Plan Review Details - Permit 13070994
Plan Review Stops For Permit 13070994
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-02-04 Cont ID  
Sent By jwitmer Date 2014-02-04 Time 18:57 Rev Time 0.00
Received By jwitmer Date 2014-02-04 Time 18:40 Sent To  
Notes
2014-02-04 18:54:08RESHORE SHOP DRAWINGS & CALCULATIONS FOR LEVLES 3 THRU
 9.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-01-27 Cont ID  
Sent By jwitmer Date 2014-01-27 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2014-01-27 Time 07:45 Sent To  
Notes
2014-01-27 08:13:44BUILDING PLAN REVIEW
 PERMIT: 13070994
 ADD: 455 HIBISCUS ST HI-RISE R1-R2
 CONT: MOSS & ASSOCIATES
 TEL: (954)524-5678
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: MONDAY JAN. 27/ 2014
 ACTION:APPROVED
  
 1) SUBMITTAL: 2ND LEVEL DECK SHORING SHOP DRAWINGS &
 CALCULATIONS.
 ENGINEERED SHOP DRAWINGS SIGNED & SEALED BY P. E.
 EDUARDO ROMAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 06:19 Rev Time 0.00
Received By jwitmer Date 2014-01-23 Time 06:00 Sent To  
Notes
2014-01-23 06:15:25BUILDING PLAN REVIEW
 PERMIT: 13070994
 ADD: 455 HIBISCUS ST HI-RISE R1-R2
 CONT: MOSS & ASSOCIATES
 TEL: (954)524-5678
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURSDAY JAN. 23/ 2014
 ACTION: DENIED
  
 1) SUBMITTAL: 2ND LEVEL DECK SHORING SHOP DRAWINGS &
 CALCULATIONS.
 ENGINEERED SHOP DRAWINGS SIGNED & SEALED BY P. E.
 EDUARDO ROMAN ARE COPIED SIGNATURES NOT ORIGINALS AS
 REQUIRED BY:
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009
 (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-20 Cont ID  
Sent By jwitmer Date 2013-11-20 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2013-11-16 Time 13:02 Sent To  
Notes
2013-11-16 15:19:36BUILDING PLAN REVIEW
 PERMIT: 13070994
 ADD: 455 HIBISCUS ST HI-RISE R1-R2
 CONT: MOSS & ASSOCIATES
 TEL: (954)524-5678
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: NOV. 16/ 2013
 ACTION:PROVISO
  
 1) SHEET (003) LS1.02 2ND FLOOR:
 1A-D) COMPLIED
  
 1E) COMPLIED: R-1 DWELLING UNITS, THE CODE COMMENTARY
 ALLOWS FOR COOKING UNITS "EXTENDED STAY" FOR NOT MORE
 THAN 30 DAYS.
  
 1F-J) COMPLIED.
  
 2A-G) COMPLIED.
  
 2H) PROVISO: FIRE COMMAND ROOM AND REQUIRED SYSTEMS.
 FBC-B 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 2I-J) COMPLIED. PLEASE ALSO INDICATE WHERE COMPLIANCE
 WITH 403.3.2 WATER SUPPLY TO THE REQUIRED FIRE PUMPS
 SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO
 WATER MAINS LOCATED IN DIFFERENT STREETS.
  
 3A) COMPLIED.
  
 3B) PROVISO: PROVIDE MANUFACURERS CUT SHEETS. PLEASE
 ALSO PROVIDE CODE COMPLIANCE FOR THE DWELLING UNIT
 FLOORS FBC-B STRUCTURE BORNE SOUND, TILE FLOORS ETC?
 3B)(1) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492
 .
 3B)(2)FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING.
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 4-7) COMPLIED.
  
