Plan Review Details - Permit 13071115
Plan Review Stops For Permit 13071115
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-01 Cont ID  
Sent By jwitmer Date 2013-10-01 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2013-10-01 Time 16:01 Sent To  
Notes
2013-10-01 16:12:49BUILDING PLAN REVIEW
 REVISION: 13071115
 PERMIT: 13010504
 ADD: 631 EVERNIA ST
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:OCT. 01/ 2013
 ACTION: DENIED
  
 1) SHEET A0450 INDICATES A REVISION FROM THE USE OF
 METAL ROOF TILE TO CONCRETE ROOF TILE. SUPPORTING
 DOCUMENTS FL APPROVAL FL 780487 ENTEGRA ROOF TILE-
 ESTATE "S" , FASTENING TABLE 3B-2 WITH 3M-2 COMPONENT
 FOAM/ ROOF TILE ADHESIVE AH 160.
  
 PROVISO : WILL NEED A PRODUCT APPROVAL FOR THE 3B-2
 WITH 3M-2 COMPONENT FOAM/ ROOF TILE ADHESIVE AH 160.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(D)
 ROOFING PRODUCTS AND ASSEMBLIES/ 1609.6.4.41 COMPONENTS
 & CLADDING
  
 2)DENIED, FIBERTECH FRP MOLDINGS. DENIED TO BE REVIEWED
 UNDER A SEPERATE REVISION. SHEETS A500 SERIES AND A600
 SERIES INDICATE THE USE OF FIBERTECH FRP MOLDINGS,
 FC-2261, PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B
 1406.2.2 TYPE I, II, III AND IV CONSTRUCTION.2.
 COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO 40
 FEET (12 192 MM) IN HEIGHT ABOVE GRADE.
  
 PLEASE PROVIDE PRODUCT TESTING THAT MEETS THE
 DEFINITION OF NONCOMBUSTIBILITY AND TEST 703.4. PLEASE
 REVIEW:
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-19 Cont ID  
Sent By jwitmer Date 2013-08-19 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2013-08-19 Time 12:31 Sent To  
Notes
2013-08-19 14:03:50BUILDING PLAN REVIEW
 REVISION: 13071115
 PERMIT: 13010504
 ADD: 631 EVERNIA ST
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 19/ 2013
 ACTION: DENIED
  
 1) SHEET A0450 INDICATES A REVISION FROM THE USE OF
 METAL ROOF TILE TO CONCRETE ROOF TILE. IN THE
 SUPPORTING DOCUMENTS, THERE IS NO PRODUCT TESTING
 SHOWING COMPLIANCE WITH:
 2010 FBC 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, PLEASE
 IDENTIFY THE TILE TYPE, AND THE ANCHOR METHOD. ALSO IF
 FOAM PRODUCTS ARE BEING USED FOR ANCHORING PLEASE
 REVIEW 2010 FBC-B 603.4, TABLE 1505.1 & 1505.3.
  
 2) SHEETS A500 SERIES AND A600 SERIES INDICATE THE USE
 OF FIBERTECH FRP MOLDINGS, FC-2261, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B
 1406.2.2 TYPE I, II, III AND IV CONSTRUCTION.2.
 COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO 40
 FEET (12 192 MM) IN HEIGHT ABOVE GRADE.
  
 PLEASE PROVIDE PRODUCT TESTING THAT MEETS THE
 DEFINITION OF NONCOMBUSTIBILITY AND TEST 703.4. PLEASE
 REVIEW:
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-08-17 Cont ID  
Sent By wjolin Date 2013-08-17 Time 15:58 Rev Time 0.00
Received By wjolin Date 2013-08-13 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-01 Cont ID  
Sent By jwitmer Date 2013-10-01 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2013-09-12 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-11 Cont ID  
Sent By rregueir Date 2013-08-27 Time 13:52 Rev Time 0.00
Received By rregueir Date 2013-07-31 Time 09:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-10-17 Cont ID  
Sent By rregueir Date 2013-10-15 Time 10:26 Rev Time 0.00
Received By rregueir Date 2013-10-15 Time 10:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-09 Cont ID  
Sent By aaponte Date 2013-08-27 Time 11:16 Rev Time 0.00
Received By aaponte Date 2013-08-27 Time 11:17 Sent To  
Notes
2013-08-27 11:17:09PROVISO NOTES INCLUDED IN MASTER PERMIT 13010504 MUST
 BE ADDRESSED BEFORE ANY ADDITIONAL REVISIONS CAN BE
 APPROVED BY ZONING. SEE BELOW
 PROVISO:
 1. PARKING STRIPING DETAIL SHALL BE CORRECTED TO
 INDICATE THE LINES IN COLOR WHITE ACCORDING TO CITY
 STANDARDS.
 2. PLEASE INCLUDE THE SIEWALK AND THE STREET LEVEL ON
 ALL BUILDING SECTIONS AND FACADES ( TO THE CURB LINE),
 AND SHOW PLANTING AREAS WHERE PROVIDED (A-601,
 602,603,604 AND ELEVATIONS)
 3. DETAILS SHALL BE PROVIDED FOR THE RESOLUTION OF THE
 ENTRANCE STAIRS ENCROACHING INTO THE ROW AND THE
 PROPOSED PLANTING AREA (DETAILS FOR CONCRETE CURB AS
 PLANTER EDGE). PLANTING SPECS HAVE BEEN PROVIDED
 ALREADY.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822 1439