12-05 |
Time |
10:05 |
Sent To |
|
|
Notes |
2013-12-05 10:18:06 | BUILDING PLAN REVIEW | | PERMIT: 13090825 | | ADD: 1155 BELVEDERE RD | | CONT: TO BE DETERMINED/ FRITZ MASSON | | TEL: (954)710-1118 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: THURSDAY DEC. 05/ 2013 | | ACTION: DENIED | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA | | THE PLANS HAVE BEEN UPDATED TO THE CORRECT BUILDING | | CATEGORY II WITH ASSOCIATED WIND DESIGN OF 170 MPH, 3 | | SECOND GUST BUT THE EXPOSURE HAS CHANGED FROM THE FIRST | | REVIEW EXPOSURE "C" TO A EXPOSURE "B". THE CORRECT | | EXPOSURE IS A "C" EXPOSURE THAT WILL AFFECT THE | | PRESSURES AND PRODUCT APPROVALS. PLEASE REVIEW AND | | UPDATE POSITIVE AND NEGATIVE PRESSURES ACCORDINGLY, | | NOTE THERE IS A MULTIPLIER TO BE USED WITH A "C" | | EXPOSURE. | | | | | | | | 2) 2ND REQUEST. UPDATE THE WIND LOAD/ PRESSURE CHART, | | THIS CHART DOES NOT INDICATE IF THE AREA AFFECTED IS 10 | | SF, 20, 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS. | | 2010 FBC-B TABLE 1609. | | | | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 4) PRESSURES WILL BE AFFECTED BY THE C EXPOSURE, AGAIN | | THE COMMENT # 2 WAS NOT ADDRESSED THIS PORTION OF THE | | REVIEW CAN NOT HAPPEN WITH OUT THE PRESSURES BROKE OUT | | TO 10, 20, 50 OR 100 SQ FT. 2 010 FBC-B 1609.1.2 | | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & | | CLADDING | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | LOUVERS, EFIS SYSTEMS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | (E) SHUTTERS | | (F) SKYLIGHTS | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | STANDS | | | | 5) COMPLIED.. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-10-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2013-10-19 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2013-10-19 |
Time |
10:30 |
Sent To |
|
|
Notes |
2013-10-19 12:03:28 | BUILDING PLAN REVIEW | | PERMIT: 13090825 | | ADD: 1155 BELVEDERE RD | | CONT: TO BE DETERMINED/ FRITZ MASSON | | TEL: (954)710-1118 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SATURDAY OCT. 19/ 2013 | | ACTION: DENIED | | | | 1) SHEET S1.01 STRUCTURAL DESIN / WIND DESIGN CRITERIA | | INDICATES A BUILDING RISK CATEGORY I WITH WIND AT VULT | | 155 MPH/ 3 SECOND GUST. PLEASE REFER TO THE 2010 FBC-B | | TABLE 1604.5 RISK CATEGORY I BUILDINGS INCLUDE MINOR | | STORAGE FACILITIES, SHEDS, AGRICULTURAL FACILITIES & | | SCREEN ENCLOSURES. PLEASE UPDATE WIND DESIGN CRITEIA | | AND ASSOCIATED PRESSURES. | | | | 1604.5.1 MULTIPLE OCCUPANCIES. | | WHERE A BUILDING OR STRUCTURE IS OCCUPIED BY TWO OR | | MORE OCCUPANCIES NOT INCLUDED IN THE SAME RISK | | CATEGORY, IT SHALL BE ASSIGNED THE CLASSIFICATION OF | | THE HIGHEST RISK CATEGORY CORRESPONDING TO THE VARIOUS | | OCCUPANCIES. WHERE BUILDINGS OR STRUCTURES HAVE TWO OR | | MORE PORTIONS THAT ARE STRUCTURALLY SEPARATED, EACH | | PORTION SHALL BE SEPARATELY CLASSIFIED. WHERE A | | SEPARATED PORTION OF A BUILDING OR STRUCTURE PROVIDES | | REQUIRED ACCESS TO, REQUIRED EGRESS FROM OR SHARES LIFE | | SAFETY COMPONENTS WITH ANOTHER PORTION HAVING A HIGHER | | RISK CATEGORY, BOTH PORTIONS SHALL BE ASSIGNED TO THE | | HIGHER RISK CATEGORY. | | | | 2) UPDATE THE WIND LOAD/ PRESSURE CHART, THIS CHART | | DOES NOT INDICATE IF THE AREA AFFECTED IS 10 SF, 20, | | 50, OR 100 SF. NOR HEIGHT ADJUSTMENT FACTORS. 