Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-09-26 Cont ID  
Sent By rmcdouga Date 2013-09-25 Time 15:31 Rev Time 0.00
Received By rmcdouga Date 2013-09-25 Time 15:19 Sent To  
Notes
2013-09-25 16:58:392010 FBC
  
 THE UPLIFT PRESSURES THAT ARE SPECIFIED ON THE FORM ARE
 LOW FOR A >0 TO 7 DEGREE ROOF WITH A 20' MRH LOCATED IN
 EXPOSURE C WITH A 170 MPH VULT / 132 VASD WIND-SPEED.
 FBC TABLE R301.2(2) AND TABLE R301.2(3) . RED-LINED
 CORRECTIONS WERE MADE TO ROOFING FORM.
  