Plan Review Details - Permit 13090023
Plan Review Stops For Permit 13090023
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 14:13 Rev Time 0.00
Received By shill Date 2013-10-26 Time 14:13 Sent To  
Notes
2013-10-26 14:14:59PROVISO
 REVISION REQUIRED
 ISSUED AT CONTRACTOR'S RISK
  
 FROM PREVIOUS BUILDING REVIEW -
  
 REVISE SHEET 6 OF 7, PROVIDE DIAMETER AND LENGTH FOR
 LAG BOLTS ATTACHING TO BACKING. ALSO PROVIDE THE SIZE
 OF THE BACKING MATERIAL INCLUDING THICKNESS, FBC
 107.2.1.3, FBC 1609.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-21 Cont ID  
Sent By jwitmer Date 2013-10-21 Time 18:44 Rev Time 0.00
Received By jwitmer Date 2013-10-21 Time 18:44 Sent To Z
Notes
2013-10-21 18:47:15PROVISO:
 PROVIDE REVISION FOR SHEET 6 OF 7, PROVIDE THE DIAMETER
 X LENGTH FOR LAG BOLTS ATTACHING TO BACKING, ALSO
 PROVIDE THE SIZE OF THE BACKING MATERILA INCLUDING
 THICKNESS.
 2010 WEST PALM BCH ADMIN CODE 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-01 Cont ID  
Sent By dharvey Date 2013-10-01 Time 15:43 Rev Time 0.00
Received By dharvey Date 2013-10-01 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-01 Cont ID  
Sent By dharvey Date 2013-10-01 Time 15:43 Rev Time 0.00
Received By dharvey Date 2013-10-01 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jlmitch Date 2013-11-01 Time 11:10 Sent To  
Notes
2013-11-01 11:11:04ROUTED TO SAMANTHA HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 14:15 Rev Time 0.00
Received By shill Date 2013-10-21 Time 15:04 Sent To  
Notes
2013-10-21 15:05:41INCOMING SENT TO ZONING, COULD NOT FIND PERMIT APP IN
 DENIED BIN. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-21 Cont ID  
Sent By jwitmer Date 2013-10-18 Time 14:55 Rev Time 0.00
Received By jwitmer Date 2013-10-07 Time 17:06 Sent To  
Notes
2013-10-09 17:06:45SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-01 Cont ID  
Sent By dharvey Date 2013-10-01 Time 15:55 Rev Time 0.00
Received By dharvey Date 2013-09-03 Time 12:24 Sent To  
Notes
2013-10-01 15:45:52CONTRACTOR CALLED. IN DENIED UNDER "H"
2013-09-03 12:24:27ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2013-10-24 Cont ID  
Sent By eschneid Date 2013-10-24 Time 16:14 Rev Time 0.25
Received By eschneid Date 2013-10-24 Time 16:14 Sent To PC
Notes
2013-10-24 16:42:33INTERIOR ARCADE SIGNS (1&2)
  
 PERMITTED: 150 SQ. FT.
 PROPOSED - 29.6 SQ. FT. (14.8 SQ. FT. X 2.)
  
 PLEASE NOTE THAT ANY INTERIOR OR STOREFRONT GLAZING
 SIGNAGE IS COUNTED IN THE TOTAL SIGNAGE IF IT IS
 VISIBLE FROM THE EXTERIOR OF THE STORE.
  
 PEDESTRIAN BLADE SIGNS (3&4)
  
 PERMITTED: 4 SQ. FT EACH
 PROPOSED: 4 SQ. FT. EACH
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-10-18 Cont ID  
Sent By eschneid Date 2013-10-18 Time 11:28 Rev Time 1.00
Received By eschneid Date 2013-10-11 Time 08:03 Sent To B
Notes
2013-10-18 13:13:05FAILED
  
 1) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 MEASURES SIGNAGE ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT
 OF SIGNAGE FOR EACH ONE LINEAR FOOT OF STORE FRONTAGE.
 PLEASE PROVIDE THE LINEAR FEET OF STORE FRONTAGE.
  
 INTERIOR ARCADE SIGNS (1&2)
  
 2) THE FACADE SHOWING THE LOCATION OF SIGN 2 WAS NOT
 PROVIDED. REVIEWING THE SHEET NUMBERS OF THE PLANS
 SUBMITTED, IT APPEARS THAT SHEET 3 OF 7 WAS NOT
 PROVIDED.
  
 3) SIGN AREA (PLEASE NOTE THAT THE INTERIOR ILLUMINATED
 STOREFRONT SIGNAGE TO BE MOUNTED ON THE DISPLAY WINDOW
 IS COUNTED IN THE TOTAL SIGNAGE IF IT IS VISIBLE FROM
 THE EXTERIOR OF THE STORE, I.E. THROUGH THE STOREFRONT
 WINDOW.)
  
 PROPOSED - 29.6 SQ. FT. (14.8 SQ. FT. X 2.)
 PERMITTED - UNKNOWN, FRONTAGE DIMENSION REQUIRED
  
 PEDESTRIAN BLADE SIGNS (3&4)
  
 4) THE FACADE SHOWING THE LOCATION OF SIGN 4 WAS NOT
 PROVIDED. REVIEWING THE SHEET NUMBERS OF THE PLANS
 SUBMITTED, IT APPEARS THAT SHEET 3 OF 7 WAS NOT
 PROVIDED.
  
