Plan Review Details - Permit 13080190
Plan Review Stops For Permit 13080190
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-08-27 Cont ID  
Sent By mgonzale Date 2013-08-27 Time   Rev Time 1.00
Received By mgonzale Date 2013-08-27 Time   Sent To I
Notes
2013-08-27 11:14:12PROVISOS:
  
 EXISTING 4" WATER LINE STUB IS AVAILABLE AT THAT
 LOCATION FOR FIRE LINE HOWEVER IF NOT USED IT MUST BE
 CAPPED AT MAIN.
 COORDINATE WITH TRAVIS HAWTHORNE (561) 644-7451
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-09-27 Cont ID  
Sent By wjolin Date 2013-09-27 Time 09:19 Rev Time 0.00
Received By wjolin Date 2013-09-27 Time 08:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-21 Cont ID  
Sent By wjolin Date 2013-08-21 Time 18:31 Rev Time 0.00
Received By wjolin Date 2013-08-21 Time 16:53 Sent To M
Notes
2013-08-21 18:31:36700 NORTH DIXIE HIGHWAY - FIRE STATION #7
 PERMIT #13080190
 MASTER #11120073
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE A 1 ZONE SYSTEM (1 FLOW SWITCH) FOR THE
 BUILDING. THERE IS NO NEED FOR A SECOND FLOOR SWITCH
 AND THIS WILL BE MISLEADING IF THERE IS AN OPERATING
 SECOND FLOOR FLOW SWITCH BECAUSE SEVERAL FIRST FLOOR
 SPRINKLERS (TRUCK BAYS AND GENERATOR ROOM) ARE BEING
 SUPPLIED FROM THE SECOND FLOOR EVEN THOUGH THE
 SPRINKLERS ARE PROTECTING THE FIRST FLOOR.
  
 NO SPRINKLER PROTECTION PROVIDED IN TWO SMALL CLOSESTS
 IN GREAT ROOM #111.
  
 NO SPRINKLER PROTECTION PROVIDED AT THE TOP OF THE
 DUMBWAITER SHAFT.
  
 PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW
 SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO
 THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER
 ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE DRY PIPE
 PREACTION SYSTEM.
  
 HYDRAULIC AREA #1 CALCULATES A MAXIMUM OF 3 SPRINKLERS
 ON AN 1-1/4" BRANCHLINE; HOWEVER, THERE ARE ADJACENT
 BRANCHLINES WITH AS MUCH AS 6 SPRINKLERS ON A 36 FOOT
 SECTION OF BRANCHLINE THAT WILL BE MORE HYDRAULICALLY
 DEMANDING. PROVIDE AN ADDITIONAL REDUCED AREA (1192
 SQ.FT.) HYDRAULIC CALCULATION FOR THE UTILITIES CALL
 TAKER ROOM #3.22 AREA.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-27 Cont ID  
Sent By wjolin Date 2013-09-27 Time 09:19 Rev Time 0.00
Received By wjolin Date 2013-09-17 Time 14:42 Sent To  
Notes
2013-09-17 14:42:33SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-29 Cont ID  
Sent By shill Date 2013-08-29 Time 11:40 Rev Time 0.00
Received By shill Date 2013-08-06 Time 10:51 Sent To  
Notes
2013-08-27 15:01:138/27 TO ZONING
  
2013-08-06 10:51:24ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-26 Cont ID  
Sent By hmoser Date 2013-08-26 Time 14:44 Rev Time 0.00
Received By hmoser Date 2013-08-26 Time 14:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-28 Cont ID  
Sent By jroach Date 2013-08-28 Time 15:15 Rev Time 0.00
Received By jroach Date 2013-08-28 Time 09:08 Sent To  
Notes
***NONE***