Plan Review Details - Permit 13090779
Plan Review Stops For Permit 13090779 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-10-11 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-10-11 |
Time |
11:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-09-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-09-25 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-09-25 |
Time |
08:27 |
Sent To |
|
|
Notes |
2013-09-25 08:33:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. DESIGN PRESSURES FOR THIS JOB (EXPOSURE C, 15' MRH) | | ARE -36.9, -63.6, AND -95.7 (ZONES 1, 2, AND 3 | | RESPECTIVELY). | | | | THE ASSEMBLY SELECTED IS FOR -90PSF AND DOES NOT MEET | | THE MINIMUM REQUIREMENT FOR THE ZONE 3. THE NOTE WHICH | | STATES THAT ENHANCEMENT LETTER IS NOT REQUIRED AS THIS | | IS UNDER 400 SQUARE FEET IS NOT APPLICABLE AS | | COMPLIANCE IS REQUIRED BY FBC 2010 RESIDENTIAL 301. | | | | ENHANCED FASTENING TO BE SPECIFIED BY A DESIGN | | PROFESSIONAL, SEE #8 ON PAGE 2. | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2013-10-09 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2013-10-09 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2013-09-24 |
Time |
15:04 |
Sent To |
|
|
Notes |
2013-09-24 15:05:04 | OK TO PASS PER F MITTNER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-10-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-10-11 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-10-11 |
Time |
11:10 |
Sent To |
|
|
Notes |
|
|
|