Plan Review Details - Permit 13071112
Plan Review Stops For Permit 13071112
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-15 Cont ID  
Sent By rmcdouga Date 2013-08-15 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2013-08-15 Time 18:38 Sent To  
Notes
2013-08-15 19:15:56APPROVED WITH EXCEPTION
 PRODUCT APPROVALS FOR SIMPSON HANGERS AND CONNECTORS TO
 BE PROVIDED TO FIELD INSPECTOR AT TIME OF INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-01 Cont ID  
Sent By rmcdouga Date 2013-08-01 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2013-08-01 Time 16:20 Sent To  
Notes
2013-08-01 16:57:182010 FBC
  
 DENIED BY BUILDING
  
 1) THE SIZE OF THE HEADER SUPPORTING THE ROOF HAS BEEN
 CHANGED FROM A NO. SYP DOUBLE 2 X 8 TO A DOUBLE 2 X 6.
 THE HEADER SPAN IS OVER 8 FEET. A 2 X 6 HEADER IS TOO
 SMALL TO HANDLE THE LOADS. PLEASE CORRECT. FBC R301.1
  
 2) THE SIMPSON HUS26-2 HANGER REQUIRES (12) 1/4" X
 2-3/4" TITEN MASONRY SCREWS AND (6) 10D NAILS FOR AN
 UPLIFT OF 1085 LBS ACCORDING TO THE SIMPSON CATALOG.
 PLEASE REVISE. FBC R301.1
  
 THE REVISION WILL NEED TO BE CORRECTED AND RESUBMITTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-15 Cont ID  
Sent By rmcdouga Date 2013-08-15 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2013-08-14 Time 17:24 Sent To  
Notes
2013-08-15 09:02:40TO RM DESK
  
2013-08-14 17:24:40TO SEW DESK (NEEDS FEES)
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2013-08-01 Cont ID  
Sent By rmcdouga Date 2013-08-01 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2013-07-30 Time 08:05 Sent To  
Notes
2013-07-31 08:05:35SENT TO MCDOUGAL