 8) PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 MISSING PRODUCT APPROVALS, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. OVERHEAD, SWING, AUTO BYPASS,
 LOUVERED & ROOF HATCHES
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOF TOP
 CURBS & FANS
 (E) PRE-ENGINEERED A/C STANDS
  
 10) PRODUCE AN IMPACT FEE RECEIPT THAT IMPACT FEES WERE
 PAID UNDER THE FOUNDATION PERMIT OR BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By jwitmer Date 2013-08-29 Time 06:39 Rev Time 0.00
Received By jwitmer Date 2013-08-25 Time 12:58 Sent To  
Notes
2013-08-29 06:40:45BUILDING PLAN REVIEW
 PERMIT: 13070994
 ADD: 455 HIBISCUS ST HI-RISE R1-R2
 CONT: MOSS & ASSOCIATES
 TEL: (954)524-5678
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: AUGUST 26/ 2013
 ACTION: DENIED
  
 1) SHEET (003) LS1.02 2ND FLOOR:
 1A) HEADING, CODE SUMMARY LIST THE 2009 IBC AS THE BASE
 CODE, WE ARE REVIEWING TO THE 2010 FBC-B, FLORIDA HAS
 MADE AMENDMENTS TO THE 2009 IBC CODE.
  
 1B) PLEASE NOTE THE 2010 FLORIDA ACCESSIBILITY CODE IS
 APPROVED BY THE DEPARTMENT OF JUSTICE AND A STRICTER
 VERSION FOR THE FEDERAL ADA. GREY BOXES OF TEXT ARE
 FLORIDA SPECIFIC AMENDMENTS.
  
 1C) HEADING, NEW BUILDING DESCRIPTION, INDICATES THIS
 TO BE TYPE I-B CONSTRUCTION, WHERE AS UNDER THE HEADING
 TABLE 601 FIRE RESISTANCE RATING DECLARE THE BUILDING
 AS A TYPE II-A, PLEASE UPDATE THIS DISCREPANCY, IF TYPE
 IA PLEASE UPDATE TABLE 601 HOUR RATINGS.
  
 1D) PLEASE PROVIDE CODE COMPLIANCE WITH 2010 FBC-B
 TABLE 602 DISTANCE FROM PROPERTY LINE WALLS, LS-1 DOES
 NOT PROVIDE A MEASUREMENT, IT APPEARS THE FIRE
 SEPARATION WILL EFFECT THE WALL RATINGS TO BE EITHER 2
 OR 3 HR.
  
 1E) HEADING; BUILDING CRITERIA LIST A MIXED USE
 BUILDING WITH ONE OF THE OCCUPANCIES AN R-1 BUT THE
 OCCUPANCY TYPES DO NOT INDICATE ANY R-2 OCCUPANCIES.
 LS-02, & LS-03 INDICATE UNITS S209, S220, SX09 & SX20 A
 TOTAL OF 16 UNITS ARE AN R2 OCCUPANCY. SEE DEFINITIONS,
 SLEEPING UNIT, DWELLING UNIT AND SECTION 2010 FBC-B
 310.1.
  
 1F) CODE REFERENCES UPPER RIGHT SIDE OF PAGE, LIST AREA
 OF REFUGE NOT REQUIRED AT ELEVATOR LOBBIES, PLAN ROOM
 #200 ELEVATOR LOBBY ALSO LIST ENCLOSURES NOT REQUIRED.
 IN BOTH THE IBC AND 2010 FBC-B 708.14.1 UNDER EXCEPTION
 # 4, (4.3) HIGH-RISES THEY ARE REQUIRED. THIS COMMENT
 WILL STAND FOR ALL FLOORS.
  
 1G) PLEASE PROVIDE A SEPARATE HEADING INDICATING THE
 ISSUED FOUNDATION PERMIT # 09020476, THE FOLLOWING
 DOCUMENTS WERE FILED UNDER THIS PERMIT, UNITY OF TITLE,
 SOILS REPORT, AND THRESHOLD INSPECTORS AGREEMENT.
  
 1H) MISSING REQUIRED STATEMENT FOR THRESHOLD BUILDINGS:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 1I) PLEASE UPDATE THE THRESHOLD AGREEMENT TO VERIFY WE
 WILL HAVE THE SAME THRESHOLD INSPECTOR ON THE JOBSITE.
 CONTACT THE MANAGER OF THE THRESHOLD INSPECTOR PROGRAM,
 KEN CONRAD AT:
 TEL: 561-805-6666
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1J) PLEASE REVIEW THE TENANT WALL BETWEEN SUITE S209 &
 GUEST LAUNDRY 205, THE WALL DOES NOT INDICATE IT TO BE
 FIRE RATED. TWO ISSUES, SEE FIRE RATING FBC-B 709.1.1,
 & 1207.2 AIR BORNE SOUND.
  
