Plan Review Details - Permit 13080797
Plan Review Stops For Permit 13080797
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-10-02 Time 11:55 Rev Time 0.00
Received By jwitmer Date 2013-10-02 Time 11:00 Sent To  
Notes
2013-10-02 11:32:26BUILDING PLAN REVIEW
 PERMIT: 13080797
 ADD: 513 CLEMATIS ST UNITS # 201, 203, & 205
 CONT: LARRY B. ROWE
 TEL: (561)835-17999
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:OCT 02/ 2013
 ACTION: PROVISO
  
 1) EGRESS COURT FOR THE REAR EXTERIOR STAIR IS TO
 COMPLY WITH:
 2010 FBC-B 1027 EGRESS COURTS
 1027.2 EXIT DISCHARGE CAPACITY.
 THE CAPACITY OF THE EXIT DISCHARGE SHALL BE NOT LESS
 THAN THE REQUIRED DISCHARGE CAPACITY OF THE EXITS BEING
 SERVED.
  
 1027.3 EXIT DISCHARGE LOCATION.
 EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE
 LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT
 LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS
 THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE
 PROTECTED IN ACCORDANCE WITH SECTION 705 BASED ON FIRE
 SEPARATION DISTANCE.
  
 1027.4 EXIT DISCHARGE COMPONENTS.
 EXIT DISCHARGE COMPONENTS SHALL BE SUFFICIENTLY OPEN TO
 THE EXTERIOR SO AS TO MINIMIZE THE ACCUMULATION OF
 SMOKE AND TOXIC GASES.
  
 1027.5 EGRESS COURTS.
 EGRESS COURTS SERVING AS A PORTION OF THE EXIT
 DISCHARGE IN THE MEANS OF EGRESS SYSTEM SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 1027.
  
 1027.5.1 WIDTH.
 THE WIDTH OF EGRESS COURTS SHALL BE DETERMINED AS
 SPECIFIED IN SECTION 1005.1, BUT SUCH WIDTH SHALL NOT
 BE LESS THAN 44 INCHES (1118 MM), EXCEPT AS SPECIFIED
 HEREIN. EGRESS COURTS SERVING GROUP R-3 AND U
 OCCUPANCIES SHALL NOT BE LESS THAN 36 INCHES (914 MM)
 IN WIDTH. THE REQUIRED WIDTH OF EGRESS COURTS SHALL BE
 UNOBSTRUCTED TO A HEIGHT OF 7 FEET (2134 MM).
  
 WHERE AN EGRESS COURT EXCEEDS THE MINIMUM REQUIRED
 WIDTH AND THE WIDTH OF SUCH EGRESS COURT IS THEN
 REDUCED ALONG THE PATH OF EXIT TRAVEL, THE REDUCTION IN
 WIDTH SHALL BE GRADUAL. THE TRANSITION IN WIDTH SHALL
 BE AFFECTED BY A GUARD NOT LESS THAN 36 INCHES (914 MM)
 IN HEIGHT AND SHALL NOT CREATE AN ANGLE OF MORE THAN 30
 DEGREES (0.52 RAD) WITH RESPECT TO THE AXIS OF THE
 EGRESS COURT ALONG THE PATH OF EGRESS TRAVEL. IN NO
 CASE SHALL THE WIDTH OF THE EGRESS COURT BE LESS THAN
 THE REQUIRED MINIMUM.
  
 1027.5.2 CONSTRUCTION AND OPENINGS.
 WHERE AN EGRESS COURT SERVING A BUILDING OR PORTION
 THEREOF IS LESS THAN 10 FEET (3048 MM) IN WIDTH, THE
 EGRESS COURT WALLS SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION FOR A DISTANCE OF 10
 FEET (3048 MM) ABOVE THE FLOOR OF THE COURT. OPENINGS
 WITHIN SUCH WALLS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-24 Cont ID  
Sent By jwitmer Date 2013-09-24 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2013-09-24 Time 11:20 Sent To  
Notes
2013-09-24 12:43:52BUILDING PLAN REVIEW
 PERMIT: 13080797
 ADD: 513 CLEMATIS ST UNITS # 201, 203, & 205
 CONT: LARRY B. ROWE
 TEL: (561)835-17999
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:SEPT 24/ 2013
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION.107.3.5.1.1. MINIMUM CRITERIA FOR COMMERCIAL
 PLAN REVIEW:
 2A) MINIMUM BUILDING TYPE
 2B)COMPLIED
 2C) COMPLIED.
 2D) SEMI-COMPLIED.
 2D)(1) LIFE SAFETY PLAN THE SECOND STORY IS SHOWN, BUT
 THE JOBSITE VISIT SHOWED THE BACK EXTERIOR STAIR WAY
 LEADING INTO A COURTYARD WITH NO EXIT. MAKING THIS A
 SINGLE EXIT FROM THE FRONT SET OF STAIRS. FBC-B TABLE
 1021.2 STORIES WITH ONE- EXIT TRAVEL DISTANCE LIMIT 75
 FEET. THE COURTYARD WILL NEED TO LEED TO A PUBLIC WAY.
 AT THE JOBSITE VISIT THE CONTRACTOR AND OWNER INDICATED
 ON THE WEST SIDE OF THE BUILDING WHERE THEY WERE GOING
 TO OPEN FRONTAGE TO CLEMATIS ST FOR THE SECOND MEANS OF
 EGRESS TO THE PUBLIC WAY, ALSO REVIEW FBC-B 1027.5
 EGRESS COURT REQUIREMENTS. PLEASE PROVIDE A SITE PLAN
 WITH THE EGRESS FOR THE BACK EXTERIOR STAIR THRU THE
 COURTYARD LEADING TO THE PUBLIC WAY.
  
