Plan Review Details - Permit 13090082
Plan Review Stops For Permit 13090082
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-02-05 Cont ID  
Sent By albarran Date 2014-02-05 Time 19:41 Rev Time 0.00
Received By albarran Date 2014-02-05 Time 19:11 Sent To FIRE
Notes
2014-02-05 19:43:33PRIOR COMMENTS WERE ADDRESSED AND CORRECTED ON THE
 REVISED SHEET.
  
 I ROUTED THIS TO FIRE SO THAT WES COULD STAMP THE
 REVISED SHEET AND ROUTE TO INCOMING STEVE KENNEDY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-01 Cont ID  
Sent By dharvey Date 2013-10-01 Time 16:22 Rev Time 0.00
Received By dharvey Date 2013-10-01 Time 16:05 Sent To  
Notes
2013-10-01 16:18:04GROUNDING ELECTRODE TO TIE INTO EXISTING GROUNDING
 EELCTRODE SYSTEM (SINGLE POINT GROUNDING) 250.50,
 250.52
 CONDUCTORS TO BE RATED BASED ON OVERCURRENT PROTECTION
 240.6, 301.15
 PROVIDE GROUNDING SYSTEM FOR TRANSFORMER TB
 REVIEW CANNOT BE COMPLETED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-11 Cont ID  
Sent By wjolin Date 2013-09-11 Time 13:38 Rev Time 0.00
Received By wjolin Date 2013-09-11 Time 13:35 Sent To P
Notes
2014-02-05 19:44:21PLEASE STAMP THE REVISED SHEET AND SEND TO STEVE FOR
 FINAL PROCESSING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-10 Cont ID  
Sent By gdorsan Date 2014-02-10 Time 09:46 Rev Time 0.00
Received By gdorsan Date 2014-01-17 Time 17:54 Sent To  
Notes
2014-01-17 17:55:22SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2013-10-01 Cont ID  
Sent By dharvey Date 2013-10-01 Time 16:24 Rev Time 0.00
Received By dharvey Date 2013-09-05 Time 10:32 Sent To  
Notes
2013-10-01 16:24:09FAILED. CALLED CONTRACTOR, MAILBOX FULL. IN DENIED
 UNDER "W"
2013-09-05 10:32:13ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-09-13 Cont ID  
Sent By lwagner Date 2013-09-13 Time 10:23 Rev Time 0.00
Received By lwagner Date 2013-09-13 Time 10:02 Sent To E
Notes
2013-09-13 10:07:09SEPARATE APPLICATION, PLAN, AND PERMIT REQUIRED FOR
 FUEL GAS.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-01-24 Cont ID  
Sent By llouie Date 2014-01-24 Time 09:17 Rev Time 0.00
Received By llouie Date 2014-01-24 Time 09:17 Sent To E
Notes
2014-01-24 09:19:59ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) HEDGE SHALL BE AT LEAST 2 FT. IN HEIGHT AT TIME OF
 PLANTING.
  
 2.) HEDGE SHALL BE MAINTAINED IN GOOD CONDITION AT ALL
 TIMES.
  
 3.) GENERATOR NOISE LEVEL SHALL COMPLY WITH THE
 PROVISIONS OF CHAPTER 34, SECTION 34-35 OF THE CITY'S
 CODE OF ORDINANCES.

Review Stop Z ZONING
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By llouie Date 2013-09-09 Time 14:28 Rev Time 0.00
Received By llouie Date 2013-09-09 Time 14:19 Sent To FIRE
Notes
2013-10-22 11:10:38** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING. RESPOND TO THE COMMENTS
 IN WRITING AND/OR ON THE PLANS WHERE APPLICABLE:
  
 1.) GENERATOR SHALL BE APPROPRIATELY SCREENED. THE
 SCREEN SHALL BE CONSTRUCTED OUT OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY OR COMPARABLY
 DURABLE WOOD AND STEEL. (ZLDR S. 94-444((B))
  
 2.) THE WALLS OF THE SCREEN SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES AT TWO-FOOT INTERVALS. (ZLDR S.
 94-444((B))
  
 3.) PROVIDE A DETAIL OF THE PROPOSED SCREEN.
  
 PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL
 COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1442 IF YOU
 HAVE QUESTIONS.
  