2013-11-08 07:06:16 | REVISION |
| |
| 1) THE FIELD OBSERVATION REPORTS WERE GIVEN TO THE |
| CHIEF BUILDING INSPECTOR, KEN CONRAD, FOR HIS REVIEW. |
| |
| 2) THE SIGNED AND SEALED FOUNDATION REPAIR DRAWINGS ARE |
| READY FOR PICKUP. |
| |
| 3) THE THREE SHEETS OF PLANS A0, A01 AND A02 THAT WERE |
| SUBMITTED ARE DENIED. SEE NOTES BELOW. |
| |
| 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) SHEET A01 SPECIES DESIGN PARAMETERS BASED ON THE |
| 2007 FBC AND ASCE 7-08. THIS PERMIT WAS ISSUED UNDER |
| THE 2010 FBC AND ASCE 7-10. THE WIND SPEED FOR THE CITY |
| OF WEST PALM BEACH FOR A RISK CATEGORY II STRUCTURE IS |
| FOR THE 2010 FBC IS 170 MPH VULT / 132 MPH VASD. THE |
| WRONG EDITION OF ACI 315 WAS SPECIFIED. THE 2008 |
| EDITION OF ACI 315 IS REFERENCED BY THE 2010 FBC. |
| PLEASE CORRECT. |
| |
| 2) THE REVISED PLANS THAT WERE SUBMITTED ARE FROM A |
| DIFFERENT DESIGNER AND HAVE BEEN SIGNED AND SEALED BY A |
| DIFFERENT DESIGN PROFESSIONAL. SINCE THE ORIGINAL PLANS |
| ARE BEING REPLACED WITH NEW ONES, ALL OF THE |
| INFORMATION PROVIDED ON THE ORIGINAL PLANS WILL NEED TO |
| BE REPRODUCED ON THE NEW ONES. FS 471 AND FAC 61G15-27 |
| SHEET A01 GENERAL INFORMATION, CONTAINED THE PROJECT |
| DATA, APPLICABLE CODES, SCOPE OF WORK, VICINITY MAP, |
| SITE PLAN, ECT. |
| SHEET A02 FLOOR PLANS, CONTAINED THE DEMO FLOOR PLAN |
| AND PROPOSED FLOOR PLAN WITH THEIR RESPECTIVE SCHEDULES |
| AND NOTES. |
| SHEET E01 ELECRTICAL PLANS, CONTAINED THE PLUMBING |
| PLAN, PLUMBING RISER DIAGRAM, ELECTRICAL PLAN, LOAD |
| CALCULATIONS AND ELECTRICAL SYMBOL LEGEND. |
| THE TWO NEW SHEETS CONTAINING THE ELEVATIONS SHOULD BE |
| ASSIGNED NEW DRAWING NUMBERS SUCH AS A03 AND A04. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |