Plan Review Details - Permit 13080940
Plan Review Stops For Permit 13080940
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By jwitmer Date 2013-10-15 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2013-10-15 Time 17:45 Sent To  
Notes
2013-10-15 18:50:16BUILDING PLAN REVIEW
 PERMIT: 13080940
 ADD: 501 FERN ST UNIT# B2 INTERIOR BUILD-OUT
 CONT: EDS ISLAND TIME SERVICES
 TEL: (561)541-0004
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 15/ 2013
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES
  
  
 1) SHEET A3 INDICATES THERE ARE TWO DRESSING ROOMS FOR
 THE MERCANTILE PORTION OF THE TENANT SPACE, PLEASE
 PROVIDE COMPLIANCE WITH:
 2010 FL ACCESSIBILITY CODE DRESSING ROOMS:
 3A) 803.2 TURNING SPACE. TURNING SPACE COMPLYING WITH
 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 1B) 803.4 BENCHES.
 A BENCH COMPLYING WITH 903 SHALL BE PROVIDED WITHIN THE
 ROOM.
  
 1C)903.3 SIZE. BENCHES SHALL HAVE SEATS THAT ARE 42
 INCHES (1065 MM) LONG MINIMUM AND 20 INCHES (510 MM)
 DEEP MINIMUM AND 24 INCHES (610 MM) DEEP MAXIMUM.
  
 1D) 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 1E) 903.5 HEIGHT.
 THE TOP OF THE BENCH SEAT SURFACE SHALL BE 17 INCHES
 (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By jwitmer Date 2013-08-28 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2013-08-28 Time 06:03 Sent To  
Notes
2013-08-28 07:29:23BUILDING PLAN REVIEW
 PERMIT: 13080940
 ADD: 501 FERN ST UNIT# B2 INTERIOR BUILD-OUT
 CONT: EDS ISLAND TIME SERVICES
 TEL: (561)541-0004
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 28/ 2013
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS, PLEASE REVIEW A1 THE
 COVERSHEET, A.3 & LS1, THEY LIST THE SAME AREA AS A A2,
 A3 OCCUPANCY AND STUDIO FOR THE SAME AREA, CITY OF WEST
 PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA BUILDING
 CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. PLEASE PROVIDE IN DETAIL WHAT THIS AREA WILL
 BE USED FOR:
 A2 INTENDED FOR FOOD OR DRINK CONSUMPTION
 A3 INTENDED FOR WORSHIP, RECREATION OR AMUSEMENT
  
 2) LS1 INDICATES 2 EXIT DOORS PLEASE PROVIDE COMPLIANCE
 WITH 2010 FBC-B 1015.2.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS. EXCEP #2, WHERE TWO EXITS OR EXIT ACCESS
 DOORWAYS ARE REQUIRED FROM ANY PORTION OF THE EXIT
 ACCESS, THE EXIT DOORS OR EXIT ACCESS DOORWAYS SHALL BE
 PLACED A DISTANCE APART EQUAL TO NOT LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED MEASURED
 IN A STRAIGHT LINE BETWEEN EXIT DOORS OR EXIT ACCESS
 DOORWAYS. IT APPEARS THE DISTANCE BETWEEN THE 2 DOORS
 DOES NOT MEET 1/3RD THE DISTANCE OF THE OVERALL
 DIAGONAL BETWEEN THE DOORS.
  
 3) SHEET A3 INDICATES THERE ARE TWO DRESSING ROOMS FOR
 THE MERCANTILE PORTION OF THE TENANT SPACE, PLEASE
 PROVIDE COMPLIANCE WITH:
 2010 FL ACCESSIBILITY CODE DRESSING ROOMS:
 3A) 803.2 TURNING SPACE. TURNING SPACE COMPLYING WITH
 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 3B) 803.4 BENCHES.
 A BENCH COMPLYING WITH 903 SHALL BE PROVIDED WITHIN THE
 ROOM.
  
 3C)903.3 SIZE.
 BENCHES SHALL HAVE SEATS THAT ARE 42 INCHES (1065 MM)
 LONG MINIMUM AND 20 INCHES (510 MM) DEEP MINIMUM AND 24
 INCHES (610 MM) DEEP MAXIMUM.
  
 3D) 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
  
 ADVISORY 903.4 BACK SUPPORT.
 TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER
 PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH,
 BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT
 OBSTRUCT TRANSFER TO THE BENCH.
  
 3E) 903.5 HEIGHT.
 THE TOP OF THE BENCH SEAT SURFACE SHALL BE 17 INCHES
 (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 3F) 803.5 COAT HOOKS AND SHELVES.
 COAT HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED
 WITHIN ONE OF THE REACH RANGES SPECIFIED IN 308.
 SHELVES SHALL BE 40 INCHES (1015 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4) SHEET A3 INDICATES USE OF A ATTIC SPACE FOR HVAC
 EQUIPMENT, PLEASE PROVIDE FLOOR LOADING FOR THIS SPACE,
 2010 FLBC-B TABLE 1607.1.
  
 5) SHEET E1 & M1 BOTH INDICATE THE AIR HANDLIER UNITS
 ARE TO BE ROOF TOP UNITS:
 5A) PROVIDE INFORMATION HOW THE COMPRESSORS ARE TO BE
 MOUNTED TO THE ROOF.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(G) EX
 PRE-ENGINEERED A/C STANDS
  
 5B) FBC-B TABLE 1509.7 HEIGHT REQUIREMENTS FOR A/C
 CONDENSOR STANDS LOCATED ON ROOFS.
  
 5C) 2010 FBC-MECHANICAL 306.5 EQUIPMENT AND APPLIANCES
 ON ROOFS OR ELEVATED STRUCTURES, ACCESS.
  