 2D)(2)SEMI-COMPLIED.9/26/13 SUBMITTED 45 MINUTE RATED
 GLASS BLOCK FOR WINDOWS WITHIN 10' OF EXTERIOR STIAR.
 THE SECOND ISSUE WHEN THE EGRESS FROM THE COURTYARD TO
 THE PUBLIC WAY OCCURS IS THE DISTANCE BETWEEN THE TOP
 OF THE 2 STAIRWAYS IS NOT 1/2 THE OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 DIAGONAL DISTANCE PER FBC-B 1015.2.1. NOTE WHEN YOU
 FIGURE THE OVERALL DIAGONAL OF THE BUILDING WITHOUT THE
 TERRRACE WE ARE WITHIN ONE FOOT OF COMPLIANCE. AT SOME
 TIME SOMEONE HAS CUT IN A EXTERIOR DOORWAY AND CREATED
 A ROOF TOP TERRACE MAKING THE OVER ALL DIAGONAL
 DISTANCE A GREATER DISTANCE FOR THE STAIRS TO BE APART,
 AND NOT CODE COMPLIANT.
  
 EVEN IF YOU LOOK AT UNIT 203 THE FURTHEST POINT ON THE
 TERRACE THE TRAVEL DISTANCE TO THE BOTTOM OF THE STAIRS
 IS OVER 75 FEET. THE FURTHEST DISTANCE FROM THE
 FURTHEST POINT ON THE TERRACE TO THE TOP LANDING AT THE
 BACK STAIR IS APPROX. 68 FEET, OUTSIDE OF THE BUILDING
 THE BUILDING OFFICIAL WILL APPROVE THIS DISTANCE BUT
 THE BATHROOM WINDOW IN UNIT DOES NEED TO BE 3/4 HOUR
 FIRE RATED, IT IS WITHIN 10 FEET OF THE EXTERIOR STAIR,
 FBC-B 1026.6 AND THE EXTERIOR DOOR WILL NEED TO BE 1
 HOUR FIRE RATED.
  
 3) LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING
 INFORMATION:
 3A COMPLIED.
 3B) COURTYARD 2010 FBC-B 1027.5.
 3C) STAIRWELL WALL RATINGS, 2010 FBC-B 1022.1, & 2010
 EXISTING BUILDING CODE 912.5.3 EXCEPTION.
 3D) 2010 EXISTING BUILDING CODE 912.4.4. HANDRAILS
 SHALL COMPLY WITH 705.9 IN AREAS OF CHANGE OF
 OCCUPANCY. HANDRAILS SHALL BE THE FULL LENGTH OF THE
 RUN OF THE STEPS ON AT LEAST ONE SIDE.
 3E) 2010 EXISTING BUILDING CODE 912.8 ACCESSIBILITY.
 3F) 2010 FBC-ACCESSIBILITY CODE 202.4.1
 DISPROPORTIONATE COST.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By jwitmer Date 2013-09-09 Time 12:33 Rev Time 0.00
Received By jwitmer Date 2013-09-09 Time 10:52 Sent To  
Notes
2013-09-09 12:26:48BUILDING PLAN REVIEW
 PERMIT: 13080797
 ADD: 513 CLEMATIS ST UNITS # ????
 CONT: LARRY B. ROWE
 TEL: (561)835-17999
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1SST REVIEW
 DATE: SEPT 09/ 2013
 ACTION: DENIED
  
 1) CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION.
 107.1. THE DESIGNER OF RECORD (CONTRACTOR) IS TO SIGN
 THE PLAN, PRINT THEIR NAME AND LICENSE NUMBER ON THE
 PLAN.
  