2010 | | FBC-B TABLE 1609. | | | | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 4) 2 010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.41 COMPONENTS & CLADDING | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS. | | (B) WINDOWS | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | LOUVERS, EFIS SYSTEMS, | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | (E) SHUTTERS | | (F) SKYLIGHTS | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | STANDS | | | | 5) SHEET S2.01 DETAIL # 14 TOWER DETAIL INDICATES THE | | STEEL STUD WALL SECTION BEING TIED DOWN TO THE 2X | | SOLLID BLOCKING BETWEEN THE JOIST BUT NO TIE DOEN TO | | THE CONCRETE WALL BENEATH, PART OF THE MWFRT, MAIN WIND | | FORCE RESISTING SYSSTEM. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-12-20 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-12-20 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-12-20 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-11-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-19 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-11-19 |
Time |
11:22 |
Sent To |
|
|
Notes |
2013-11-19 11:25:57 | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | PER FBC 107.3.5.1.2 ELECTRICAL PROVIDE AN ELECTRICAL | | PLAN DEMONSTRATING THE FOLLOWING: 1. ELECTRICAL WIRING, | | SERVICES, FEEDERS AND BRANCH CIRCUITS, OVERCURRENT | | PROTECTION,GROUNDING,WIRING METHODS AND MATERIALS, | | GFCIS; 2. EQUIPMENT; 3. SPECIAL OCCUPANCIES; 4. | | EMERGENCY SYSTEMS; 5. COMMUNICATION SYSTEMS; 6. LOW | | VOLTAGE; 7. LOAD CALCULATIONS | | STEVEN KENNEDY | | 561 805 6710 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2013-12-12 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2013-12-12 |
Time |
13:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2013-10-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2013-10-07 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2013-10-07 |
Time |
14:46 |
Sent To |
|
|
Notes |
2013-10-07 14:53:35 | THIS PLAN IS APPROVED WITH COMMENTS. | | | | THE EXIT SIGNS AND EMRGENCY LIGHTING LOCATIONS ARE NOT | | CLEARLY INDICATED ON THE PLAN. | | | | PER NFPA 101 LL ED. EXIT LIGHTS AND EMERGENCY LIGHTS | | ARE REQUIRED, CHAPTER 42.2.8.1 & 42.2.2.9. | | | | ANY FIRE ALARM OR FIRE SPRINKLER SYSTEM | | ALTERATIONS/ADDITIONS SHALL BECOMPLETED BY A CERTIFIED | | CONTRACTOR AND UNDER SEPARATE SHOP DRAWING PERMIT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-03-17 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-03-17 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-02-18 |
Time |
10:21 |
Sent To |
|
|
Notes |
2014-02-19 10:22:37 | RESUBMITTAL SENT TO J. WITMER'S DESK FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-01-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-01-14 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2013-11-27 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-11-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-19 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-09-25 |
Time |
18:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2013-12-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-12-19 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-12-19 |
Time |
15:11 |
Sent To |
|
|
Notes |
2013-12-19 17:31:49 | REVIEW BY J SAEZ | | PX 1328 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2013-11-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2013-11-19 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2013-11-19 |
Time |
11:26 |
Sent To |
|
|
Notes |
2013-11-19 11:30:58 | PLEASE PROVIDE A MECHANICAL PLAN SHOWING EXISTING OR | | PROPOSED MECHANICAL IMPROVEMENTS, PURSUANT TO: | | FBC 107.3.5.1.4 MECHANICAL, SHOW: | | EXHAUST SYSTEMS, EQUIPMENT & LOCATION. MAKE-UP AIR | | .ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS. VENTILATION, | | ETC. | | STEVEN KENNEDY | | 561 805 6710 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2013-12-10 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-12-10 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-12-09 |
Time |
14:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2013-09-30 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-09-30 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-09-30 |
Time |
12:45 |
Sent To |
|
|
Notes |
2013-09-30 13:19:20 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | A1.01 SHOWS WHAT APPEARS TO BE NEW PLUMBING FIXTURES. | | IF THESE ARE NOT EXISTING FIXTURES, THEN A PLUMBING ISO | | DRAWINGS WILL BE REQUIRED. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2014-03-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-03-14 |
Time |
13:47 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2014-03-14 |
Time |
13:47 |
Sent To |
PC |
|
Notes |
2014-03-14 13:59:28 | PASSED W/PROVISO | | | | 1) PRIOR TO THE ISSUANCE OF A FINAL (104) FOR THE | | BUILDING, THE APPLICANT SHALL PROVIDE THE PLANNING | | DIVISION WITH THE FINAL MINOR AMENDMENT PLANS ON A DISC | | IN .PDF FORMAT. | | | | 2) PLEASE NOTE THAT SIGNAGE AND THE FENCES/GATES | | REQUIRES SEPARATE PERMITS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2014-01-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-01-14 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-02-20 |
Time |
06:30 |
Sent To |
|
|
Notes |
2014-01-14 11:39:07 | FAILED | | | | 1) THIS PROPERTY IS ZONED COMMERCIAL PLANNED | | DEVELOPMENT, SO ANY CHANGES TO THE EXTERIOR OF THE SITE | | REQUIRE A PLANNED DEVELOPMENT AMENDMENT. THE MINOR | | AMENDMENT COMMENTS HAVE NOT BEEN SUFFICIENTLY ADDRESSED | | TO ISSUE AN APPROVAL LETTER OR FOR ZONING TO APPROVE | | THIS PERMIT APPLICATION. | | | | 2) PERMIT NO. 13090825 IS ONLY FOR THE RENOVATION TO | | THE EXISTING BUILDINGS. AS STATED IN PREVIOUS COMMENTS, | | THE CITY DOES NOT REVIEW ALL OF THE WORK DESCRIBED, | | INCLUDING THE SITE WORK, PARKING, FENCING AND | | LANDSCAPING PLANS, ON THE SAME PERMIT AS THE WORK ON | | THE BUILDINGS. THE PLANS FOR THIS WORK HAVE BEEN | | REMOVED FROM THE PLANS SUBMITTED FOR PERMIT NO. | | 13090825 FOR RETURN TO THE CONTRACTOR. SEPARATE PERMITS | | WITH PLANS, EACH WITH THE VALUE OF THE WORK APPLIED | | SEPARATELY, ARE REQUIRED FOR THE FOLLOWING: | | | | A. PARKING LOT, TO INCLUDE THE STRIPING. | | B. LANDSCAPE