Plan Review Details - Permit 13080941
Plan Review Stops For Permit 13080941
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-15 Cont ID  
Sent By jwitmer Date 2013-10-15 Time 17:45 Rev Time 0.00
Received By jwitmer Date 2013-10-15 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By jwitmer Date 2013-08-28 Time 09:04 Rev Time 0.00
Received By jwitmer Date 2013-08-28 Time 07:33 Sent To  
Notes
2013-08-28 08:39:11BUILDING PLAN REVIEW
 PERMIT: 13080941
 ADD: 501 FERN ST UNIT# B1 INTERIOR BUILD-OUT
 CONT: EDS ISLAND TIME SERVICES
 TEL: (561)541-0004
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 28/ 2013
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED 107.2.1.3, THE
 STRUCTURAL SHEET S2 DETAIL F & H INCLUDES A VERTICAL
 STEEL COLUMN WITH A 6"X3"X 1/4" STEEL PLATE WELDED AT
 ELEVATION 8'-0" ABOVE FINISH FLOOR. IT APPEARS A BOTTOM
 PLATE STEEL TRACK 14 GAUGE IS ATTACHED TO THE 1/4"
 STEEL PLATE. THERE IS NO MULLION, OR BUILT UP BOX BEAM,
 PLEASE PROVIDE HOW THE LOADS ARE GOING TO BE
 TRANSFERRED WITH NO FRAMING MEMBER, IS THE 14 GAUGE
 TRACK
 HEAVY ENOUGH TO TRANSFER THE WIND LOADS. IF YOU COULD
 PLEASE PROVIDE SOME ADDITIONAL INFORMATION. THANK YOU.
  
 2) THE SUBMITTED PRODUCT APPROVAL (11-1117.02) DOES
 NEED THE DESIGNER OF RECORD TO REVIEW AND PLACE A SHOP
 DRAWING STAMP. PRODUCT APPROVALS: 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 SHEET 3 OF 13 TYPICAL ANCHORS C INDICATES THE FASTENERS
 TO FASTEN INTO A36 STEEL, PLEASE PROVIDE IF THE 14
 GAUGE TRACK MEETS THIS REQUIREMENT. SHEET 9 OF 13
 PLEASE CIRCLE THE APPROPRIATE WINDOW SIZE ANCHOR TYPES
 FOR THE PRESSURES REQUIRED. PLEASE CIRCLE WHICH TYPE OF
 FASTENERS AND HOW MANY WILL BE REQUIRED FOR EACH SIDE
 OF THE STRUCTURAL STEEL COLUMN.
  
 3) SHEET A4 INDICATES USE OF A ATTIC SPACE FOR HVAC
 EQUIPMENT, PLEASE PROVIDE FLOOR LOADING FOR THIS SPACE,
 2010 FLBC-B TABLE 1607.1.
  
 4) SHEET A4 & M.2 BOTH INDICATE THE AIR HANDLIER UNITS
 ARE TO BE ROOF TOP UNITS:
 4A) PROVIDE INFORMATION HOW THE COMPRESSORS ARE TO BE
 MOUNTED TO THE ROOF.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(G) EX
 PRE-ENGINEERED A/C STANDS
  
 4B) FBC-B TABLE 1509.7 HEIGHT REQUIREMENTS FOR A/C
 CONDENSOR STANDS LOCATED ON ROOFS.
  
 4C) 2010 FBC-MECHANICAL 306.5 EQUIPMENT AND APPLIANCES
 ON ROOFS OR ELEVATED STRUCTURES, ACCESS.
  
 4C) IF A ROOF HATCH IS USED, 1009.13.2 PROTECTION AT
 ROOF HATCH OPENINGS.
 WHERE THE ROOF HATCH OPENING PROVIDING THE REQUIRED
 ACCESS IS LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF
 EDGE, SUCH ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED
 BY GUARDS INSTALLED IN ACCORDANCE WITH THE PROVISIONS
 OF SECTION 1013.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By dharvey Date 2013-10-18 Time 14:01 Rev Time 0.00
Received By dharvey Date 2013-10-18 Time 14:01 Sent To I
Notes
2013-10-18 14:01:34THESE PLANS WERE PREVIOUSLY REVIEWED BY DH. NO NEW
 REVIEW WAS DONE, SIMPLY WE STAMPED THE NEWLY PRINTED
 SHEETS.
  
 SENT TO SH DESK BY: MA

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-03 Cont ID  
Sent By dharvey Date 2013-09-03 Time 15:39 Rev Time 0.00
Received By dharvey Date 2013-09-03 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-07 Cont ID  
Sent By scaldero Date 2013-10-07 Time 13:33 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 13:33 Sent To  
Notes
2013-10-07 13:33:41PERMIT #13080941
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****PROVISO*****
 MEAN OR METHOD TO PREVENT CUSTOMERS FROM OCCUPYING THE
 STORAGE MEZZANINE IS APPROVED PENDING FIELD INSPECTION.
  
 MEAN OR METHOD TO PREVENT THE ATTIC FLOOR AREA FROM
 BECOMING STORAGE SPACE IS APPROVED PENDING FIELD
 INSPECTION.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By wjolin Date 2013-08-29 Time 10:43 Rev Time 0.00
Received By wjolin Date 2013-08-29 Time 09:53 Sent To  
Notes
2013-08-29 10:43:34501 FERN STREET - #B1
 PERMIT #13080941
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE COVER SHEET MAKES TWO OR THREE REFERENCES TO GROUP
 A-2 ASSEMBLY IN LIEU OF MERCANTILE.
  
 PLEASE INDICATE WHAT MEANS OR METHODS WILL BE IN PLACE
 TO PREVENT CUSTOMERS FROM OCCUPYING THE STORAGE
 MEZZANINE.
  
 PLEASE INDICATE WHAT MEANS OR METHODS WILL BE IN PLACE
 TO PREVENT THE ATTIC FLOOR AREA FROM BECOMING STORAGE
 SPACE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-18 Cont ID  
Sent By hmoser Date 2013-10-18 Time 14:55 Rev Time 0.00
Received By hmoser Date 2013-10-02 Time 18:02 Sent To  
Notes
2013-10-02 18:03:15INCOMING SENT TO B34 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-05 Cont ID  
Sent By hmoser Date 2013-09-05 Time 15:28 Rev Time 0.00
Received By hmoser Date 2013-08-23 Time 17:39 Sent To  
Notes
2013-08-23 17:39:51SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2013-10-15 Cont ID  
Sent By jwitmer Date 2013-10-15 Time 17:32 Rev Time 0.00
Received By jwitmer Date 2013-10-15 Time 17:32 Sent To  
Notes
2013-10-15 17:32:56PLANS STAMPED FROM PB COUNTY IMPACT ASSESSMENT: NO FEES
 DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By jwitmer Date 2013-08-28 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2013-08-28 Time 07:34 Sent To  
Notes
2013-08-28 07:35:12BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By hmoser Date 2013-10-18 Time 14:54 Rev Time 0.00
Received By hmoser Date 2013-10-18 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By hmoser Date 2013-09-05 Time 15:22 Rev Time 0.00
Received By hmoser Date 2013-09-05 Time 15:22 Sent To  
Notes
2013-09-05 15:28:40PLANS DENIED
 PROVIDE DUCT SIZE, GRILL SIZE AND CFM ON PLANS
 PER SECTION 107 FBC
 REFER TO SECTION 306.3 APPLIANCE IN ATTICS
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-11 Cont ID  
Sent By lwagner Date 2013-10-11 Time 12:38 Rev Time 0.00
Received By lwagner Date 2013-10-11 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-04 Cont ID  
Sent By lwagner Date 2013-09-04 Time 10:34 Rev Time 0.00
Received By lwagner Date 2013-09-04 Time 10:10 Sent To  
Notes
2013-09-04 10:33:07FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THE WATER CLOSETS ARE NOT PROPERLY VENTED AS SHOWN. WET
 VENTING IS ONLY PERMITTED FOR UP TO TWO BATHROOMS AND
 FOUR ARE SHOWN ON THE PLAN. CONNECTING EACH LAVATORY
 STACK TO ITS ASSOCIATED WATER CLOSET BRANCH LINE,
 CREATING FOUR WET VENTED RESTROOMS, WOULD BE OK.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-05 Cont ID  
Sent By aaponte Date 2013-09-05 Time 12:04 Rev Time 0.00
Received By aaponte Date 2013-09-05 Time 12:04 Sent To  
Notes
2013-08-28 14:23:048/28/13