Plan Review Details - Permit 13090565
Plan Review Stops For Permit 13090565
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-26 Cont ID  
Sent By JWITMER Date 2013-10-26 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2013-10-26 Time 06:02 Sent To  
Notes
2013-10-26 06:40:0661G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION CODE, 2010 EDITION,
 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION...
  
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE
  
 SITE ADDRESS: 4105 MILLER AVE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-10-23 Cont ID  
Sent By jwitmer Date 2013-10-23 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2013-10-23 Time 16:40 Sent To  
Notes
2013-10-23 16:49:38BUILDING PLAN REVIEW
 PERMIT: 13090565
 ADD: 4105 MILLER AVENUE
 CONT: TO BE DETERMINED
 TEL: (954) 978-9300
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: OCT. 23/ 2013
 ACTION: DENIED
  
 1) THE PLANS DO NOT PROVIDE AN ADDRESS WHERE THE
 LOCATION OF WORK IS TO BE COMPLETED. * 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 2010 EDITION 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF WORK TO BE COMPLETED...
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-01 Cont ID  
Sent By jwitmer Date 2013-10-01 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2013-10-01 Time 11:09 Sent To  
Notes
2013-10-01 11:24:36ON THE STATE APPROVED PLANS SALF01 THE PLANS INDICATE
 THERE ARE THREE BUILDING TYPE PLANS INCLUDED UNDER THE
 STATE APPROVAL, BLDG-A, BLDG-B & BLDG TYPE BLDG-C
 PLEASE CIRCLE WHICH BUILDING TYPE WILL BE INSTALLED AND
 THE APPROPRIATE SHEETS FOR THIS BUILDING TYPE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-22 Cont ID  
Sent By albarran Date 2013-10-22 Time 14:11 Rev Time 0.00
Received By albarran Date 2013-10-22 Time 13:30 Sent To  
Notes
2013-10-22 14:17:29THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO THE
 DIRECTIONAL BORING FOR THE CONNECTION OF MULTIPLE
 PRE-SELECTED AND INSTALLED EQUIPMENT AS WELL AS THE ON
 SITE INSTALLATION OF THE LIGHTNING PROTECTION.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2013-10-29 Cont ID  
Sent By MGONZALE Date 2013-10-29 Time   Rev Time 1.00
Received By mgonzale Date 2013-10-29 Time   Sent To I
Notes
2013-10-28 23:59:55PROVISOS:
  
 1. NEW FENCE ALONG NORTH PROPERTY LINE APPEARS TO LIE
 OUTSIDE OF PARCEL IN SOUTHERN BLVD. R/W. SUBMIT CORRECT
 LOCATION UNDER A FENCE PERMIT.
 2. CHANGE ELEVATIONS TO CITY DATUM OF NGVD-29, SUBMIT
 CORRECTION TO ENGINEERING SERVICES - REFERENCE
 TRANSMITTAL - JURISDICTIONAL REVIEW.
 3. ADD TWO PROPOSED X-SECTIONS EAST-WEST AND
 NORTH-SOUTH OF THE PROPERTY, SUBMIT CORRECTION TO
 ENGINEERING SERVICES - REFERENCE TRANSMITTAL -
 JURISDICTIONAL REVIEW.
 4. SUBMIT DRAINAGE CALCULATIONS REVISION IN RESPONSE TO
 COMMENTS AS PER CITY STORMWATER ENGINEER AT ENGINEERING
 SERVICES - REFERENCE TRANSMITTAL - JURISDICTIONAL
 REVIEW.
 C/O WILL NOT BE ISSUED WITHOUT THIS SUBMISSION AND
 APPROVAL.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2013-10-22 Cont ID  
Sent By Mgonzale Date 2013-10-22 Time   Rev Time 1.00
Received By mgonzale Date 2013-10-22 Time   Sent To E
Notes
2013-10-22 12:56:46PROVISOS:
  