WORK. NOTE ANY TREE REMOVAL OR RELOCATION | | REQUIRES A TREE ALTERATION PERMIT. | | C. SIGNAGE | | D. FENCES AND GATES. | | E. TRASH ENCLOSURES. | | F. IRRIGATION. | | G. EXTERIOR SITE DEMOLITION | | | | THE ZONING REVIEW WILL BE CHANGED TO "PASS" WITH THE | | SUBMITTAL OF THE PERMITS FOR THE ITEMS IN LISTED IN 2) | | A, B, F AND G. THE COMMENTS LISTED BELOW RELATE TO THE | | EXTERIOR SITE IMPROVEMENTS THAT SHALL BE ADDRESSED AS | | PART OF THE INDIVIDUAL PERMITS LISTED IN 2) A. THROUGH | | G. PLEASE NOTE THAT MORE COMMENTS MAY BE GENERATED UPON | | SUBMITTAL OF THE INDIVIDUAL PERMITS. | | | | 3) WHEN SUBMITTED, THE PERMITS FOR EXTERIOR WORK WILL | | REQUIRE THE SUBMITTAL OF TWO COPIES OF A RECENT SIGNED | | AND SEALED SURVEY, LESS THAN ONE YEAR OLD, SHOWING THE | | EXTERIOR FEATURES ON THE SITE. THE EXISTING CONDITIONS | | PLAN IS NOT A SURVEY. WHILE IT MAY INCLUDE THE BASE | | INFORMATION FROM A SURVEY, THE SURVEY SHALL BE | | SUBMITTED FOR VERIFICATION PURPOSES. | | | | 4) THE PORTION OF THE PARKING LOT ALONG THE SOUTH | | PROPERTY LINE WHERE PAVEMENT IS BEING REMOVED SHALL BE | | REPLACED WITH LANDSCAPE IN ACCORDANCE WITH THE CITY'S | | LANDSCAPE REQUIREMENTS. THE PORTION IN THE RIGHT-OF-WAY | | SHALL BE REPLACED WITH SOD. THIS IS NOT CLEARLY SHOWN | | ON THE SUBMITTED LANDSCAPE SHEETS. | | | | 5) THE PAVING AND GRADING PLAN STILL INCLUDES A TAG | | LINE WITH ?MILLING/OVERLAY LIMITS? WHICH SHALL BE | | REMOVED ON THE PARKING LOT PERMITS IF IT IS NOT TO | | OCCUR. | | | | 6) THE AREAS WHERE THE PARKING LOT IS MODIFIED, TO | | INCLUDE THE NORTHWEST AREA REQUIRES COMPLIANCE WITH THE | | CITY?S LANDSCAPE REGULATIONS. THE LANDSCAPE PLAN WILL | | BE FULLY REVIEWED AS PART OF THE REQUIRED LANDSCAPE | | PERMIT. PLEASE NOTE THE FOLLOWING REPEAT COMMENTS: | | | | A) THE PLANS SHOW SABAL PALMS USED AS A PARKING LOT | | ISLAND TREE, WHICH REQUIRES A GROUPING OF THREE PALM | | TREES, NOT TWO PALM TREES. IF THREE SABAL PALMS DO NOT | | FIT, AND THUS ARE INAPPROPRIATE, USE A DIFFERENT PALM | | SPECIES WHICH COMPLIES WITH THE CITY?S REQUIREMENTS OR | | USE A SMALL SHADE TREE SUCH AS A DAHOON HOLLY. | | | | B) THE TREE PLANTING DIAGRAM SHALL CLEARLY INDICATE | | THAT THE TOP OF THE ROOTBALL SHALL BE ABOVE THE | | FINISHED GRADE. NO NOTE WAS ADDED TO THE TREE PLANTING | | DIAGRAM TO CALL THIS OUT (THE PALM PLANTING DIAGRAM | | DOES INCLUDE THE NOTE). | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | 2013-12-05 15:36:42 | 12/5/13 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2013-10-21 |
|
|
Cont ID |
|
Sent By |
eschnied |
Date |
2013-10-21 |
Time |
14:56 |
Rev Time |
2.00 |
Received By |
eschneid |
Date |
2013-10-21 |
Time |
14:56 |
Sent To |
|
|
Notes |
2013-10-21 16:37:53 | FAILED | | | | 1) IT IS UNCLEAR WHAT THE SCOPE OF WORK IS FOR THIS | | PERMIT. THE EXISTING CONDITIONS AND DEMOLITION PLAN | | SHOW FEATURES REMAINING THAT ARE NOT SHOWN ON THE OTHER | | PLANS. THE APPLICATION IS FOR "INTERIOR REMIX AND | | RENOVATION, EXTERIOR RENOVATION". THE CITY DOES NOT | | PERMIT ALL OF THE WORK DESCRIBED, INCLUDING THE SITE | | WORK, PARKING, FENCING AND LANDSCAPING PLANS, ON THE | | SAME PERMIT AS THE WORK ON THE BUILDINGS. SEPARATE | | PERMITS