Plan Review Details - Permit 13090401
Plan Review Stops For Permit 13090401
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-23 Cont ID  
Sent By lphilmor Date 2013-09-23 Time 13:17 Rev Time 0.00
Received By lphilmor Date 2013-09-23 Time 13:15 Sent To  
Notes
2013-09-23 13:17:19105 EVERNIA ST
 PERMIT # 13090401
 REIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-26 Cont ID  
Sent By wjolin Date 2013-09-26 Time 12:00 Rev Time 0.00
Received By wjolin Date 2013-09-13 Time 14:43 Sent To  
Notes
2013-09-13 14:43:34ROUTED TO TEMP TENTS