 5C) IF A ROOF HATCH IS USED, 1009.13.2 PROTECTION AT
 ROOF HATCH OPENINGS.
 WHERE THE ROOF HATCH OPENING PROVIDING THE REQUIRED
 ACCESS IS LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF
 EDGE, SUCH ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED
 BY GUARDS INSTALLED IN ACCORDANCE WITH THE PROVISIONS
 OF SECTION 1013.
  
 6) SHEET A.3 INDICATE A CHECK OUT COUNTER FOR THE
 MERCANTILE OCCUPANCY PLEASE SHOW COMPLIANCE WITH: 2010
 FBC-ACCESSIBILITY CODE EITHER 904.32 COUNTERS, 904.3.3
 CHECK WRITING SURFACES AND OR 904.4 SALES AND SERVICE
 COUNTERS.
  
 7) PRODUCT APPROVALS: 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) PERMIT # 13080941 HAS A ATTACHED S3 PLAN WHICH LOOKS
 LIKE IT SHOULD BE ATTACHED TO THIS SET OF PLANS OR MORE
 LIKELY S3 PLANS SHOULD SET IN SETS FOR BOTH PERMITS...
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By dharvey Date 2013-10-18 Time 13:48 Rev Time 0.00
Received By dharvey Date 2013-10-18 Time 13:47 Sent To I
Notes
2013-10-18 13:49:42THESE PLANS WERE PREVIOUSLY REVIEWED BY DH. NO NEW
 REVIEW WAS DONE, SIMPLY WE STAMPED THE NEWLY PRINTED
 SHEETS.
  
 SENT TO SH DESK BY: MA

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-03 Cont ID  
Sent By dharvey Date 2013-09-03 Time 15:40 Rev Time 0.00
Received By dharvey Date 2013-09-03 Time 15:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By scaldero Date 2013-10-18 Time 13:16 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 13:14 Sent To  
Notes
2013-10-07 13:14:17PERMIT #13080940
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
  
 NOTATIONS ARE REQUIRED ON THE PLAN PER AGREEMENT WITH
 W. JOLIN AND J. WITMER.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By wjolin Date 2013-08-29 Time 09:51 Rev Time 0.00
Received By wjolin Date 2013-08-28 Time 13:07 Sent To  
Notes
2013-08-29 09:51:31501 FERN STREET - #B2
 PERMIT #13080940
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE WHAT USE IS INTENDED FOR THE ASSEMBLY AREA.
  
 PROVIDE A FURNITURE/EQUIPMENT/MERCHANDISE LAYOUT.
  
 PER NFPA 101 SECTION 7.5.1.3.3, IN BUILDINGS PROTECTED
 THROUGHOUT BY A SPRINKLER SYSTEM, THE MINIMUM
 SEPARATION DISTANCE BETWEEN TWO EXITS OR EXIT ACCESS
 DOORS SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF
 THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING
 OR AREA BEING SERVED.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING
 CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
 A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER NFPA 101 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-18 Cont ID  
Sent By hmoser Date 2013-10-18 Time 15:05 Rev Time 0.00
Received By hmoser Date 2013-10-02 Time 18:10 Sent To  
Notes
2013-10-02 18:10:31INCOMING SENT TO B-34 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-05 Cont ID  
Sent By hmoser Date 2013-09-05 Time 15:07 Rev Time 0.00
Received By hmoser Date 2013-08-23 Time 17:47 Sent To  
Notes
2013-08-23 17:47:40SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2013-10-15 Cont ID  
Sent By jwitmer Date 2013-10-15 Time 18:02 Rev Time 0.00
Received By jwitmer Date 2013-10-15 Time 18:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By jwitmer Date 2013-08-28 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2013-08-28 Time 07:33 Sent To  
Notes
2013-08-28 07:34:33BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-18 Cont ID  
Sent By hmoser Date 2013-10-18 Time 15:05 Rev Time 0.00
Received By hmoser Date 2013-10-18 Time 15:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By hmoser Date 2013-09-05 Time 15:06 Rev Time 0.00
Received By hmoser Date 2013-09-05 Time 14:17 Sent To  
Notes
2013-09-05 15:06:23PLANS DENIED
 1) PROVIDE DUCT SIZE, CFM AND GRILL SIZE ON PLANS
 PER SECTION 107 FBC 2010
 2) REFER TO SECTION 303.3 APPLIANCE IN ATTIC.
 2010 FBC (M)
 3) EXHAUST DUCT IN BATHROOMS DISCHARGE TO R.C.
 WHAT IS R.C.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-11 Cont ID  
Sent By lwagner Date 2013-10-11 Time 11:14 Rev Time 0.00
Received By lwagner Date 2013-10-11 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-04 Cont ID  
Sent By lwagner Date 2013-09-04 Time 10:37 Rev Time 0.00
Received By lwagner Date 2013-09-04 Time 10:36 Sent To  
Notes
2013-09-04 10:38:56 
 FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THE WATER CLOSETS ARE NOT PROPERLY VENTED AS SHOWN. WET
 VENTING IS ONLY PERMITTED FOR UP TO TWO BATHROOMS AND
 FOUR ARE SHOWN ON THE PLAN. CONNECTING EACH LAVATORY
 STACK TO ITS ASSOCIATED WATER CLOSET BRANCH LINE,
 CREATING FOUR WET VENTED RESTROOMS, WOULD BE OK.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-05 Cont ID  
Sent By aaponte Date 2013-09-05 Time 11:59 Rev Time 0.00
Received By aaponte Date 2013-09-05 Time 11:59 Sent To  
Notes
2013-08-28 14:26:388/28/13