Plan Review Details - Permit 13081155
Plan Review Stops For Permit 13081155
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-11-15 Cont ID  
Sent By jwitmer Date 2013-11-15 Time 07:52 Rev Time 0.00
Received By jwitmer Date 2013-11-15 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-10-22 Cont ID  
Sent By jwitmer Date 2013-10-22 Time 14:09 Rev Time 0.00
Received By jwitmer Date 2013-10-22 Time 14:09 Sent To  
Notes
2013-10-22 14:10:54BUILDING PLAN REVIEW
 PERMIT: 13081155
 ADD: 616 DATURA ST
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: OCT. 22/ 2013
 ACTION: DENIED
  
 1) 2ND REQUEST, PLEASE PROVIDE A SITE PLAN WITH THE
 LOCATION OF THE STRUCTURE, PROVIDE DISTANCE FROM THE
 PROPERTY LINES. 2010 FBC-B TABLE 602 FIRE RESISTANCE
 RATING REQUIREMENTSFOR EXTERIOR WALLS BASED ON
 FIRE SEPERATION DISTANCE, TABLE 602 FOR A TYPE VB
 STRUCTURE WIL REQUIRE A MINIMUM OF 10 SEPERATION FROM
 THE PROPERETY LINE, TABLE 602.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-12 Cont ID  
Sent By jwitmer Date 2013-09-12 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2013-09-12 Time 15:17 Sent To  
Notes
2013-09-12 15:23:19BUILDING PLAN REVIEW
 PERMIT: 13081155
 ADD: 616 DATURA ST
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT 12/ 2013
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SITE PLAN WITH THE LOCATION OF THE
 STRUCTURE, PROVIDE DISTANCE FROM THE PROPERTY LINES.
 2010 FBC-B TABLE 602 FIRE RESISTANCE RATING
 REQUIREMENTSFOR EXTERIOR WALLS BASED ON
 FIRE SEPERATION DISTANCE, TABLE 602 FOR A TYPE VB
 STRUCTURE WIL REQUIRE A MINIMUM OF 10 SEPERATION FROM
 THE PROPERETY LINE, TABLE 602.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-07 Cont ID  
Sent By albarran Date 2013-11-07 Time 19:45 Rev Time 0.00
Received By albarran Date 2013-11-07 Time 18:51 Sent To I
Notes
2013-11-07 19:45:17THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO
 PROVIDING THE ELECTRICAL SERVICE TO A MANUFACTURED
 OFFICE TRAILER. NO ADDITIONAL WORK IS AUTHORIZED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-23 Cont ID  
Sent By dharvey Date 2013-09-23 Time 16:45 Rev Time 0.00
Received By dharvey Date 2013-09-23 Time 16:45 Sent To  
Notes
2013-09-23 16:48:219-23-13
  
 HOW MANY TRAILERS? NEED MUCH MORE CLARIFICATION.
  
 PROVIDE A SITE PLAN SHOWING THE NUMBER OF TRAILER (S)
 AND THEIR EXACT LOCATION ON THE PROPERTY.
  
 PROVIDE THE POINT OF ELECTRICAL CONNECTION TO THE POWER
 SOURCE AND THE TRAILER (S)?
  
 NEED ELECTRICAL PERMIT
  
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-23 Cont ID  
Sent By scaldero Date 2013-10-23 Time 14:13 Rev Time 0.00
Received By scaldero Date 2013-10-08 Time 14:13 Sent To  
Notes
2013-10-08 14:25:27PERMIT #13081155
  
 APPROVED AS DISCUSSED BY W. JOLIN & CONTRACTOR.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By wjolin Date 2013-09-05 Time 15:32 Rev Time 0.00
Received By wjolin Date 2013-09-05 Time 14:32 Sent To  
Notes
2013-09-05 15:32:12616 DATURA STREET
 PERMIT #13081155
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A DETAILED SITE DRAWING INDICATING THE
 ORIENTATION AND DISTANCE OF THE TRAILER IN REGARDS TO
 ANY ADJACENT STRUCTURES.
  
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2
 TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM
 ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE STAIR DETAIL. STAIR RISERS SHALL BE BETWEEN 4
 INCHES AND 7 INCHES IN HEIGHT. STAIRS SHALL BE SLIP
 RESISTANT AND HAVE A MINIMUM TREAD DEPTH OF 11 INCHES
 AND PREVENT THE ACCUMULATION OF WATER. HANDRAILS ARE
 REQUIRED ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE
 LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38
 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED
 VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE
 OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE
 WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES.
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-15 Cont ID  
Sent By jwitmer Date 2013-11-15 Time 07:52 Rev Time 0.00
Received By jwitmer Date 2013-11-12 Time 17:53 Sent To  
Notes
2013-11-13 17:54:06SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-12 Cont ID  
Sent By shill Date 2013-11-12 Time 17:19 Rev Time 0.00
Received By shill Date 2013-10-02 Time 17:10 Sent To  
Notes
2013-10-02 17:10:44INCOMING SENT TO B15 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-23 Cont ID  
Sent By dharvey Date 2013-09-23 Time 16:51 Rev Time 0.00
Received By dharvey Date 2013-09-23 Time 16:51 Sent To  
Notes
2013-08-29 18:01:46SENT TO B6 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-09-10 Cont ID  
Sent By lwagner Date 2013-09-10 Time 10:43 Rev Time 0.00
Received By lwagner Date 2013-09-10 Time 10:25 Sent To  
Notes
2013-09-10 10:44:27SEPARATE PLUMBING PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By aaponte Date 2013-09-12 Time 09:36 Rev Time 0.00
Received By aaponte Date 2013-09-12 Time 09:35 Sent To  
Notes
2013-09-12 09:36:37PROVISO: TRAILER SHALL BE SET BACK 16 FEET FROM THE
 BACK OF CURB ALONG DATURA STREET.
2013-09-05 09:25:109/5/13