2013-08-17 12:55:16 | BUILDING/ PLUMBING PLAN REVIEW |
| PERMIT: 13080619 |
| ADD: 255 EVERNIA SUITE # 1507 |
| CONT: CREATIVE HOMEWORKS |
| TEL: (561)506-4466 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: AUGUST 17/2013 |
| ACTION: PROVISO |
| |
| BUILDING PROVISO: |
| 1) SUBMIT PRODUCT TESTING FOR FLOOR INSULATION: |
| 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING |
| FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| |
| 2) NEW SHOWER COMPARTMENT BACKER BOARD TO COMPLY WITH: |
| 2010 FBC-B 2509.2 BASE FOR TILE. GLASS MAT |
| WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE |
| NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR |
| NONASBESTOS FIBER-MAT REINFORCED CEMENT SUBSTRATE |
| SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325 |
| AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| 2509.3 LIMITATIONS. |
| WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| IN THE FOLLOWING LOCATIONS: |
| 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| COMPARTMENTS. |
| 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD. |
| |
| PLUMBING PROVISO: |
| |
| 2010 FBC-P 417.5.2 SHOWER LINING. FLOORS UNDER SHOWER |
| COMPARTMENTS, SUCH LINERS SHALL TURN UP ON ALL SIDES AT |
| LEAST 2 INCHES (51 MM) ABOVE THE FINISHED THRESHOLD |
| LEVEL. LINERS SHALL BE RECESSED AND FASTENED TO AN |
| APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE REQUIRED |
| FOR WALL COVERING, AND SHALL NOT BE NAILED OR |
| PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE |
| THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED |
| ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE |
| OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT |
| JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED |
| LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |