Plan Review Details - Permit 13080442
Plan Review Stops For Permit 13080442
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-15 Cont ID  
Sent By rmcdouga Date 2013-08-15 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2013-08-15 Time 15:17 Sent To  
Notes
2013-08-15 16:15:00SEE NOTE 9 ON PAGE 2 OF 12 FOR REQUIRED FASTENER
 WITHDRAWAL RESISTANCE TEST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-14 Cont ID  
Sent By rmcdouga Date 2013-08-14 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2013-08-14 Time 10:29 Sent To  
Notes
2013-08-14 10:46:572010 FBC
  
 DENIED BY BUILDING
  
 1) THIS STRUCTURE IS LOCATED IN A 170 MPH VULT / 132
 MPH VASD WIND SPEED AND THE EXPOSURE CATEGORY IS D. THE
 REQUIRED UPLIFT FOR A ROOF SLOPE OF 0 TO 7 DEGREES WITH
 A 20 FT MEAN ROOF HEIGHT IS -82 PSF IN ROOF ZONE 2 AND
 -123 PSF IN ROOF ZONE 3. THE MAXIMUM DESIGN PRESSURE IS
 -60.0 PSF FOR THE SEALOFLEX W-5 SYSTEM THAT WAS
 SPECIFIED. THIS DESIGN PRESSURE DOES NOT MEET THE
 REQUIRED PRESSURES FOR ZONES 2 AND 3. ACCORDING TO THE
 PRODUCT APPROVAL NOTE #8 THE MAXIMUM DESIGN PRESSURE
 FOR FULLY BONDED ASSEMBLIES CAN NOT BE INCREASED BY
 RATIONAL ANALYSIS. PLEASE SUBMIT PRODUCT APPROVALS FOR
 A COMPLIANT ASSEMBLY. DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-14 Cont ID  
Sent By rmcdouga Date 2013-08-14 Time 12:50 Rev Time 0.00
Received By rmcdouga Date 2013-08-13 Time 15:07 Sent To  
Notes
2013-08-13 15:08:11SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.