Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2013-09-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-09-05 |
Time |
18:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-09-05 |
Time |
17:52 |
Sent To |
|
|
Notes |
2013-09-05 18:09:57 | DENIED BY BUILDING | | | | 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT / 132 | | VASD WIND SPEED AND THE EXPOSURE CATEGORY IS C. SPECIFY | | THE APPROVED ASSEMBLY, FASTENING OPTION AND MAXIMUM | | DESIGN PRESSURE FROM THE GAF BUR PRODUCT APPROVAL (NOA | | NO. 07-1219.09) THAT WILL BE INSTALLED. FBC R301.2.1 | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR ENHANCED FASTENING FOR CORNER AND | | PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION NUMBER 7 | | ON PAGE 19 OF THE GAF BUR NOA. FBC R301.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
|