Plan Review Details - Permit 13080523
Plan Review Stops For Permit 13080523 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2013-08-23 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-08-23 |
Time |
07:11 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-08-23 |
Time |
07:00 |
Sent To |
|
|
Notes |
2013-08-23 07:12:42 | SEE NOTES ON PLANS | | | | 18.4.1.3* SOUND FROM NORMAL OR PERMANENT SOURCES, | | HAVING A DURATION GREATER THAN 60 SECONDS, SHALL BE | | INCLUDED WHEN MEASURING MAXIMUM AMBIENT SOUND LEVEL. | | SOUND FROM TEMPORARY OR ABNORMAL SOURCES SHALL NOT BE | | REQUIRED TO BE INCLUDED WHEN MEASURING MAXIMUM AMBIENT | | SOUND LEVEL. | | | | | | 18.4.1.4 AUDIBLE NOTIFICATION APPLIANCES FOR ALERT AND | | EVACUATION SIGNAL TONES SHALL MEET THE REQUIREMENTS OF | | 18.4.3 (PUBLIC MODE AUDIBLE REQUIREMENTS), 18.4.4 | | (PRIVATE MODE AUDIBLE REQUIREMENTS), 18.4.5 (SLEEPING | | AREA REQUIREMENTS), OR 18.4.6 (NARROW BAND TONE | | SIGNALING FOR EXCEEDING MASKED THRESHOLDS), AS | | APPLICABLE. | | | | 18.4.3* PUBLIC MODE AUDIBLE REQUIREMENTS. | | | | 18.4.3.1* TO ENSURE THAT AUDIBLE PUBLIC MODE SIGNALS | | ARE CLEARLY HEARD, UNLESS OTHERWISE PERMITTED BY | | 18.4.3.2 THROUGH 18.4.3.5, THEY SHALL HAVE A SOUND | | LEVEL AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND | | LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A | | DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, | | MEASURED 5 FT (1.5 M) ABOVE THE FLOOR IN THE AREA | | REQUIRED TO BE SERVED BY THE SYSTEM USING THE | | A-WEIGHTED SCALE (DBA). | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2013-08-21 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2013-08-20 |
Time |
|
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2013-08-20 |
Time |
14:16 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-08-23 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-08-23 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-08-14 |
Time |
15:31 |
Sent To |
|
|
Notes |
2013-08-23 07:13:05 | TO J WITMER | 2013-08-14 15:31:14 | ROUTED TO FIRE |
|
|
|
Account Summary | Usage Policy | Privacy Policy