 5) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT PEDESTRIAN BLADE SIGNS (INCLUDING
 MOUNTING FRAMES) PROVIDE A MINIMUM OF 8 FEET OF
 CLEARANCE. PROVIDE THE PEDESTRIAN BLADE SIGN CLEARANCE.
  
 9) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT PEDESTRIAN BLADE SIGNS SHALL NOT BE
 WITHIN SIX INCHES OF A NEUTRAL PIER. PROVIDE THE
 DIMENSIONS FROM THE FURTHEST PROJECTION OF THE
 PEDESTRIAN BLADE SIGN TO THE NEUTRAL PIER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-10-11 08:11:0110/11/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2013-09-18 Cont ID  
Sent By eschneid Date 2013-09-18 Time 11:13 Rev Time 0.75
Received By eschneid Date 2013-09-05 Time 08:07 Sent To E
Notes
2013-09-18 11:13:44FAILED
  
 1) THE CITYPLACE MASTER SIGN PLAN MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE. PLEASE PROVIDE
 THE LINEAR FEET OF STORE FRONTAGE.
  
 EXTERIOR ARCADE SIGNS (5&6)
  
 2) THE SOUTHERNMOST AND NORTHERNMOST H&M SIGNS DIRECTLY
 OVER THE ARCHED OPENINGS ARE NOT DESIGNATED SIGN ZONE
 LOCATIONS IN THE CITYPLACE MASTER SIGN PLAN. THE
 CITYPLACE MASTER SIGN PLAN ALLOWS CITYPLACE RETAIL TO
 APPROVE AN ADMINISTRATIVE VARIANCE TO PERMIT AN
 ALTERNATE PLACEMENT IN THE HORIZONTAL LINE OF THE SIGN
 ZONE. PROVIDE A NOTARIZED LETTER FROM CITYPLACE THAT
 THEY HAVE GRANTED THE VARIANCE TO THE ALTERNATE SIGN
 PLACEMENT IN THE HORIZONTAL LITE OF THE SIGN ZONE.
  
 3) SIGN AREA
  
 PROPOSED - 27.8 SQ. FT. (6.1 SQ. FT. X 3 PLUS 9.5 SQ.
 FT.)
 PERMITTED - UNKNOWN, FRONTAGE DIMENSION REQUIRED
  
 INTERIOR ARCADE SIGNS (1&2)
  
 4) THE CITYPLACE MASTER SIGN PLAN PROHIBITS INTERNALLY
 ILLUMINATED SIGNS WITHIN THE INTERIOR OF THE ARCADE.
  
 5) SIGN AREA
  
 PROPOSED - 29.6 SQ. FT. (14.8 SQ. FT. X 2.)
 PERMITTED - UNKNOWN, FRONTAGE DIMENSION REQUIRED
  
 6) THE ARCHITECTURAL ELEVATIONS AND THE ENGINEER PLANS
 SHOW DIFFERENT SIGN AND MOUNTING DIMENSIONS. PLEASE
 CLARIFY WHICH ONE IS CORRECT. ALL PLANS SHALL MATCH.
  
 PEDESTRIAN BLADE SIGNS (3&4)
  
 7) THE CITYPLACE MASTER SIGN PLAN ALLOWS EACH STORE TO
 INSTALL ONE (1), TWO-SIDED PEDESTRIAN BLADE SIGN FOR
 EACH STORE ENTRANCE, PLUS ONE (1) ADDITIONAL PEDESTRIAN
 BLADE SIGN PROVIDED, THE STOREFRONT HAS A MINIMUM OF
 SEVENTY FIVE (75) FEET OF FRONTAGE. THIS ADDITIONAL
 PEDESTRIAN BLADE SIGN SHALL PROVIDE A MINIMUM OF THIRTY
 (30) FEET OF SEPARATION FROM THE OTHER PEDESTRIAN
 BLADES SIGNS FOR THAT SAME STOREFRONT. PROVIDE
 DIMENSIONS TO VERIFY THAT THE TWO PROPOSED PEDESTRIAN
 BLADE SIGNS MEET THIS CRITERIA.
  
 8) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 PEDESTRIAN BLADE SIGNS (INCLUDING MOUNTING FRAMES)
 PROVIDE A MINIMUM OF 8 FEET OF CLEARANCE. PROVIDE THE
 PEDESTRIAN BLADE SIGN CLEARANCE.
  
 9) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 PEDESTRIAN BLADE SIGNS SHALL NOT BE WITHIN SIX INCHES
 OF A NEUTRAL PIER. PROVIDE THE DIMENSIONS FROM THE
 FURTHEST PROJECTION OF THE PEDESTRIAN BLADE SIGN TO THE
 NEUTRAL PIER.
  
 10) THE CITYPLACE MASTER SIGN PLAN DOES NOT ALLOW
 INTERNALLY ILLUMINATED PEDESTRIAN BLADE SIGNS EXCEEDING
 FOUR (4) INCHES IN WIDTH. PLEASE NOTE THAT THE FOUR
 INCH DIMENSION IS THE FULL WIDTH OF THE SIGN. THE "END
 VIEW" SHOWN ON THE PLANS DID NOT MEASURE THE FULL WIDTH
 OF THE SIGN.
  
 A COPY OF THESE COMMENTS HAS BEEN SENT TO CARLOS BERNAL
 AT CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-09-05 08:08:00ZONING RECEIVED. ROUTED TO ESCHNEIDER FOR REVIEW.