 2) SHEET (002) LS1.01, 1ST FLOOR:
 2A) THE ENTRY LOBBY, BREAKFAST AREA & STUDY NOOK AREA
 REQUIRE TWO MEANS OF EGRESS, SHEET E2.8 INDICATES 3
 DOORS AS EGRESS DOORS, 100B, 103 & 126. SHEET A1.01
 DOES NOT SHOW ANYONE EGRESSING THROUGH DOOR 103, THIS
 DOOR LEADS OUT ONTO THE EAST PATIO AREA, OR EGRESS
 COURT, TO GET A EGRESS PATH TO THE PUBLIC WAY THE
 OCCUPANTS PASS A POINT WHERE THE WIDTH IS AS NARROW AS
 5?-0? WIDE AND LOCATED AT THE PROPERTY LINE. PLEASE
 SHOW COMPLIANCE WITH 1027.5.2.
  
 2B) EAST WALL LINE AT STAIR TOWER AND THE TRANSFORMER
 ROOM, WOMEN?S RESTROOM AND EMPLOYEES LOUNGE AS A
 BUILDING TYPE IB SEE FIRE RATING REQUIRED TABLE 602
 0-5? REQUIRES 3 HOUR RATING AND WALLS 5?-10? WILL
 REQUIRE 2 HOUR FIRE RATING.
  
 2C) THE GENERATOR ROOM # 145 DOES NOT INDICATE THE
 WALLS AS RATED PER 2010 FBC-B 403.4.7.1, WHICH REQUIRES
 2 HR WALLS, 1 ? HR OPENING PROTECTIVE?S. UPDATE DOOR
 SCHEDULE OPENING PROTECTIVE?S FBC-B 715.4.
  
 2D) THE TRANSFORMER ROOM # 128 DOES NOT INDICATE FIRE
 RATING AS REQUIRED BY NEC 110.31A SEE ELECTRICAL
 COMMENTS. . UPDATE DOOR SCHEDULE OPENING PROTECTIVE?S
 FBC-B 715.4.
  
 2E) MAIN ELECTRICAL ROOM NEC OVER 600 VOLTS NFPA
 13.8.14.10 1 HOUR FIRE RATING,
 . UPDATE DOOR SCHEDULE OPENING PROTECTIVE?S FBC-B
 715.4.
  
 2F) TRANSFORMER ROOM PLEASE SEE ELECTRICAL REVIEW ALSO
 3 HR WALLS PER NEC 110.31A / 2 HR OPENING PROTECTIVE?S
 FBC-B TABLE 715.4.
  
 2G) THE EAST POOL GATE INDICATES 175 OCCUPANTS GO
 THROUGH THIS GATE IF THIS IS A 36 ? GATE IT IS ONLY
 GOOD FOR 170. PLEASE PROVIDE THE WIDTH OF THE GATE, IT
 IS NOT FOUND ON THE DOOR SCHEDULE. 2010 FBC-B 1005.1.
  
 2H) FIRE COMMAND ROOM AND REQUIRED SYSTEMS. FBC-B
 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE. EMERGENCY
 RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 2I) PLEASE ALSO INDICATE WHERE COMPLIANCE WITH 403.3.2
 WATER SUPPLY TO THE REQUIRED FIRE PUMPS SHALL BE
 SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS
 LOCATED IN DIFFERENT STREETS.
  
 2J) THE PLANS INDICATE THE LOCATION OF THE GENERATOR
 BUT DO NOT PROVIDE WHERE THE FUEL TANK IS LOCATED? WHAT
 TYPE OF FUEL, AND HOW MANY GALLONS?
  
 3A) SHEETS A1.02-A1.05 INDICATE DWELLING UNITS, S209,
 S220, SX09 & SX20, A TOTAL OF (16) DWELLING UNITS, THE
 WALL TYPES ARE NOT TAGGED TO IDENTIFY WHICH WALL TYPE
 OF CONSTRUCTION THEY CONSTRUCTED. A1.13 DOES NOT
 PROVIDE SOUND RATING REQUIREMENTS FOR THESE UNITS AS
 REQUIRED BY THE 2010 FBC-B 1207.2.
  
