Plan Review Details - Permit 13080114
Plan Review Stops For Permit 13080114 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-08-16 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-08-16 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-08-16 |
Time |
16:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-08-07 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-08-07 |
Time |
06:54 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-08-07 |
Time |
06:44 |
Sent To |
|
|
Notes |
2013-08-07 06:54:25 | PROVIDE INFORMATION ON REMAINDER OF SYSTEM. IDENTIFY | | ZONES THAT EXIST. ENSURE COMPATIBILITY OF EXISTING | | SYSTEM AND COMPONENTS WITH NEW ALARM PANEL. SCOPE OF | | WORK STATES THIS WORK IS ONLY IN THIS SUITE AND ON THIS | | FLOOR. PLANS APPEAR TO INDICATE OTHERWISE. SEE FIRE | | REVIEW COMMENTS |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2013-08-14 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-08-14 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-08-14 |
Time |
16:44 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2013-08-06 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2013-08-06 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2013-08-06 |
Time |
16:40 |
Sent To |
E |
|
Notes |
2013-08-06 16:45:28 | 901 NORTHPOINT PARKWAY - SUITE #400-404 | | PERMIT #13080114 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PER THE FLORIDA BUILDING CODE AND FLORIDA STATUTE 471, | | PLANS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL | | ENGINEER. THE CURRENT SIGN/SEAL IS FROM AN ARCHITECT | | (SANDRA PUERTA). | | | | FBC SECTION105.3.1.2: NO PERMIT MAY BE ISSUED FOR ANY | | BUILDING CONSTRUCTION, ERECTION, ALTERATION, | | MODIFICATION, REPAIR, OR ADDITION UNLESS THE APPLICANT | | FOR SUCH PERMIT PROVIDES TO THE ENFORCING AGENCY WHICH | | ISSUES THE PERMIT ANY OF THE FOLLOWING DOCUMENTS WHICH | | APPLY TO THE CONSTRUCTION FOR WHICH THE PERMIT IS TO BE | | ISSUED AND WHICH SHALL BE PREPARED BY OR UNDER THE | | DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471, | | FLORIDA STATUTES: (3) ANY SPECIALIZED MECHANICAL, | | ELECTRICAL, OR PLUMBING DOCUMENT FOR ANY NEW BUILDING | | OR ADDITION WHICH INCLUDES A MEDICAL GAS, OXYGEN, | | STEAM, VACUUM, TOXIC AIR FILTRATION, HALON, OR FIRE | | DETECTION AND ALARM SYSTEM WHICH COSTS MORE THAN | | $5,000. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2013-08-16 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-08-16 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-08-09 |
Time |
07:52 |
Sent To |
|
|
Notes |
2013-08-16 16:31:30 | TO S HILL | 2013-08-12 07:53:16 | SENT TO FIRE BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-08-12 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-08-07 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-08-05 |
Time |
09:01 |
Sent To |
|
|
Notes |
2013-08-07 07:01:08 | PLACED IN DENIED UNDER "S" DH | 2013-08-05 09:02:34 | ROUTED TO FIRE |
|
|
|