Plan Review Stops For Permit 13080504 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2013-08-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-08-20 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-08-20 |
Time |
11:49 |
Sent To |
|
|
Notes |
2013-08-20 11:53:43 | ****PROVISO**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | ****REVISION REQUIRED SUBJECT TO INSPECTOR'S | | DISCRETION**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATION FOR THE | | EMERGENCY MEANS OF ESCAPE, FBC R310.4: | | | | THE MEANS OF ESCAPE SHALL BE WITHIN THE FIRST FLOOR OF | | THE DWELLING OR DWELLING UNIT AND SHALL NOT BE LOCATED | | WITHIN A GARAGE WITHOUT A SIDE-HINGED DOOR LEADING | | DIRECTLY TO THE EXTERIOR. OCCUPANTS IN ANY PART OF THE | | DWELLING OR DWELLING UNIT SHALL BE ABLE TO ACCESS THE | | MEANS OF ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR | | NOT UNDER THEIR CONTROL. | | | | IF COMPLIANCE WITH THIS CODE SECTION IS NOT CLEAR ON | | THE REVISED FLOOR PLAN TO BE PROVIDED AT INSPECTION, | | SUBJECT TO INSPECTOR'S DISCRETION A REVISION IS | | REQUIRED. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-08-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2013-08-20 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2013-08-14 |
Time |
13:08 |
Sent To |
|
|
Notes |
2013-08-14 13:08:49 | MISC 1 |
|
|
|