 1. NEW FENCE ALONG NORTH PROPERTY LINE APPEARS TO LIE
 OUTSIDE OF PARCEL IN SOUTHERN BLVD. R/W. SUBMIT CORRECT
 LOCATION UNDER A FENCE PERMIT.
 2. CHANGE ELEVATIONS TO CITY DATUM OF NGVD-29, SUBMIT
 CORRECTION TO ENGINEERING SERVICES - REFERENCE
 TRANSMITTAL - JURISDICTIONAL REVIEW.
 3. ADD TWO PROPOSED X-SECTIONS EAST-WEST AND
 NORTH-SOUTH OF THE PROPERTY, SUBMIT CORRECTION TO
 ENGINEERING SERVICES - REFERENCE TRANSMITTAL -
 JURISDICTIONAL REVIEW.
 4. SUBMIT DRAINAGE CALCULATIONS REVISION IN RESPONSE TO
 COMMENTS AS PER CITY STORMWATER ENGINEER AT ENGINEERING
 SERVICES - REFERENCE TRANSMITTAL - JURISDICTIONAL
 REVIEW.
 C/O WILL NOT BE ISSUED WITHOUT THIS SUBMISSION AND
 APPROVAL.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-28 Cont ID  
Sent By WJOLIN Date 2013-10-28 Time 14:01 Rev Time 0.00
Received By rferguso Date 2013-10-28 Time 14:01 Sent To  
Notes
2013-10-28 14:21:504105 MILLER AVE
 PERMIT #13090565
  
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 * PLAN OK (PROVSO), AS PREVIOUSLY NOTED, THE COMPLTE
 ADDRESS MUST BE PLACED IN THE TITAL BLOCK OF THE WORK
 LOCATION SITE PLANS E-01 THRU E-08.
  
  
 RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4700

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-28 Cont ID  
Sent By wjolin Date 2013-09-28 Time 10:50 Rev Time 0.00
Received By wjolin Date 2013-09-28 Time 10:16 Sent To  
Notes
2013-09-28 10:50:314105 MILLER AVENUE
 PERMIT #13090565
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT DOORS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL BE APPROPRIATE FOR HAZARD BEING PROTECTED AND
 SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 DESIGN SHALL CONFORM TO NFPA 1 (2009 EDITION) CHAPTER
 52 - STATIONARY STORAGE BATTERY SYSTEMS. SOME OF THE
 REQUIREMENTS ARE INDICATED BELOW:
  
 52.3.10 SMOKE DETECTION. AN APPROVED AUTOMATIC SMOKE
 DETECTION SYSTEM SHALL BE INSTALLED IN SUCH AREAS AND
 SUPERVISED BY AN APPROVED CENTRAL, PROPRIETARY, OR
 REMOTE STATION SERVICE OR A LOCAL ALARM THAT WILL GIVE
 AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
  
 52.3.8.1 DOORS OR ACCESSES INTO ROOMS, BUILDINGS, OR
 AREAS CONTAINING STATIONARY STORAGE BATTERY SYSTEMS
 SHALL BE PROVIDED WITH APPROVED SIGNS. THE SIGNS SHALL
 STATE THAT THE ROOM CONTAINS STATIONARY STORAGE BATTERY
 SYSTEMS, THAT THE BATTERY ROOM CONTAINS ENERGIZED
 ELECTRICAL CIRCUITS, AND THAT THE BATTERY ELECTROLYTE,
 WHERE PRESENT, ARE CORROSIVE LIQUIDS. BATTERY CABINETS
 SHALL BE PROVIDED WITH EXTERIOR LABELS THAT IDENTIFY
 THE MANUFACTURER AND MODEL NUMBER OF THE SYSTEM AND
 ELECTRICAL RATING (VOLTAGE AND CURRENT) OF THE
 CONTAINED BATTERY SYSTEM. SIGNS SHALL BE PROVIDED
 WITHIN BATTERY CABINETS TO INDICATE THE RELEVANT
 ELECTRICAL, CHEMICAL, AND FIRE HAZARD.
  
