Plan Review Details - Permit 13090105
Plan Review Stops For Permit 13090105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-13 Cont ID  
Sent By rmcdouga Date 2013-09-13 Time 13:17 Rev Time 0.00
Received By rmcdouga Date 2013-09-13 Time 13:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By rmcdouga Date 2013-09-05 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2013-09-05 Time 17:52 Sent To  
Notes
2013-09-05 18:09:57DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT / 132
 VASD WIND SPEED AND THE EXPOSURE CATEGORY IS C. SPECIFY
 THE APPROVED ASSEMBLY, FASTENING OPTION AND MAXIMUM
 DESIGN PRESSURE FROM THE GAF BUR PRODUCT APPROVAL (NOA
 NO. 07-1219.09) THAT WILL BE INSTALLED. FBC R301.2.1
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FOR CORNER AND
 PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 19 OF THE GAF BUR NOA. FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]