Plan Review Details - Permit 13080319
Plan Review Stops For Permit 13080319
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-09 Cont ID  
Sent By jgomez Date 2013-08-09 Time 17:55 Rev Time 0.00
Received By jgomez Date 2013-08-09 Time 17:55 Sent To  
Notes
2013-08-09 17:56:01REVIEWED AND APPROVED BY DOUGH HARVEY. SEE STAMPED
 PLAN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-09-09 Cont ID  
Sent By jgomez Date 2013-09-09 Time 13:42 Rev Time 0.00
Received By jgomez Date 2013-09-09 Time 13:42 Sent To  
Notes
2013-09-09 13:42:37A/C AS BUILTS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-19 Cont ID  
Sent By jgomez Date 2013-08-19 Time 18:47 Rev Time 0.00
Received By jgomez Date 2013-08-16 Time 16:28 Sent To  
Notes
2013-08-16 16:28:31TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-09 Cont ID  
Sent By jgomez Date 2013-08-09 Time 18:03 Rev Time 0.00
Received By jgomez Date 2013-08-08 Time 09:37 Sent To  
Notes
2013-08-09 09:37:47** EXPEDITED **
  
 TO DH DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2013-09-09 Cont ID  
Sent By jgomez Date 2013-09-09 Time 13:42 Rev Time 0.00
Received By jgomez Date 2013-09-09 Time 13:42 Sent To  
Notes
2013-09-09 13:44:01A/C AS BUILT REVIEWED UNDER REVISION #13080876. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-08-19 Cont ID  
Sent By jgomez Date 2013-08-19 Time 18:38 Rev Time 0.00
Received By jgomez Date 2013-08-19 Time 18:17 Sent To  
Notes
2013-08-19 18:38:25RESIDENTIAL (R3) REVISION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PLANS SUBMITTED DON'T SHOW THE SIZE OF THE TRANSFER
 GRILLS ABOVE THE DOORS. THEREFORE, UNABLE TO VERIFY
 COMPLIANCE WITH SEC. M1602.4 EXCEPTION #2.
  
 2- BALANCED RETURN AIR IS FOR HABITABLE ROOMS ONLY.
 SEC. M1602.4 EXCEPTION #3. PLANS SHOW TRANSFER GRILLS
 ON THE BATHROOMS. REVISE AS REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-09 Cont ID  
Sent By jgomez Date 2013-08-09 Time 17:56 Rev Time 0.00
Received By jgomez Date 2013-08-09 Time 17:28 Sent To  
Notes
2013-08-09 18:01:26RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: 2010 FBC.
  
 1- DUCTWORK IN MAIN HOUSE DOESN'T COMPLY WITH THE
 RETURN AIR REQUIREMENTS OF SEC. M1602 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712