Plan Review Details - Permit 13080160
Plan Review Stops For Permit 13080160
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-10-30 Cont ID  
Sent By shill Date 2013-10-30 Time 09:04 Rev Time 0.00
Received By shill Date 2013-10-30 Time 09:04 Sent To  
Notes
2013-10-30 09:05:55OK AS 489 EXEMPT FOR FACE CHANGE AND FOR NEW SIGN
 (VINYL W/TAPCONS TO BUILDING) PER ROBERT BROWN,
 BUILDING OFFICIAL
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 15:53 Rev Time 0.00
Received By shill Date 2013-10-26 Time 15:53 Sent To  
Notes
2013-10-26 15:57:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SCOPE OF WORK ON APPLICATION CONFLICTS WITH PLAN.
  
 APPLICATION INDICATES THAT A NEW SIGN WILL BE
 INSTALLED. APPLICANT TOLD PREVIOUS REVIEWER THAT THIS
 IS A FACE CHANGE ONLY. MY UNDERSTANDING (PER JOHN
 FRASCA, CODE OFFICER) IS THAT ONE SIGN IS A FACE CHANGE
 BUT THE OTHER SIGN SHOWN IS A NEW SIGN.
  
 A CALL WAS PLACED TO THE APPLICANT, BUT I HAVE NOT
 RECEIVED A RETURN CALL.
  
 SUGGESTED COURSE OF ACTION -
  
 EITHER REVISE SCOPE TO FACE CHANGE, AND THE FACE CHANGE
 WILL BE ISSUED, SEPARATE PERMIT REQUIRED FOR THE NEW
 SIGN,
  
 OR
  
 REVISE SCOPE ON PERMIT TO INCLUDE FACE CHANGE AND
 SUBMIT STRUCTURAL DRAWINGS FOR THE NEW SIGN FBC 1609.
 DRAWINGS ARE TO INCLUDE ALL STRUCTURAL DETAILS, WIND
 DESIGN CRITERIA, AND THE NAME AND SIGNATURE OF THE
 INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN. IF
 PLANS BY A DESIGN PROFESSIONAL ARE NOT SUBMITTED,
 CALCULATIONS MAY BE REQUIRED. A CONTRACTOR MAY BE
 REQUIRED SUBJECT TO BUILDING OFFICIAL'S DISCRETION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-02 Cont ID  
Sent By dharvey Date 2013-10-02 Time 06:41 Rev Time 0.00
Received By dharvey Date 2013-10-02 Time 06:41 Sent To  
Notes
2013-10-02 06:42:11NO CHANGES OR MODIFICATIONS TO EXISTING SIGNS. FACE
 CHANGE ONLY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By dharvey Date 2013-08-07 Time 17:37 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 17:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2013-10-30 Cont ID  
Sent By dharvey Date 2013-10-02 Time 06:40 Rev Time 0.00
Received By shill Date 2013-10-02 Time 06:35 Sent To  
Notes
2013-10-02 06:41:25FACE CHANGES ONLY. NO ELECTRICAL WORK, NO STRUCTURAL
 WORK. ANY CHANGES TO EITHER REQUIRE SIGNED AND SEALED
 PLANS IN FULL COMPLIANCE WITH FLORIDA BUILDING CODE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By dharvey Date 2013-08-07 Time 17:37 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 17:36 Sent To  
Notes
2013-08-07 17:39:34PROVIDE CONTRACTOR PERMIT AND CONTRACTOR INFORMATION
2013-08-07 17:37:41INSUFFICIENT INFORMATION PROVIDED FOR A COMPLETE
 REVIEW. COMPLETE ENGINEERING FOR ELECTRICAL AND
 WINDLOAD. PROVIDE ELECTRICAL DETAILS INCLUDING LIGHTING
 SIZE, TYPE, WATTAGE, DESIGN, DISCONNECT, CONTROL, ETC.
 PROVIDE MOUNTING DETAILS SHOWING STRUCTURE TYPE, METHOD
 OF ATTACHEMENT AND ASSOCIATED ENGINEERING TO VERIFY THE
 ATTACHEMENT. EXACT LOCATION SURVEY REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-02 Cont ID  
Sent By dharvey Date 2013-10-02 Time 06:42 Rev Time 0.00
Received By dharvey Date 2013-09-05 Time 07:51 Sent To  
Notes
2013-10-02 06:42:41TO S HILL
2013-09-14 09:41:569/14 TO ELEC
  
2013-09-06 07:51:56SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By dharvey Date 2013-08-07 Time 17:38 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 15:14 Sent To  
Notes
2013-08-07 17:38:53IN DENIED UNDER "M" AS NO CONTRACTOR IS SPECIFIED. M IS
 THE CONTACT PERSON
2013-08-05 15:14:30ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2013-09-09 Cont ID  
Sent By llouie Date 2013-09-09 Time 12:25 Rev Time 0.00
Received By llouie Date 2013-09-09 Time 12:25 Sent To B
Notes
2013-09-09 12:27:53ZONING PASSED WITH THE FOLLOWING PROVISO:
  
 1.) SIGNAGE ON WEST FACADE (MILITARY TRAIL): FACE
 CHANGE ONLY. NO STRUCTURE MODIFICATION PERMITTED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By llouie Date 2013-08-07 Time 15:47 Rev Time 0.00
Received By llouie Date 2013-08-07 Time 15:46 Sent To E
Notes
2013-08-07 16:09:40ZONING FAILED DUE TO INSUFFICIENT INFORMATION PROVIDED
 WITH THE APPLICATION. PLEASE SUBMIT/PROVIDE THE
 FOLLOWING INFORMATION:
  
 1.) PROVIDE A SURVEY AND IDENTIFY WHICH BUILDING THE
 PROPOSED SIGNAGE IS TO BE LOCATED ON.
  
 2.) PROVIDE INFORMATION ON THE DIMENSIONS OF ALL
 PROPOSED SIGNAGE (I.E. HEIGHT, WIDTH, TOTAL SF, ETC.).
  
 3.) PROVIDE BUILDING FACADE DIMENSIONS.
  
 4.) SPECIFY THE TYPE OF SIGNAGE.
  
 THE ABOVE INFORMATION IS REQUIRED TO CALCULATE THE
 MAXIMUM SIGN AREA PERMITTED ON THE BUILDING FACADE PER
 ZLDR S. 94-408 AND S.94-409.
  
 DON'T HESITATE TO CONTACT ME SHOULD YOU HAVE QUESTIONS.
  
 LINDA LOUIE, PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 EMAIL: [email protected]
  