Plan Review Details - Permit 13090717
Plan Review Stops For Permit 13090717
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-13 Cont ID  
Sent By jwitmer Date 2013-11-13 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2013-11-13 Time 07:01 Sent To  
Notes
2013-11-13 07:53:21BUILDING PLAN REVIEW
 PERMIT: 13090717
 ADD: 700 S ROSEMARY # 102
 CONT: TO BE DETERMINED
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. NOV. 13/ 2013
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THE CONTRACTOR ELECTS TO BRING THESE PRODUCT APPROVALS
 IN AFTER PERMIT ISSUANCE, WILL BE CONSIDERED A
 REVISION, WITH SEPARATE REVIEW AND ASSOCIATED FEES.
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) SOFFITS & METAL CLADDING ON EXTERIOR WALLS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 12:30 Sent To  
Notes
2013-09-25 13:19:13BUILDING PLAN REVIEW
 PERMIT: 13090717
 ADD: 700 S ROSEMARY # 102
 CONT: TO BE DETERMINED
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 25/ 2013
 ACTION: DENIED
  
 2010 FBC-B 426.1 SCOPE.
 PUBLIC FOOD SERVICE ESTABLISHMENTS OR FOOD
 ESTABLISHMENTS SHALL COMPLY WITH DESIGN AND
 CONSTRUCTION STANDARDS AS DESCRIBED IN THE FOOD CODE,
 CHAPTER 509 PART I OR CHAPTER 500, FLORIDA STATUTES, AS
 APPLICABLE.
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 MAY APPLY. SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION (DBPR) RULE 61C-4, FLORIDA ADMINISTRATIVE
 CODE CHAPTER 500 AND CHAPTER 509, FLORIDA STATUTES.
  
  
 THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. THE PARKING GARAGE IS STILL PART OF THE SAME
 BUILDING, BEING 5 STORIES TALL IT CLASSIFIES THE TOTAL
 BUILDING AS "THRESHOLD BUILDING".
  
 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 3) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT
 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 4) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
 4.1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
 4.2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 5) THREE SETS OF ALL DOCUMENTS WILL BE REQUIRED FOR
 PERMIT ISSUANCE, PLANS & PRODUCT APPROVALS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) SOFFITS & METAL CLADDING ON EXTERIOR WALLS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-17 Cont ID  
Sent By dharvey Date 2013-10-17 Time 09:05 Rev Time 0.00
Received By dharvey Date 2013-10-17 Time 06:52 Sent To B
Notes
2013-10-17 09:05:25SHEET E1.0 INDICATES #6 ISOLATED GROUND FROM XFORMER
 AND BETWEEN PANELBOARDS. PLEASE INDICATE METHODS OF
 COMPLIANCE WITH 250.30, 250 PART III, 250.58, 250.104,
 PROVIDE STROBES IN BATHROOMS. PLANS NOTED AND APPROVED.
 GIVEN TO J WITMER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-28 Cont ID  
Sent By wjolin Date 2013-09-28 Time 09:32 Rev Time 0.00
Received By wjolin Date 2013-09-28 Time 09:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-10-03 Cont ID  
Sent By lwagner Date 2013-10-03 Time 10:05 Rev Time 0.00
Received By lwagner Date 2013-10-03 Time 09:49 Sent To  
Notes
2013-10-03 10:06:21GAS PERMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-13 Cont ID  
Sent By jwitmer Date 2013-11-13 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2013-11-05 Time 12:13 Sent To  
Notes
2013-11-05 12:29:34C04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-17 Cont ID  
Sent By dharvey Date 2013-10-17 Time 09:05 Rev Time 0.00
Received By dharvey Date 2013-09-23 Time 09:04 Sent To  
Notes
2013-09-24 09:04:32SENT TO C2 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-11-12 Cont ID  
Sent By hmoser Date 2013-11-12 Time 09:21 Rev Time 0.00
Received By hmoser Date 2013-11-08 Time 13:42 Sent To  
Notes
2013-11-12 09:21:10KITCHEN HOOD IS NOT INCLUDED IN THIS REVIEW.
 SEPARATE PERMIT APPLICATION AND PLAN REVIEW
 ARE REQUIRED.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-09 Cont ID  
Sent By hmoser Date 2013-10-09 Time 09:59 Rev Time 0.00
Received By hmoser Date 2013-10-09 Time 07:55 Sent To  
Notes
2013-10-09 09:59:52PLANS DENIED
 1) NOTE # 1 AND 9 CONFLICT EACH OTHER ON PAGE M-1.0
 OF THE PLANS.
 2) REFER TO SECTION 503.2.44 SHUT OFF DAMPER CONTROLS
 ( FOR FRESH AIR AND EXHAUST ) 2010 FLORIDA ENERGY CODE.
 3) PROVIDE CHILLED WATER PIPING PLAN ON MECHANICAL
 PLANS
 PER SECTION 107 FBC 2010
 4) SEPARATE APPLICATION, PLANS AND PERMIT REQUIRED FOR
 GREASE HOOD , COOLERS AND FIRE SUPPRESSION FOR GREASE
 HOOD .
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-03 Cont ID  
Sent By lwagner Date 2013-10-03 Time 10:06 Rev Time 0.00
Received By lwagner Date 2013-10-02 Time 13:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-01 Cont ID  
Sent By eschneid Date 2013-10-01 Time 18:52 Rev Time 0.50
Received By eschneid Date 2013-10-01 Time 18:52 Sent To  
Notes
2013-10-01 18:53:34THE SIGN AND AWNING REQUIRE SEPARATE PERMITS WITH
 PLANS.
  
 PLEASE NOTE THAT INTERNALLY ILLUMINATED BOX SIGNS ARE
 NOT PERMITTED WITHIN CITYPLACE.
2013-09-24 10:29:169/24/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved