Plan Review Details - Permit 13071055
Plan Review Stops For Permit 13071055
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-20 Cont ID  
Sent By GOMEZ Date 2013-09-20 Time 17:29 Rev Time 0.00
Received By jgomez Date 2013-09-20 Time 17:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-16 Time 13:36 Rev Time 0.00
Received By jgomez Date 2013-08-16 Time 13:35 Sent To  
Notes
2013-08-16 14:36:00RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR FLAT ROOF ASSEMBLY. AND,
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION # 7. NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS IS ALLOWED BY GENERAL
 LIMITATION #7 (SEE LAST PAGE OF NOA) TO ACHIEVE THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 2- PROVIDE CURRENT NOA FOR THE ROOF SHINGLES TO BE
 INSTALLED. NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-26 Cont ID  
Sent By MCDOUGAL Date 2013-09-26 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2013-09-26 Time 08:41 Sent To  
Notes
2013-09-26 08:42:54RED-LINED PLANS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By rmcdouga Date 2013-08-28 Time 17:00 Rev Time 0.00
Received By rmcdouga Date 2013-08-28 Time 11:24 Sent To  
Notes
2013-08-28 17:45:372010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) PROVIDE LOAD CALCULATIONS AND PANEL SCHEDULE FOR THE
 NEW 100 AMP SUB PANEL.NEC 220.40
  
 2) SHOW THE 100 AMP SUB-PANEL ON THE RISER DIAGRAM (NEC
 215.5). SPECIFY THE WIRING METHOD AND SIZES OF THE
 GROUNDED AND UNGROUNDED CONDUCTORS FEEDING THE 100 AMP
 PANEL (NEC TABLE 310.16) AND THE GROUNDING CONDUCTOR
 SIZE (NEC 250.122).
  
 3) SPECIFY THE RATING OF THE BUS STABS IN THE 150 AMP
 MAIN PANEL NEC 110.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-26 Cont ID  
Sent By rmcdouga Date 2013-09-26 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 07:19 Sent To  
Notes
2013-09-20 07:20:41R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-28 Cont ID  
Sent By rmcdouga Date 2013-08-28 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2013-07-29 Time 08:24 Sent To  
Notes
2013-07-31 08:34:08R19
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-20 Cont ID  
Sent By jgomez Date 2013-09-20 Time 18:25 Rev Time 0.00
Received By jgomez Date 2013-09-20 Time 18:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-16 Time 14:36 Rev Time 0.00
Received By jgomez Date 2013-08-16 Time 14:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-09-20 Cont ID  
Sent By dkittred Date 2013-09-20 Time 11:41 Rev Time 0.00
Received By dkittred Date 2013-09-20 Time 11:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-06 Cont ID  
Sent By dkittrid Date 2013-08-06 Time 13:41 Rev Time 0.00
Received By dkittred Date 2013-08-06 Time 13:28 Sent To  
Notes
2013-08-06 13:50:08PLANNING & ZONING COMMENTS: ****FAILED****
  
 8/6/2013
  
 THE TOTAL VALUE OF THE CONSTRUCTION ($85,000+) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($49,324) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV. IF THE SITE CONFORMS
 TO ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 NOTE - ZLDR SEC. 94-442(2)A. - REQUIRES ONE SHADE OR
 FLOWERING TREE BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF AND ONE SHRUB BE PLANTED
 FOR EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION
 THEREOF.
  
 IF YOU HAVE QUESTIONS PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE
 SENIOR PLANNER
 (561) 822-1443
 [email protected]
2013-08-01 16:26:408/1/13