 2) CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION.107.3.5.1.1. MINIMUM CRITERIA FOR COMMERCIAL
 PLAN REVIEW:
 2A) MINIMUM BUILDING TYPE
 2B) FIRE SPRINKLERRED OR NOT?
 2C) TYPE OF OCCUPANCY, THERE IS NO COMMERCIAL,
 ASSEMBLY, BUSNIESS, MERCANTILE OR LIVE/WORK UNITS?
 2D) LIFE SAFETY PLAN
  
 3) LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING
 INFORMATION:
 3A) OCCUPANCY 2010 FBC-B 302.1., TABLE 508.4 & TABLE
 707.3.9.
 3B ) MEANS OF EGRESS, COMMON PATH OF TRAVEL 2010 FBC-B
 1014.3
 3C) STAIRWELL WALL RATINGS, 2010 FBC-B 1022.1, & 2010
 EXISSTING BUILDING CODE 912.5.3 EXCEPTION.
 3D) 2010 EXISTING BUILDING CODE 912.4.4. HANDRAILS
 SHALL COMPLY WITH 705.9 IN AREAS OF CHANGE OF
 OCCUPANCY. HANDRAILS SHALL BE THE FULL LENGTH OF THE
 RUN OF THE STEPS ON AT LEAST ONE SIDE.
 3E) 2010 EXISTING BUILDING CODE 912.8 ACCESSIBILITY.
 3F) 2010 FBC-ACCESSIBILITY CODE 202.4.1
 DISPROPORTIONATE COST.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2013-10-10 Cont ID  
Sent By dharvey Date 2013-10-10 Time 09:03 Rev Time 0.00
Received By dharvey Date 2013-10-10 Time 09:03 Sent To  
Notes
2013-10-10 09:03:57NO ELECTRIC SHOWN, NO REVIEW PERFORMED. DH

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-11-02 Cont ID  
Sent By wjolin Date 2013-11-02 Time 13:39 Rev Time 0.00
Received By wjolin Date 2013-11-02 Time 13:31 Sent To  
Notes
2013-11-02 13:39:19513 CLEMATIS STREET
 PERMIT #13080797
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE UNIT DOORS (A,B, C), STORAGE ROOM DOOR, 1ST LEVEL
 DOOR NEED TO HAVE A FIRE RESISTANCE RATING, LATCH, AND
 AUTOMATIC CLOSER. WINDOWS TO BE FIRE RESISTANCE RATED
 ALSO. SEE BELOW.
  
 NONE OF THE DOORS AND WINDOWS ADJACENT TO THE EXTERIOR
 STAIRS ARE PROTECTED. PER NFPA 101 SECTION 7.2.2.6.3
 "SEPARATION AND PROTECTION OF OUTSIDE STAIRS: OUTSIDE
 STAIRS SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE
 RATING REQUIRED FOR ENCLOSED STAIRS WITH FIXED OR
 SELF-CLOSING OPENING PROTECTIVES." WALL CONSTRUCTION
 SHALL EXTEND AS FOLLOWS: (1) VERTICALLY FROM THE
 FINISHED GROUND LEVEL TO A POINT 10 FEET ABOVE THE
 TOPMOST LANDING OF THE STAIRS OR TO THE ROOFLINE,
 WHICHEVER IS LOWER (2) HORIZONTALLY FOR NOT LESS THAN
 10 FEET. PER NFPA 101 SECTION 7.2.2.6.4 "PROTECTION OF
 OPENINGS: ALL OPENINGS BELOW AN OUTSIDE STAIR SHALL BE
 PROTECTED WITH AN ASSEMBLY HAVING A MINIMUM 45-MINUTE
 FIRE PROTECTION RATING."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-09-19 Cont ID  
Sent By wjolin Date 2013-09-19 Time 16:52 Rev Time 0.00
Received By wjolin Date 2013-09-19 Time 14:53 Sent To  
Notes
2013-09-19 16:52:37513 CLEMATIS STREET
 PERMIT #13080797
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THE SECOND FLOOR HAS BOTH AN INSIDE EGRESS STAIR
 AND AN EXTERIOR STAIR; HOWEVER, THE STAIRS ARE NOT
 SEPARATED BY AT LEAST 42 FEET (84 FOOT DIAGONAL/ 2 = 42
 FEET [WORST CASE] OR 64 FOOT DIAGONAL/ 2 = 32 FEET
 [BEST CASE]) TO BE CONSIDERED TWO SEPARATE EXITS. NEW
 BUSINESS OCCUPANCIES ARE PERMITTED ONE EXIT PER NFPA
 101 SECTION 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED
 FOR A ROOM OR AREA WITH A TOTAL OCCUPANT LOAD OF FEWER
 THAN 100 PERSONS WHEN A SINGLE OUTSIDE STAIR IN
 ACCORDANCE WITH 7.2.2 IS INSTALLED AND WILL SERVE ALL
 FLOORS PERMITTED WITHIN THE 15 FEET VERTICAL TRAVEL
 LIMITATION.
  