 3B) PLEASE ALSO PROVIDE CODE COMPLIANCE FOR THE
 DWELLING UNIT FLOORS FBC-B STRUCTURE BORNE SOUND, TILE
 FLOORS ETC?
 3B)(1) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492
 .
 3B)(2)FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING.
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 3B)(3) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 4) THE SAME SHEETS A1.02- A1.05 ALSO ARE MISSING WALL
 IDENTIFICATION TAGS FOR OTHER RATED WALLS 438.2, 708.2
 SHAFT WALLS & 708.13.3. LAUNDRY CHUTE ACCESS ROOMS.
  
 5) SHEET A4.04 THE LINEN CHUTE SECTION DOES NOT COMPLY
 WITH SECTION FBC-B 903.2.11.2 AUTOMATIC FIRE SPRINKLER
 SYSTEM SHALL BE INSTALLED AT THE TOP OF THE LINEN CHUTE
 AND IN THEIR TERMINATION ROOM AND HAVE ADDITIONAL HEADS
 AT ALTERNATE FLOORS.
  
  
 6) SHEET A5.04;
 6A) MEN?S ACCESSIBLE STALL THE MINIMUM DIMENSION IS TO
 SMALL, SEE FBC-ACCESSIBILITY 604.3.2. THE MINIMUM
 DIMENSION FOR THIS TYPE OF LAYOUT IS 7?-1?.
  
 6B) MEN?S ACCESSIBLE RESTROOM IS NOT PROVIDED WITH A
 OVERALL DIMENSION? 2010 FL ACC CODE 604.3.2.
  
 6C) WOMEN?S ACCESSIBLE RESTROOM # 122 IS NOT PROVIDED
 WITH AN OVER ALL DIMENSION. FL ACC CODE 604.3.2.
  
 6D) ) WOMEN?S ACCESSIBLE RESTROOM # 147 IS NOT PROVIDED
 WITH AN OVER ALL DIMENSION. FL ACC CODE 604.3.2.
  
 7) A5.05 HIGH SIDE OF DRINKING FOUNTAIN WILL NEED TO
 COMPLY WITH FL ACC CODE 307.2 PROTRUDING OBJECTS, 27?
 MAX. SOME MANUFACTURERS MAKE A SKIRTING THAT CAN BE
 ATTACHED TO THE DRINKING FOUNTAIN TO MAINTAIN THE
 MAXIMUM 27 INCHES.
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) MISSING PRODUCT APPROVALS, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. OVERHEAD, SWING, AUTO BYPASS,
 LOUVERED & ROOF HATCHES
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOF TOP
 CURBS & FANS
 (E) PRE-ENGINEERED A/C STANDS
  
 10) PRODUCE AN IMPACT FEE RECEIPT THAT IMPACT FEES WERE
 PAID UNDER THE FOUNDATION PERMIT OR BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-03 Cont ID  
Sent By albarran Date 2013-12-03 Time 21:06 Rev Time 5.00
Received By albarran Date 2013-12-03 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-30 Cont ID  
Sent By dharvey Date 2013-09-30 Time 13:55 Rev Time 0.00
Received By dharvey Date 2013-09-27 Time 14:38 Sent To  
Notes
2013-09-19 14:02:18#13070994
 455 HIBISCUS
 MARRIOTT RESIDENCE INN
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 E1.1
 PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE
 ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC
 215.5, 110.26
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 VERIFY THE FIRE PUMP CIRCUIT CONDUCTORS ARE PROPERLY
 PROTECTED. NEC 695.6
  
 VERIFY THE FIRE PUMP OVER CURRENT PROTECTIVE DEVICES
 HAVE BEEN SELECTED TO CARRY INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR CURRENT OF THE FIRE PUMP EQUIPMENT. NEC
 694.4
  
 PROVIDE A SIGN AT THE SERVICE-ENTRANCE EQUIPMENT
 INDICATING TYPE AND LOCATION OF THE ON-SITE EMERGENCY
 POWER SOURCES. NEC 700.8
  
 PROVIDE SIGNAGE DETAIL FOR ALL FIRE PUMP DISCONNECTS
 AND CONTROLLERS. NEC 695.4
  
 VERIFY THE POWER SOURCE SUPPLIED BY THE ON-SITE
 GENERATOR TO THE FIRE PUMP CONNECTS TO A DEDICATED
 DISCONNECTING MEANS SEPARATE FORM THE OTHER GENERATOR
 DISCONNECTING MEANS. NEC 695.4
  
