Plan Review Details - Permit 13090669
Plan Review Stops For Permit 13090669
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-27 Cont ID  
Sent By albarran Date 2013-11-27 Time 12:12 Rev Time 0.00
Received By albarran Date 2013-11-27 Time 11:53 Sent To I
Notes
2013-11-27 12:22:17SENT TO SH DESK
2013-11-27 12:21:28PROVISIOS:
 1. THE SCOPE OF THIS PERMIT IS AS INDICATED ON THE
 PERMIT APPLICATION, TO REMOVE AND REPLACE BROKEN METER
 SOCKET AND RISER PIPE. IF THE REMOVAL OF THE METER
 SOCKET CREATES A SITUATION WHERE THE FEEDERS MUST BE
 REPLACED, THE NEW WIRING, REGARDLESS OF WHAT IS
 EXISTING, SHALL BE IN ACCORDANCE WITH THE CURRENT
 EDITION OF THE NEC.
 2. ALL GROUNDING SYSTEM SHALL BE REPLACED AND MADE
 CURRENT, INCLUDING THE INSTALLATION OF THE INTER-SYSTEM
 BONDING TERMINAL REQUIRED BY NEC 250.94.
 3. ALL WORK SHALL COMPLY WITH ALL REQUIREMENTS OF THE
 2008 EDITION OF THE NEC AND IS SUBJECT TO THE APPROVAL
 OF THE FIELD INSPECTOR.
2013-11-27 11:54:52THE CONTRACTOR CALLED IN THIS MORNING ALLEGING THAT
 DOUG HAD ALREADY SIGNED OFF ON THIS PERMIT, BUT THE
 RECORDS DO NOT REFLECT SUCH. I WILL ONCE AGAIN LOOK AT
 THE SUBMITTAL AND EVALUATE THE CIRCUMSTANCES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-26 Cont ID  
Sent By dharvey Date 2013-09-26 Time 15:04 Rev Time 0.00
Received By dharvey Date 2013-09-26 Time 14:52 Sent To  
Notes
2013-09-26 15:08:1613090669
 4000 GREEN WOOD
 NEW ELECTRIC SERVICE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW LOCATION OF ALL SERVICE DISCONNECTS. A BUILDING OR
 OTHER STRUCTURE SERVED SHALL BE SUPPLIED BY ONLY ONE
 SERVICE. MAIN DISCONNECTS ARE REQUIRED TO BE GROUPED IN
 ONE LOCATION. NEC 230.2
  
 SERVICE CONDUCTORS NEED TO BE RATED FOR WET LOCATION.
 NEC 310.10
  
 INDICATE THE SIZE, RATING, AND LOCATION OF THE EXISTING
 PANEL BOARDS. INDICATE SIZE OF PANEL FEEDERS. NEC 215.5
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. FBC R313
  
 A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-02 Cont ID  
Sent By shill Date 2013-09-26 Time 10:18 Rev Time  
Received By shill Date 2013-09-20 Time   Sent To  
Notes
2013-09-20 15:43:32<5000 ELEC


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved