Plan Review Details - Permit 13071145
Plan Review Stops For Permit 13071145
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-11-01 Cont ID  
Sent By jgomez Date 2013-11-01 Time 15:55 Rev Time 0.00
Received By jgomez Date 2013-11-01 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-10-30 Cont ID  
Sent By jgomez Date 2013-10-28 Time 11:26 Rev Time 0.00
Received By jgomez Date 2013-10-28 Time 11:26 Sent To  
Notes
2013-10-28 12:00:24THIRD BUILDING REVIEW COMMENTS.
  
 1- TITLE BLOCK FOR SHEETS P-01 AND E-01 HAVE THE NAME
 OF THE ENGINEER JOHN H. CRESWELL AND THE ARCHITECTS'
 OFFICE "SSC DESIGN GROUP". ACCORDING TO FLORIDA
 STATUTES 471 AND 481 ALL SHEETS WITH AN ENGINEER OR
 ARCHITECT NAME MUST BE SIGNED AND SEALED BY THE
 LICENSED PROFESSIONAL. OTHERWISE, REMOVE THE NAMES FROM
 THE TITLE BLOCK AND PROVIDE ONLY THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 2- REVISE DETAIL 3 ON SHEET A1. CONCRETE BLOCK WALL
 INSULATION R-VALUE TO MATCH THE ONE REQUIRED BY THE
 ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 3- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING
 FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL
 ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY
 CONSERVATION AND TABLE 405.6.6. (***NOTE: CALCULATIONS
 ARE DONE FOR THE ENTIRE HOUSE, THEREFORE IF TAKING
 CEILING FAN CREDIT, THEN ALL THE ROOMS NEED TO HAVE
 CEILING FANS).
  
 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT
 COMMENT)
  
  
 ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-19 Cont ID  
Sent By jgomez Date 2013-09-19 Time 13:48 Rev Time 0.00
Received By jgomez Date 2013-09-19 Time 13:48 Sent To  
Notes
2013-09-19 13:59:49RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- A) ENGINEER OF RECORD SIGNED AND SEALED PLANS ON THE
 WRONG SPACE IN THE TITLE BLOCK, NOT UNDER HIS NAME AND
 LICENSE NUMBER SPACE. HE SIGNED THE SPACE FOR "SSC
 DESIGN GROUP", WHICH IS AN ARCHITECTURAL FIRM THAT
 DOESN'T HAVE A FLORIDA FIRM LICENSE NUMBER. RESUBMIT
 DRAWINGS WITH SIGNATURE ON CORRECT SPACE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 B) ENGINEER OF RECORD TO SIGN AND SEAL ALL PLANS
 SUBMITTED AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 SOME DRAWINGS ARE MISSING THE SEAL AND SIGNATURE.
  
 2- NEED ARCHITECTURAL FIRM FLORIDA LICENSE NUMBER FOR
 "SSC DESIGN GROUP" AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTE. (REPEAT COMMENT). OR REMOVE NAME FROM TITLE
 BLOCK.
  
 3- REVISE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
 A) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH ON
 ITEM #7 TO MATCH PLANS (IT'S NOT 2.000FT).
  
 B) REVISE ROOF MATERIAL ON PAGE 2 OF 7. THERE ARE NOT
 SHINGLES ON THE HOUSE.
  
 C) REVISE ALL DOORS ON PAGE 4 OF 7 TO MATCH PLANS AND
 PRODUCT APPROVALS SUBMITTED. REVISE TYPE, SIZE ETC. TO
 MATCH PLANS.
  
 D) REVISE ALL WINDOWS TO MATCH PLANS AND PRODUCT
 APPROVALS. AND REVISE THE OVERHANG DEPTH AND SEPARATION
 TO MATCH PLANS.
  
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE CORRECT BUILDER'S NAME.
  
 4- PROVIDE DETAILS AND SPECIFICATIONS ON PLANS SHOWING
 HOW OBTAINING R-13 ON CONCRETE BLOCK WALLS FOR INTERIOR
 AND EXTERIOR WALLS AS SPECIFIED ON THE ENERGY
 CALCULATIONS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 5- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING
 FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL
 ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY
 CONSERVATION AND TABLE 405.6.6.
  
 6- REVISE/COORDINATE ALL WINDOW AND DOOR SCHEDULE
 INFORMATION TO MATCH THE ENERGY CALCULATIONS. MATERIAL
 TYPE ETC. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8"
 PRECAST LINTEL. NOA 13-0321.07 SUBMITTED IS FOR 4", 6"
 & 12" LINTELS.
  
 B) INSWING WOOD DOOR AS SHOWN ON PLANS FOR NEW CABANA
 BATHROOM. (REPEAT COMMENT).
  
 C) ENTRY DOORS THAT MEET THE CALCULATED DESIGN
 PRESSURES. FLORIDA PRODUCT APPROVAL FL9390-R2 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY SIZE
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. (REPEAT
 COMMENT).
  
 E)FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 ***NOTE: ALSO, NEED PRODUCT APPROVAL FOR ALL WINDOW
 SIZES SHOWN ON PLANS. SEE WINDOW SCHEDULE. (REPEAT
 COMMENT).
  
 8- ABOVE PRODUCT APPROVALS TO BE REVIEWED AND APPROVED
 IN WRITING BY THE ENGINEER OF RECORD (NOT SIGNING AND
 SEALING). SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 9- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM AS
 REQUIRED BY SEC. R315. (REPEAT COMMENT).
  
 10- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT
 COMMENT)
  
  
 ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  
 ****NOTE: PROVIDE COMPLETE INFORMATION UNDER SEPARATE
 PERMITS FOR: POOL WORK, NEW GENERATOR, SCREEN ENCLOSURE
 WORK, GAS WORK, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-22 Cont ID  
Sent By jgomez Date 2013-08-22 Time 10:31 Rev Time 0.00
Received By jgomez Date 2013-08-22 Time 10:31 Sent To  
Notes
2013-08-22 10:40:03RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET A0:
 A) REVISE THE BUILDING EXPOSURE SPECIFIED ON THE
 "DEVELOPMENT DATA" SPECIFICATIONS. ACCORDING TO SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT "B".
  
 B) REVISE THE WINDOWS/DOORS DESIGN PRESSURES TO
 CORRESPOND TO EXPOSURE "C". ***NOTE: REVISE PRESSURES
 ON WINDOW/DOOR SCHEDULES ALSO AND INCLUDE GARAGE DOOR.
  
 2- PLANS TO BE SIGNED AND SEALED BY FLORIDA LICENSED
 ARCHITECT OR ENGINEER. SEAL STAMPED ON "BASIL
 IRVING-SSC DESIGN GROUP" IS NOT FROM AN ARCHITECT OR
 ENGINEER. IT'S A CORPORATE SEAL. CORPORATE SEAL DOESN'T
 ENTITLE TO PRACTICE ARCHITECTURE OR ENGINEERING.
 FLORIDA STATUTE 481 AND 471.
 A) NEED ENGINEER OR ARCHITECT SEAL AND SIGNATURE ON ALL
 DRAWINGS. CHAPTER 471 OR 481 FLORIDA STATUTE.
  
 B) NEED FIRM FLORIDA LICENSE NUMBER FOR "SSC DESIGN
 GROUP". CHAPTER 481 FLORIDA STATUTE.
  
 3- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION. PLEASE MAKE SURE IS FILLED
 COMPLETELY AND SIGNED & DATED BY THE OWNER/AGENT ALSO.
  
 4- SHEET A1: REVISE GARAGE SWING DOOR SPECIFICATIONS ON
 THE DOOR SCHEDULE. NEED TO COMPLY WITH FIRE RATING OF
 SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) INSWING WOOD DOOR AS SHOWN ON PLANS FOR NEW CABANA
 BATHROOM.
  
 C) GARAGE DOOR FOR SIZE SHOWN ON PLANS. AND, CLARIFY IF
 REPLACING GARAGE DOORS OR NOT. FLOOR PLAN ON SHEET A2
 SAYS "RETAIN EXT OVERHEAD DOOR" AND, SPECIFY THE DESIGN
 PRESSURES.
  
 D) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 E) FRENCH DOORS AS SHOWN ON PLANS.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS.
  
