Plan Review Details - Permit 13080341
Plan Review Stops For Permit 13080341
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-14 Cont ID  
Sent By rmcdouga Date 2013-08-14 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2013-08-14 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-12 Cont ID  
Sent By rmcdouga Date 2013-08-12 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2013-08-12 Time 10:29 Sent To  
Notes
2013-08-12 11:14:392010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED 220 FEET FROM THE
 INTERCOASTAL WATERWAY, THEREFORE, IT IS CLASSIFIED AS
 EXPOSURE D. PLEASE REVISE RAS 117 CALCULATIONS FOR THE
 FLAT ROOF. FBC R301.2.1.4.3
  
 2) PROVIDE TWO COPIES OF A ROOF PLAN WITH THE
 DIMENSIONS FOR EACH AREA AND SPECIFY THE SLOPED & FLAT
 AREAS. SPECIFY THE PITCH OF THE SLOPED ROOF ON THE
 PLANS. FBC 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]