Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 10:06 Rev Time 0.00
Received By shill Date 2013-10-26 Time 10:06 Sent To  
Notes
2013-10-26 10:08:57ALUMINUM PANEL ONLY
  
 CLEAR PANEL REQUIRES A REVISION WITH INSTALLATION
 SCHEDULE AND PRODUCT APPROVAL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 18:36 Rev Time 0.00
Received By shill Date 2013-09-25 Time 18:36 Sent To  
Notes
2013-09-25 18:40:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGN PRESSURES APPEAR TOO LOW, PROVIDE
 CALCULATIONS AS TO HOW THESE PRESSURES HAVE BEEN
 DETERMINED. SEE TABLE FBC R 301.2.1.7 TO OBTAIN DESIGN
 PRESSURES. REVISE INSTALLATION SCHEDULE.
  
 2. UNABLE TO LOCATE ITW TAPCON ON THE ANCHOR CHARTS.
 PLEASE CIRCLE PROPOSED INSTALLATION AND REVISE
 INSTALLATION SCHEDULE. REGULAR TAPCON AND 410 SS TAPCON
 CANNOT BE USED IN DETAIL 1, TOP, TO MASONRY. 410 SS
 TAPCON CANNOT BE USED IN DETAIL 1, BOTTOM, TO MASONRY.
 REVISE INSTALLATION SCHEDULE.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 10:09 Rev Time 0.00
Received By shill Date 2013-10-26 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 18:40 Rev Time 0.00
Received By shill Date 2013-09-24 Time 16:57 Sent To  
Notes
2013-09-24 16:57:12TO SH DESK
  