 G) FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 ***NOTE: ALSO, NEED PRODUCT APRPOVAL FOR ALL WINDOW
 SIZES SHOWN ON PLANS. SEE WINDOW SCHEDULE.
  
 6- PRODUCT APPROVALS TO BE REVIEWED AND APPROVED IN
 WRITING BY THE ENGINEER OF RECORD (NOT SIGNING AND
 SEALING). SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
 ***NOTE: PRODUCT APPROVALS HAVE A CORPORATE SEAL. THIS
 DOESN'T ENTITLE TO PRACTICE ARCHITECTURE OR
 ENGINEERING. FLORIDA STATUTE 471 AND 481.
  
 7- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM AS
 REQUIRED BY SEC. R315.
  
 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 ****NOTE: PROVIDE COMPLETE INFORMATION UNDER SEPARATE
 PERMITS FOR: POOL WORK, NEW GENERATOR, SCREEN ENCLOSURE
 WORK, GAS WORK, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-10-30 Cont ID  
Sent By skennedy Date 2013-10-30 Time 15:08 Rev Time 0.00
Received By skennedy Date 2013-10-30 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2013-10-18 Time   Rev Time 0.00
Received By skennedy Date 2013-10-18 Time 15:49 Sent To  
Notes
2013-10-18 15:55:00REVIEW COMMENTS BY DOUG HARVEY OF 9/4/13 WERE NOT
 ADDRESSED IN THE RESUBMITTAL OF 9/13/13.
  
 FBC 107.3.5.3 ? PROVIDE PANEL SCHEDULES AND SHOW
 CIRCUITS ON FLOOR PLAN.
 FBC 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 NEC 210.12B ? PROVIDE AFCI PROTECTION.
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 15:44 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 15:44 Sent To  
Notes
2013-09-04 15:47:42FIRST REVIEW - 9-4-13
  
 1. PROVIDE PANEL SCHEDULE IN DETAIL PEER NBEC 408.4
 2. SHOW CIRCUITRY ON FLOOR PLAN
 3. NOTE THE FOLLOWING ON DRAWINGS.....
 TAMPER RESISTANT RECEPTS REQUIRED PER NEC 406.11
 AFCI PROTECTION REQUIRED PER NEC 210.12B
 SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE 314/315

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-11-01 Cont ID  
Sent By jgomez Date 2013-11-01 Time 15:53 Rev Time 0.00
Received By jgomez Date 2013-11-01 Time 15:53 Sent To  
Notes
2013-11-01 15:54:30REVISED ENERGY CALCULATIONS SUBMITTED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-31 Cont ID  
Sent By skennedy Date 2013-10-30 Time 15:15 Rev Time 0.00
Received By jgomez Date 2013-10-22 Time 17:10 Sent To  
Notes
2013-10-30 15:13:53INFORMED BASIL IRVIN REVIEW COMPLETE. FILED IN LARGE
 DENIED PLANS "A." SAK
2013-10-22 17:10:46SENT TO R13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-10-18 Time   Rev Time 0.00
Received By rmcdouga Date 2013-09-13 Time 07:21 Sent To  
Notes
2013-10-18 16:00:47ADVISED CHARLES ZATERPALEK BY VOICE MAIL. PLACED
 SUBMITTAL IN DENIED PLANS LARGE, A.
2013-09-16 07:32:12R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 15:48 Rev Time 0.00
Received By dharvey Date 2013-09-04 Time 15:48 Sent To  
Notes
2013-07-31 15:19:58R-10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-10-30 Cont ID  
Sent By jgomez Date 2013-10-30 Time 10:57 Rev Time 0.00
Received By jgomez Date 2013-10-30 Time 10:57 Sent To  
Notes
2013-10-30 10:58:04USING EXISTING A/C UNITS. SEE AIR CONDITIONING
 CALCULATIONS ON SHEET A0. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-09-20 Cont ID  
Sent By jgomez Date 2013-09-20 Time 08:27 Rev Time 0.00
Received By jgomez Date 2013-09-20 Time 08:27 Sent To  
Notes
2013-09-20 08:32:21RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- THERE WAS NO A/C INFORMATION SUBMITTED THE FIRST
 TIME, EXCEPT FOR THE 5" FLEX DUCT SHOWN ON SHEET A-06
 TO FEED THE NEW CABANA. CLARIFY SCOPE OF WORK. NOW,
 THERE ARE EQUIPMENT SIZING CALCULATIONS SUBMITTED. WHY
 SUBMITTING THESE CALCULATIONS. IS THERE GOING TO BE AN
 EXACT CHANGE OUT. IF SO, PROVIDE COMPLETE EQUIPMENT
 SIZING CALCULATIONS, NOT JUST THE SUMMARY AND COMPLETE
 THE REQUIRED CHANGE OUT FORMS. IF DOING ANY OTHER
 DUCTWORK, THEN A/C PLANS ARE REQUIRED. SEC.
 107..5.3(10) OF CITY AMENDMENTS TO FBC.
  
