Plan Review Details - Permit 13090779
Plan Review Stops For Permit 13090779
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-11 Cont ID  
Sent By jgomez Date 2013-10-11 Time 11:10 Rev Time 0.00
Received By jgomez Date 2013-10-11 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 08:27 Rev Time 0.00
Received By shill Date 2013-09-25 Time 08:27 Sent To  
Notes
2013-09-25 08:33:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGN PRESSURES FOR THIS JOB (EXPOSURE C, 15' MRH)
 ARE -36.9, -63.6, AND -95.7 (ZONES 1, 2, AND 3
 RESPECTIVELY).
  
 THE ASSEMBLY SELECTED IS FOR -90PSF AND DOES NOT MEET
 THE MINIMUM REQUIREMENT FOR THE ZONE 3. THE NOTE WHICH
 STATES THAT ENHANCEMENT LETTER IS NOT REQUIRED AS THIS
 IS UNDER 400 SQUARE FEET IS NOT APPLICABLE AS
 COMPLIANCE IS REQUIRED BY FBC 2010 RESIDENTIAL 301.
  
 ENHANCED FASTENING TO BE SPECIFIED BY A DESIGN
 PROFESSIONAL, SEE #8 ON PAGE 2.
  