2013-09-10 12:27:43 | BUILDING PLAN REVIEW |
| REVISION: 13080802 |
| PERMIT: 13070239 |
| ADD: 513 CLEMATIS ST SUITE # ???? |
| CONT: LARRY ROWE |
| TEL: (561) 635-8227 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1) PLANS DO NOT IDENTIFY WHICH SUITE OR UNIT NUMBER |
| THIS IS FOR, THERE ARE TWO UNITS ON THE FIRST FLOOR AND |
| THREE ON THE SECOND FLOOR, WE NEED THIS INFORMATION TO |
| PUT INTO OUR DATA BASE FOR FUTURE TRACKING OF |
| RENOVATIONS AND BUSINESS TAX FOR LICENSING OF |
| BUSINESSES AS WELL AS FOR THE FIRE DEPARTMENT AND OTHER |
| GOVERNMENTAL AGENCIES.CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRTION, 2010 EDITION. 107.2.1. |
| |
| 2) A ELECTRICAL PLAN HAS BEEN SUBMITTED, NO FLOOR PLAN |
| HAS BEEN SUBMITTED FOR THE BUILDING PORTION OF THE |
| REVIEW. THE CONTRACTOR HAS TAKEN THE EXCEPTION FOR THE |
| REQUIREMENT OF SIGNED AND SEALED PLANS UNDER FL S 481. |
| 22.9 EXCEPTION (1)(C) . THE .CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRTION, 2010 EDITION. 107.2.1 REQUIRES THE |
| CONTRACTOR TO BEAR THE NAME, SIGNATURE AND LICENSE |
| NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 3) THE PLANS DO NOT INDICATE THE TYPE OF OCCUPANCY THIS |
| SPACE IS DESIGNED FOR, CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRTION, 2010 EDITION, 107.3.5.1.1 |
| (2). |
| |
| 4) PLANS INDICATE A NEW PROPOSED OFFICE PLEASE |
| DIMENSIONS OF OFFICE, A CUT SECTION OF WALL, AND DOOR |
| DIMENSION SIZE, NOT SHOWN ON THE ELECTRICAL PLAN. .CITY |
| OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRTION, 2010 EDITION, 107.1.2. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| |
| 5) THE NEW PROPOSED OFFICE INDICATES A NEW SINK, THE |
| PLANS ARE DEFICIENT IN NOT SHOWING COMPLIANCE WITH 2010 |
| FBC-ACCESSIBILITY CODE 606.1-5. SINKS. |
| |
| 6) NO "WHITE OUT OF PLANS" IS ALLOWED, .CITY OF WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRTION, 2010 EDITION,107.2.1.4. |
| QUALITY OF PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR |
| OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| . |
| |