2013-09-11 11:47:12 | 2010 FBC |
| |
| 1) THE PERMIT APPLICATION INDICATES THE ADDITION IS TO |
| BE STORAGE AND THE PLANS DO NOT SPECIFY THE ROOM USE. |
| BASED ON THE PLANS THAT WERE SUBMITTED THE ADDITION |
| APPEARS TO BE A BEDROOM OR COULD BE USED AS A BEDROOM |
| BY AN OWNER IN THE FUTURE. PLEASE CLARIFY BY LABELING |
| THE ROOM ON THE PLANS. |
| |
| 2) THE PLANS SPECIFY THAT THE SPACE WILL BE |
| CONDITIONED. SUBMIT TWO COPIES OF ENERGY CALCULATIONS |
| FOR THE BUILDING. FBC ENERGY CONSERVATION SECTIONS |
| 101.4.3 , 101.4.5 |
| |
| 3) SHOW COMPLIANCE WITH FBCR 318 FOR TERMITE |
| PROTECTION. |
| |
| 4) FBC R403.1.4 REQUIRES ALL EXTERIOR FOOTINGS TO BE |
| PLACED AT LEAST 12 INCHES BELOW GRADE AND FBC R317.1 |
| (5) REQUIRES PROTECTION OF WOOD AND WOOD PRODUCTS FROM |
| DECAY FOR WALL FRAMING AND SHEATHING AT THE EXTERIOR OF |
| A BUILDING HAVING A CLEARANCE OF LESS THAN 6" FROM THE |
| GROUND. THE 16" DEEP FOOTING SPECIFIED ON THE PLANS |
| WILL ONLY PROVIDE 4" FROM THE GROUND. SPECIFY HOW THIS |
| REQUIREMENT WILL BE ADDRESSED. |
| |
| 5) SHOW COMPLIANCE WITH FBCR 318.6 WHICH REQUIRES |
| GUTTERS AND DOWNSPOUTS AT THE REAR OF THE STRUCTURE |
| WITH NO EAVE PROJECTION WHERE THE RAIN WATER FROM THE |
| ROOF IS DISCHARGED. |
| |
| 6) SHOW COMPLIANCE WITH FBCR 806 FOR REQUIRED ATTIC |
| VENTILATION. |
| |
| 7) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE 4 X 10 |
| WOOD BEAM AT THE COVERED PORCH IS TO BE NOTCHED INTO |
| THE CORNERS AT EACH END (INCLUDING THE EXISTING |
| CORNER). SPECIFY THE NUMBER OF FRAMING MEMBERS REQUIRED |
| FOR BEARING AND THE REQUIRED STRAPS AND CONNECTORS FOR |
| UPLIFT AND LATERAL FORCES. FBC R301.1 |
| |
| 8) PLEASE CLARIFY IF THE (3) #5 BARS IN THE FOOTING ARE |
| TO BE DOWELED INTO THE EXISTING FOOTING. FBC R301.1 |
| |
| 9) PROVIDE A STRUCTURAL DETAIL OF THE PARAPET |
| CONSTRUCTION. SHOW ALL CONNECTORS REQUIRED TO ACHIEVE A |
| CONTINUOUS LOAD PATH. FBC R301.1 |
| |
| 10) PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE |
| REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD FOR THE PROJECT. CITY AMENDMENTS 10 |
| |
| 11) SUBMIT (2) COPIES OF PRODUCT APPROVALS FOR THE NEW |
| EXTERIOR DOOR, THE ROOF TILE AND THE SIMPSON CONNECTORS |
| AS REQUIRED BY DCA RULE 9N-3. |
| |
| 12) SPECIFY WHICH METHOD OF ATTACHMENT LISTED IN THE |
| ROOF TILE PRODUCT APPROVAL WILL BE USED TO INSTALL IT. |
| IF AN ADHESIVE IS USED, SUBMIT TWO COPIES OF THE |
| PRODUCT APPROVAL. FBC R905.1 |
| |
| 13) SPECIFY THE APPROVED ASSEMBLY, INSULATION TYPE, |
| FASTENING OPTION AND MAXIMUM DESIGN PRESSURE FROM THE |
| MULE- HIDE ROOFING PRODUCT APPROVAL (NOA # 12-0815.09) |
| THAT WILL BE USED. IF ENHANCED FASTENING OF THE BASE |
| SHEET IS REQUIRED TO MEET THE UPLIFT PRESSURE |
| REQUIREMENTS OF THE PERIMETER AND CORNER ROOF AREAS |
| SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| CALCULATIONS IN ACCORDANCE WITH LIMITATION #7 ON PAGE |
| 25 OF THE NOA. FBC R905.1 |
| |
| 14) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE |
| REVIEW COMMENTS HAVE BEEN ADDRESSED. THIS WILL AID IN |
| SPEEDING REVIEW TIMES. |
| |