Plan Review Details - Permit 13090535
Plan Review Stops For Permit 13090535 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2013-10-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2013-10-01 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2013-10-01 |
Time |
12:10 |
Sent To |
|
|
Notes |
2013-10-01 12:40:07 | PASSED. | | 2010 EXT BLDG CODE 701.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 2010 FBC-B 709.1 EXCEPTION # 4. OTHER THAN DWELLING | | UNITS OR SLEEPING UNITS, WALLS USED TO SEPARATE | | INDIVIDUAL TENANT SPACES SHALL NOT BE REQUIRED TO HAVE | | A FIRE-RESISTANCE RATING WHEN THE BUILDING IS PROTECTED | | BY A COMPLETE AUTOMATIC SPRINKLER SYSTEM INSTALLED IN | | ACCORDANCE WITH SECTION 903.3.1.1 | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2013-10-28 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2013-10-28 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2013-10-28 |
Time |
14:13 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2013-10-07 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2013-10-07 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2013-10-07 |
Time |
14:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-10-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-10-28 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-09-18 |
Time |
06:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2013-10-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2013-10-01 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2013-10-01 |
Time |
12:40 |
Sent To |
|
|
Notes |
2013-10-01 12:40:57 | PASSED. | | 2010 EXT BLDG CODE 701.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 2010 FBC-B 709.1 EXCEPTION # 4. OTHER THAN DWELLING | | UNITS OR SLEEPING UNITS, WALLS USED TO SEPARATE | | INDIVIDUAL TENANT SPACES SHALL NOT BE REQUIRED TO HAVE | | A FIRE-RESISTANCE RATING WHEN THE BUILDING IS PROTECTED | | BY A COMPLETE AUTOMATIC SPRINKLER SYSTEM INSTALLED IN | | ACCORDANCE WITH SECTION 903.3.1.1 | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2013-09-20 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-09-20 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-09-20 |
Time |
14:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2013-09-20 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2013-09-20 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2013-09-20 |
Time |
11:13 |
Sent To |
|
|
Notes |
|
|
|