 NONE OF THE DOORS AND WINDOWS ADJACENT TO THE EXTERIOR
 STAIRS ARE PROTECTED. PER NFPA 101 SECTION 7.2.2.6.3
 "SEPARATION AND PROTECTION OF OUTSIDE STAIRS: OUTSIDE
 STAIRS SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE
 RATING REQUIRED FOR ENCLOSED STAIRS WITH FIXED OR
 SELF-CLOSING OPENING PROTECTIVES." WALL CONSTRUCTION
 SHALL EXTEND AS FOLLOWS: (1) VERTICALLY FROM THE
 FINISHED GROUND LEVEL TO A POINT 10 FEET ABOVE THE
 TOPMOST LANDING OF THE STAIRS OR TO THE ROOFLINE,
 WHICHEVER IS LOWER (2) HORIZONTALLY FOR NOT LESS THAN
 10 FEET. PER NFPA 101 SECTION 7.2.2.6.4 "PROTECTION OF
 OPENINGS: ALL OPENINGS BELOW AN OUTSIDE STAIR SHALL BE
 PROTECTED WITH AN ASSEMBLY HAVING A MINIMUM 45-MINUTE
 FIRE PROTECTION RATING."
  
 PLANS DO NOT INDICATE WHERE THE EXTERIOR STAIR
 DISCHARGES TO. PER NFPA 101 SECTION 7.7.1 EXITS SHALL
 DISCHARGE OR LEAD TO A STREET, ALLEY, PUBLIC WAY, ETC.
  
 PLANS DO NOT INDICATE IF ANY OF THE TENANT SPACES ARE
 FIRE SEPARATED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By wjolin Date 2013-08-28 Time 11:18 Rev Time 0.00
Received By jwitmer Date 2013-09-09 Time 10:52 Sent To  
Notes
2013-08-28 11:18:05513 CLEMATIS STREET
 PERMIT #13080797
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES A CHANGE OF OCCUPANCY
 FROM RESIDENTIAL TO COMMERCIAL; HOWEVER, THE PLANS DO
 NOT INDICATE THE INTENDED COMMERCIAL OCCUPANCY
 (BUSINESS, MERCANTILE, ETC.)
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, FIRE RATE DOORS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE PERFORMED
 AT THIS TIME.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-10 Cont ID  
Sent By jwitmer Date 2013-10-10 Time 09:04 Rev Time 0.00
Received By dharvey Date 2013-09-12 Time 15:02 Sent To  
Notes
2013-09-13 15:02:45B19
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-04 Cont ID  
Sent By shill Date 2013-09-12 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2013-08-21 Time 13:32 Sent To  
Notes
2013-08-22 13:33:10SENT TO B19 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-10-17 Cont ID  
Sent By jwitmer Date 2013-10-17 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2013-10-17 Time 14:19 Sent To FIRE
Notes
2013-10-17 14:21:30IMPACT FEES ASSESSMENT
 CHANGE OF OCCUPANCY UPSTAIRS FROM RESIDENTIAL TO
 BUSINESS.
 TRACKING NUMBER MU-2013-021855-0000
 AMOUNT $855.82

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-09-24 Cont ID  
Sent By jwitmer Date 2013-09-24 Time 12:45 Rev Time 0.00
Received By jwitmer Date 2013-09-24 Time 12:45 Sent To  
Notes
2013-09-24 12:45:33BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-09-24 Cont ID  
Sent By jwitmer Date 2013-09-24 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2013-09-24 Time 12:44 Sent To  
Notes
2013-09-24 12:44:53BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-09-09 Cont ID  
Sent By hmoser Date 2013-09-09 Time 15:23 Rev Time 0.00
Received By hmoser Date 2013-09-09 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-09-09 Cont ID  
Sent By lwagner Date 2013-09-09 Time 15:43 Rev Time 0.00
Received By lwagner Date 2013-09-09 Time 15:40 Sent To  
Notes
2013-09-09 15:44:42FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 NO PLUMBING SHOWN AT THIS TIME. HOWEVER, DEPENDING UPON
 THE OCCUPANCY TYPE, THERE MAY BE FIXTURE REQUIREMENTS.
 BUSINESS OCCUPANCIES WITH UNDER 15 OCCUPANTS WOULD NOT
 REQUIRE A DRINKING FOUNTAIN.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-05 Cont ID  
Sent By aaponte Date 2013-09-05 Time 11:34 Rev Time 0.00
Received By aaponte Date 2013-09-05 Time 11:34 Sent To  
Notes
2013-09-05 11:35:19CHANGE OF OCCUPANCY INTO A COMMERCIAL USE.
2013-08-28 14:49:108/28/13