Plan Review Details - Permit 13080144
Plan Review Stops For Permit 13080144
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-05 Cont ID  
Sent By albarran Date 2013-11-05 Time 15:10 Rev Time 0.00
Received By albarran Date 2013-11-04 Time 09:58 Sent To I
Notes
2013-11-05 15:11:47THIS AFTERNOON I RECEIVED AN EMAIL CLARIFICATION FROM
 THE ELECTRICAL ENGINEER, AS COPY OF WHICH IS INCLUDED
 IN THE FILE.
 SENT TO SH DESK
2013-11-04 11:15:27WAITING ON A CONDUCTOR PROPERTY CLARIFICATION ON PAGE
 E2.1 REQUESTED VIA EMAIL TO GARY CLEMENS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-05 Cont ID  
Sent By dharvey Date 2013-08-05 Time 17:18 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 17:18 Sent To Z
Notes
2013-08-05 17:18:29WIND LOAD WAS PERFORMED WITHOUT FIXTURES. PROVIDE
 REVISED ENGINEERED WIND LOAD SHOWING THE FIXTURE AND
 ARMS IN PLACE. PLANS AND ENGINEERING DO NOT AGREE FOR
 POLE INSETION DEPTH.
 PROVIDE CLEAR PHOTOMETRICS OF DESIGN TO ENSURE SAFETY
 AND LIGHTING BEYOND THE PROPERTY LINE DOES NOT EXCEED
 .5 FC AND HOW IT WILL BE ACHIEVED IN ACCORDANCE WITH
 THE LISTING OF THE FIXTURE. CLEARLY IDENTIFY POLE
 LOCATIONS AND FIXTURE CONFIGURATION ON PHOTOMETRIC
 PLAN.
 PROVIDE LISTING INFORMATION FOR FIXTURES AND ALL
 COMPONENTS
 PROVIDE VOLTAGE DROP CALCS SHOWING COMPLIANCE WITH
 FBC-EC 505.7.3
 PROVIDE EXTERIOR LIGHTING POWER DENSITY INFORMATION PER
 FBC-EC 505.6
 PROVIDE TIME CLOCK WITH PROGRAMING BACKUP FOR MINIMUM
 10 HOURS PER FBC-EC 505.2.4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-13 Cont ID  
Sent By shill Date 2013-11-13 Time 13:08 Rev Time  
Received By skennedy Date 2013-10-22 Time 17:49 Sent To  
Notes
2013-11-06 08:52:2011/4 TO ZONING (NEW SHEET) SH
  
2013-10-22 17:50:06SENT TO ELECTRICAL SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-30 Cont ID  
Sent By dmalone Date 2013-08-19 Time 15:56 Rev Time 0.00
Received By dmalone Date 2013-08-05 Time 13:55 Sent To  
Notes
2013-08-05 13:55:26ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 2 Status N Date 2013-11-06 Cont ID  
Sent By dmalone Date 2013-11-06 Time 16:17 Rev Time 0.00
Received By llouie Date 2013-11-06 Time 09:47 Sent To E
Notes
2013-11-06 09:48:0411/6/13 - ZONING REVIEW NOT REQUIRED PER DENISE MALONE.
 LL

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-30 Cont ID  
Sent By dmalone Date 2013-08-19 Time 15:56 Rev Time 0.00
Received By dmalone Date 2013-08-08 Time 12:05 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved