Plan Review Details - Permit 13090799
Plan Review Stops For Permit 13090799
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-26 Cont ID  
Sent By wjolin Date 2013-09-26 Time 12:18 Rev Time 0.00
Received By wjolin Date 2013-09-26 Time 12:17 Sent To  
Notes
2013-09-26 12:18:00PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY
 MATERIAL.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-26 Cont ID  
Sent By wjolin Date 2013-09-26 Time 12:18 Rev Time 0.00
Received By wjolin Date 2013-09-25 Time 10:28 Sent To  
Notes
2013-09-25 10:29:00ROUTED TO TEMP TENTS