 52.3.6 VENTILATION. FOR FLOODED LEAD-ACID, FLOODED
 NICKEL-CADMIUM, AND VRLA BATTERIES, VENTILATION SHALL
 BE PROVIDED FOR ROOMS AND CABINETS IN ACCORDANCE WITH
 THE MECHANICAL CODE AND ONE OF THE FOLLOWING: (1) THE
 VENTILATION SYSTEM SHALL BE DESIGNED TO LIMIT THE
 MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF THE
 TOTAL VOLUME OF THE ROOM DURING THE WORST-CASE EVENT OF
 SIMULTANEOUS ?BOOST? CHARGING OF ALL THE BATTERIES, IN
 ACCORDANCE WITH NATIONALLY RECOGNIZED STANDARDS. (2)
 CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE OF
 NOT LESS THAN 1 FT3/MIN/FT2 (5.1 L/SEC/M2) OF FLOOR
 AREA OF THE ROOM OR CABINET.
  
 52.3.5 NEUTRALIZATION. AN APPROVED METHOD TO NEUTRALIZE
 SPILLED ELECTROLYTE SHALL BE PROVIDED.
  
 52.3.4 SPILL CONTROL. ROOMS, BUILDINGS, OR AREAS
 CONTAINING FREE-FLOWING LIQUID ELECTROLYTE IN
 INDIVIDUAL VESSELS HAVING A CAPACITY OF MORE THAN 55
 GAL (208 L) OR MULTIPLE VESSELS HAVING AN AGGREGATE
 CAPACITY EXCEEDING 1000 GAL (3785 L) SHALL BE PROVIDED
 WITH SPILL CONTROL TO PREVENT THE FLOW OF LIQUIDS TO
 ADJOINING AREAS.
  
 52.3.2 THERMAL RUNAWAY. VRLA, LITHIUM-ION, AND LITHIUM
 METAL POLYMER BATTERY SYSTEMS SHALL BE PROVIDED WITH A
 LISTED DEVICE OR OTHER APPROVED METHOD TO PRECLUDE,
 DETECT, AND CONTROL THERMAL RUNAWAY.
  
 SEPARATE PLANS AND PERMITS NEEDED FOR EMERGENCY
 GENERATOR AND DIESEL FUEL TANK.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-29 Cont ID  
Sent By shill Date 2013-10-29 Time 09:09 Rev Time 0.00
Received By shill Date 2013-10-24 Time 17:04 Sent To  
Notes
2013-10-24 17:04:47B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-22 Cont ID  
Sent By albarran Date 2013-10-22 Time 16:17 Rev Time 0.00
Received By rbrown Date 2013-09-18 Time 18:05 Sent To  
Notes
2013-09-19 18:06:54C11

Review Stop Z ZONING
Rev No 2 Status P Date 2013-10-28 Cont ID  
Sent By AJONES Date 2013-10-28 Time 16:29 Rev Time 0.00
Received By ajones Date 2013-10-28 Time 16:29 Sent To  
Notes
2013-10-28 16:46:3210/28/13 - APPROVED WITH THE FOLLOWING PROVISO:
  
 1. A SEPERATE FENCE PERMIT WILL BE REQUIRED. THE SITE
 PLAN SHOWS THE PROPOSED FENCE IN THE SOUTHERN BOULEVARD
 ROW.
 2. A SEPERATE LANDSCAPE PERMIT WILL BE REQUIRED.
 3. A SEPERATE PERMIT WILL BE REQUIRED FOR ALL
 GENERATORS AND FUEL TANKS. THE ZONING REGULATIONS
 REQUIRED THAT ALL GENERATORS AND FUEL TANKS BE SCREENED
 WITH A SOLID WALL OR FENCE WITH LANDSCAPING.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2013-09-24 Cont ID  
Sent By avann Date 2013-09-24 Time 17:16 Rev Time 0.00
Received By ajones Date 2013-09-24 Time 17:16 Sent To  
Notes
2013-09-24 17:20:029/24/13- SEC. 94-35 OF THE ZONING AND LAND DEVELOMENT
 REGULATIONS REQUIRES SITE PLAN REVIEW AND APPROVAL
 THROUGH THE PLANNING DIVISION FOR ALL NEW CONSTRUCTION
 EXCEEDING 1,000 SQ. FT.
  
 ANGELLA VANN
 561-822-1441
 [email protected]
2013-09-20 11:07:259/20/13