Plan Review Details - Permit 13090531
Plan Review Stops For Permit 13090531 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-10-10 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-10 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-10 |
Time |
08:29 |
Sent To |
|
|
Notes |
2013-10-10 09:19:55 | REVIEWED BY WDS. | | ENGINEERS RESPONES FOR COMMENTS ARE ATTACHED TO | | ELECTRICAL PLANS. 10-10-2013. | | TO S HILL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-09-25 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-09-25 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-09-25 |
Time |
14:58 |
Sent To |
|
|
Notes |
2013-09-25 15:01:58 | REVIEWED - 9-25-13 | | | | 1. WHERE IS PANEL AC1 LOCATED? HOW FAR FROM NEW | | LOCATION? | | 2. IS CONDUIT RUN EXPOSED ON ROOF TOP? IF SO, A | | TEMPEATURE DERATING MAY BE REQUIRED FOR THE CONDUCTORS | | 3. IF PVC IS USED, EXPANSION FITTINGS ARE REQUIRED | | 4. HAS VOLTAGE DROP BEEN ADDRESSED? DISTANCE IS | | INCREASED. | | VB | | | | 10-10-2013 COMMENTS ADDRESS AND ELECTRCIAL APPROVED. | | REVIEWED BY WDS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-10-10 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-10-10 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-10-03 |
Time |
06:44 |
Sent To |
|
|
Notes |
2013-10-10 09:20:44 | TO S HILL. | | | 2013-10-05 06:45:21 | SENT TO ELECTRICAL BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-09-26 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-09-26 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-09-18 |
Time |
17:34 |
Sent To |
|
|
Notes |
2013-09-19 17:34:49 | SENT TO MECHANICAL BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2013-09-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-09-24 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-09-24 |
Time |
14:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2013-09-26 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2013-09-26 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2013-09-26 |
Time |
14:34 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy