Plan Review Details - Permit 13090220
Plan Review Stops For Permit 13090220
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-09-13 Cont ID  
Sent By jwitmer Date 2013-09-13 Time 14:43 Rev Time 0.00
Received By jwitmer Date 2013-09-13 Time 13:05 Sent To  
Notes
2013-09-13 13:47:04BUILDING PLAN REVIEW
 PERMIT: 13090220
 ADD: 2616 TAMERIND AVE
 CONT: KARNS & BALDWIN
 TEL: (561)805-7528
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT. 13/ 2013
 ACTION: PROVISO
  
 1) RESTROOMS THE MINIMUM DIMENSION FOR RESTROOM 7'-1"
 SEE 2010 FL ACCESSIBILITY CODE 604.3.2. OVERLAP. NO
 OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN
 THE REQUIRED WATER CLOSET CLEARANCE. OK, TO RED LINE I
 SPOKE WITH DESIGNER OF RECORD MARK MCCREE.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-15 Cont ID  
Sent By dharvey Date 2013-11-15 Time 06:54 Rev Time 0.00
Received By dharvey Date 2013-11-05 Time 16:45 Sent To  
Notes
2013-11-05 17:03:58ARE PANELBOARD BUS STABS RATED FOR 150A BRANCH BREAKER?
 PLAN SHOWS STAIRS TO LEVEL 2 BUT NO DETAILS - ON
 ORIGINAL SUBMISSION
 DEPENDING ON CONFIGURATION AND LAYOUT, ADDITONAL EM
 LIGHTS MAY BE REQUIRED FOR SAFETY AROUND MACHINERY AND
 FOR EXITING
 WHERE IS PANEL A-2-C AND WHAT ARE THE LOADS? - ON
 ORIGINAL SUBMISSION
 ELECTRICAL LOAD CALCULATION REQUIRED SHOWING MOTOR
 LOADS, MACHINERY LABELS AND LOADS, CONTINUOUS LOADS AT
 125%
 PROVIDE ENERGY CODE CALCULATION FOR ENERGY BUDGET AND
 CONSUMPTION
 SMOKE DETECTORS ARE SHOWN ON PLANS AND NO FACP IS
 INDICATED, PLEASE EXPLAIN THE DESIGN OF THE SYSTEM
 #6 CONDUCTORS NOT RATED 80 AMPS (MILL #1)
 WATER FOUNTAIN RECEPTACLE TO BE INDICATED AS GFCI OR
 GFCI PROTECTED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By dharvey Date 2013-09-25 Time 17:51 Rev Time 0.00
Received By dharvey Date 2013-09-25 Time 17:51 Sent To  
Notes
2013-09-25 17:53:559-25-13
 FIRST REVIEW
  
 1. SCOPE OF WORK ON PERMIT APPLICATION STATES REMODEL 2
 BATHROOMS. IT APPEARS THERE IS MORE WORK THAN THAT.
  
 2. ARE PANELS EXISTING? IS LIGHTING EXISTING? IT
 APPEARS THERE ARE NEW CIRCUITS.
  
 3. IF OVER 5000SQ FT, MUST HAVE LIGHTING CONTROLS
  
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By wjolin Date 2013-09-12 Time 13:33 Rev Time 0.00
Received By wjolin Date 2013-09-12 Time 13:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-15 Cont ID  
Sent By dharvey Date 2013-11-15 Time 06:54 Rev Time 0.00
Received By shill Date 2013-10-16 Time 09:29 Sent To  
Notes
2013-10-17 09:30:09SENT TO ELECTRICAL SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-04 Cont ID  
Sent By hmoser Date 2013-10-04 Time 12:19 Rev Time 0.00
Received By hmoser Date 2013-09-09 Time 07:32 Sent To  
Notes
2013-09-10 07:33:26B14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-04 Cont ID  
Sent By hmoser Date 2013-10-04 Time 12:19 Rev Time 0.00
Received By hmoser Date 2013-10-04 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By lwagner Date 2013-09-16 Time 14:47 Rev Time 0.00
Received By lwagner Date 2013-09-16 Time 14:35 Sent To  
Notes
***NONE***