WITH PLANS, EACH WITH THE VALUE OF THE WORK | | APPLIED SEPARATELY, ARE REQUIRED FOR THE FOLLOWING: | | | | A. PARKING LOT, TO INCLUDE THE STRIPING. | | B. LANDSCAPE WORK. NOTE ANY TREE REMOVAL OR RELOCATION | | REQUIRES A TREE ALTERATION PERMIT. | | C. SIGNAGE | | D. FENCES AND GATES. | | E. TRASH ENCLOSURES. | | F. IRRIGATION. | | | | 2) THE PERMITS FOR EXTERIOR WORK WILL REQUIRE THE | | SUBMITTAL OF TWO COPIES OF A RECENT SIGNED AND SEALED | | SURVEY, LESS THAN ONE YEAR OLD, SHOWING THE EXTERIOR | | FEATURES ON THE SITE. | | | | 3) THIS PROPERTY IS ZONED COMMERCIAL PLANNED | | DEVELOPMENT, SO ANY CHANGES TO THE EXTERIOR OF THE SITE | | REQUIRE A PLANNED DEVELOPMENT AMENDMENT. WHILE AN | | AMENDMENT WAS FILED ON FEBRUARY 28, 2013, NONE OF THE | | COMMENTS ISSUED AT THE TIME WERE ADDRESSED. THIS PERMIT | | APPEARS TO SHOW DIFFERENT CONDITIONS FROM THE PLAN AT | | THE TIME OF THE AMENDMENT APPLICATION. | | | | 4) THE PORTION OF THE PARKING LOT ALONG THE SOUTH | | PROPERTY LINE WHERE PAVEMENT IS BEING REMOVED WITHIN | | THE FIVE (5) FOOT WIDE LANDSCAPE BUFFER AREA MAY NOT BE | | FILLED IN WITH PAVEMENT, BUT RATHER SHALL COMPLY WITH | | THE CITY'S LANDSCAPE REQUIREMENTS. | | | | 5) THE PAVING AND GRADING PLAN SHOWS AREAS OF THE | | PARKING LOT PROPOSED FOR MILLING AND OVERLAY. PLEASE | | CLEARLY DESIGNATE THESE AREAS ON THE PLANS. THESE AREAS | | ARE CONSIDERED NEW PARKING LOTS AND SHALL HAVE ALL THE | | REQUIRED LANDSCAPE INSTALLED IN COMPLIANCE WITH THE | | ZONING AND LAND DEVELOPMENT REGULATIONS. PLEASE NOTE | | THAT ANY AREAS WHERE THE PARKING LOT IS MODIFIED, TO | | INCLUDE THE NORTHWEST AREA REQUIRES LANDSCAPE | | COMPLIANCE AS WELL. THE LANDSCAPE PLAN SHALL VERIFY | | COMPLIANCE BY GRAPHIC AND TABULAR MEANS, NOT JUST | | "EXISTING LANDSCAPE TO REMAIN". THE LANDSCAPE PLAN WILL | | BE FULLY REVIEWED AS PART OF THE REQUIRED LANDSCAPE | | PERMIT. | | | | 6) THE GENERAL NOTES ON THE LANDSCAPE PLAN REFER TO | | APPROVALS FROM NEW SMYRNA BEACH WHICH IS THE INCORRECT | | JURISDICTION. | | | | 7) THE PARKING TABLE SHOWS THE CORRECT PARKING | | REQUIREMENTS, BUT THE PARKING HAS BEEN INCORRECTLY | | CALCULATED. PROVIDE A BREAKDOWN OF THE WAREHOUSE AND | | OFFICE SPACE ON THE PLANS.. | | | | 9) THE PARKING SPACE STRIPING DETAIL DOES NOT COMPLY | | WITH THE CITY STANDARDS. THERE SHALL BE TWO (2) FEET | | FROM THE BACK OF THE WHEEL STOP TO THE END OF THE | | PARKING SPACE. ADDITIONALLY, THE CITY REQUIRES THAT THE | | PARKING LOT STRIPES SHALL BE FOUR (4) INCHES WIDE AND | | SEPARATED BY 12 INCHES. THIS SHALL BE SHOW ON THE | | PARKING STRIPING DETAIL. | | | | 10) THE PLANS SHOW SABAL PALMS USED AS A PARKING LOT | | ISLAND TREE, WHICH REQUIRES A GROUPING OF THREE PALM | | TREES, NOT TWO PALM TREES. | | | | 11) THE TREE PLANTING DIAGRAM SHALL CLEARLY INDICATE | | THAT THE TOP OF THE ROOTBALL SHALL BE ABOVE THE | | FINISHED GRADE. | | | | 12) THE TRASH ENCLOSURES DOES NOT COMPLY WITH THE | | CITY'S STANDARD DEPTH. PLEASE VERIFY THE ENCLOSURE SIZE | | WITH THE CITY'S SANITATION DIVISION. | | | | 13) THE TRASH ENCLOSURE SHALL HAVE THE OPAQUE PANELS ON | | THE GATE. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | 2013-09-30 10:46:18 | 9/30/13 |
|
|
|