 2- PROVIDE SPECIFICATIONS FOR EXHAUST HOOD TO BE
 INSTALLED ABOVE THE GRILL IN THE SUMMER KITCHEN. AND,
 CLARIFY WHERE I S THE HOOD VENTING TO. ELEVATIONS DON'T
 SHOW HOOD VENTING TO THE ROOF. SEC. M1505 OF 2010
 FBC-RESIDENTIAL (REPEAT COMMENT).
  
 3- SPECIFY THE EXHAUST FAN FOR BATHROOM #1 AS REQUIRED
 BY SEC. M1507. ONLY SHOWING EXHAUST FAN AT THE TOILET
 ROOM (REPEAT COMMENT).
  
  
 ****NOTE; PLEASE PROVIDE RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-26 Cont ID  
Sent By jgomez Date 2013-08-26 Time 18:45 Rev Time 0.00
Received By jgomez Date 2013-08-26 Time 18:45 Sent To  
Notes
2013-08-26 18:48:35RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE SPECIFICATIONS FOR EXHAUST HOOD TO BE
 INSTALLED ABOVE THE GRILL IN THE SUMMER KITCHEN. AND,
 CLARIFY WHERE I S THE HOOD VENTING TO. ELEVATIONS DON'T
 SHOW HOOD VENTING TO THE ROOF. SEC. M1505 OF 2010
 FBC-RESIDENTIAL.
  
 2- SPECIFY THE EXHAUST FAN FOR BATHROOM #1 AS REQUIRED
 BY SEC. M1507. ONLY SHOWING EXHAUST FAN AT THE TOILET
 ROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6712
2013-08-23 12:22:43REVIEW IN PROGRESS...

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-20 Cont ID  
Sent By jgomez Date 2013-09-20 Time 08:33 Rev Time 0.00
Received By jgomez Date 2013-09-20 Time 08:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-23 Cont ID  
Sent By jgomez Date 2013-08-23 Time 09:31 Rev Time 0.00
Received By jgomez Date 2013-08-23 Time 09:31 Sent To  
Notes
2013-08-23 09:32:22RESIDENTIAL (R3) ADDITION/ALTERATION, PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
  
 1- SPECIFY SIZE OF SHOWER IN NEW CABANA BATHROOM. SEC.
 P2708 OF 2010 FBC-RESIDENTIAL.
  
 2- PLUMBING RISER DIAGRAM TO SPECIFY ALL CLEANOUTS
 REQUIRED BY SEC. P3005.2.4 WHEN THERE IS A CHANGE OF
 DIRECTION.
  
 3- PLUMBING RISER DIAGRAM IS MISSING THE NEW BIDET.
 SEC. P2721.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-08-22 Cont ID  
Sent By jgomez Date 2013-08-22 Time 16:43 Rev Time 0.00
Received By jgomez Date 2013-08-22 Time 16:43 Sent To  
Notes
2013-08-22 16:44:09RE-ROOF IS NOT INCLUDED IN THIS REVIEW. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-06 Cont ID  
Sent By llouie Date 2013-08-06 Time 10:33 Rev Time 0.00
Received By llouie Date 2013-08-06 Time 10:33 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-06 Cont ID  
Sent By llouie Date 2013-08-06 Time 10:21 Rev Time 0.00
Received By llouie Date 2013-08-06 Time 10:21 Sent To  
Notes
2013-08-01 16:31:438/1/13