 VERIFY THE EMERGENCY CIRCUIT WIRING IS FULLY PROTECTED.
 NEC 695.14, 700.9
  
 VERIFY THAT ALL WIRING FROM THE EMERGENCY SOURCE HAS
 BEEN KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND
 EQUIPMENT INCLUDING CONTROL CONDUCTORS TO THE
 GENERATOR. NEC 695.14 700.9(B)
  
 PROVIDE LISTING AND SPECIFICATIONS ON THE EMERGENCY
 ELEVATOR RECALL TRANSFER SWITCH. NEC 110.3
  
 PROVIDE A LOAD SUMMARY FOR THE GENERATOR BRANCH WHICH
 SUPPORTS ITS SELECTION TO PROVIDE EMERGENCY POWER TO
 'EDP', 'E1' AND THE FIRE PUMP. NEC 215.2, 220.40
  
 VERIFY THE GENERATOR HAS DUAL FUEL SUPPLIES. NEC
 700.12(B)
  
 VERIFY THE EMERGENCY SYSTEM HAS THE CAPACITY TO CONNECT
 TO A PORTABLE OR TEMPORARY ALTERNATE SOURCE OF POWER
 WHEN THE GENERATOR IS OUT OF SERVICE FOR MAJOR REPAIR.
 NEC 700.5 B
  
  
 E1.2
  
 FIRE PUMP FEEDER APPEARS TO BE UNDERSIZED BASED ON THE
 SELECTED 100 HP FIRE PUMP WITH PRESSURE MAINTENANCE
 PUMPS. NEC 695.6
  
 VERIFY EQUIPMENT GROUND SELECTION FOR PANEL 'DBP'. NEC
 T250.122
  
 E1.3
 PROVIDE DETAIL FOR FIRE STOPPING OF ALL FLOOR AND WALL
 PENETRATIONS. NEC 300.21
  
 E1.4
 CLARIFY PANEL S2 FED FROM DPX ? WHAT IS DPX?
  
 CLARIFY LOCATION OF PANEL C (100 AMP) NOT SHOWN ON
 MSB-B
  
 VERIFY ELEVATOR PIT AND LIGHT FED FROM PANEL 'L' IS NOT
 CONSIDERED AN EMERGENCY LOAD.
  
 VERIFY THE SUMP PUMP FED FROM PANEL 'L' IS NOT
 CONSIDERED AN EMERGENCY LOAD.
  
 E 2.2
 VERIFY THE FIRE PUMP HAS BEEN LOCATED WITHIN A ROOM
 THAT HAS A 2 HOUR RATED FIRE RESISTIVE SEPARATION. FBC
 913.2.1
  
 INDICATE THE PROPOSED WIRING METHOD AND CLASSIFICATION
 FOR THE POOL EQUIPMENT AREA. NEC 505.5
  
 E2.3
 VERIFY THE TRANSFORMER VAULT HAS A 3 HOUR FIRE
 RESISTIVE CONSTRUCTION . NEC 450.42
 VERIFY THE ELECTRIC DRINKING FOUNTAIN HAS GFCI
 PROTECTION. NEC 422.52
  
 E2.5, E2.8, E2.9
  
 LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC
 505.2.4
  
 VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS
 MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2
  
 PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION
 ON ELECTRICAL PLANS. FBC-EC 505.503
  
 SEPARATE PERMIT WITH PLANS AND WIND LOAD ENGINEERING
 FOR POLES WITH LIGHT ASSEMBLY REQUIRED FOR
 CONSTRUCTION. FBC 1604.1, ASCE 7/10
  
 E3.1
 PROVIDE SAFE WORKING CLEARANCE DETAIL/DIMENSIONS ON
 PLANS FOR ALL GUEST ROOM PANEL BOARDS. NEC 110.26
  
 E5.1
 PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INCLUDING DISTRIBUTION AND GUEST ROOMS. NEC
 230.31
  
  
 NOTE: SEPARATE PERMITS AND PLANS REQUIRED FOR SWIMMING
 POOL, FIRE ALARM SYSTEM, SITE LIGHTING, LOW VOLTAGE
 SYSTEMS, ETC.
  
 DOUG HARVEY
 [email protected]
 561-805-6740
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2013-09-18 Cont ID  
Sent By shill Date 2013-09-18 Time 13:00 Rev Time 0.00
Received By shill Date 2013-09-18 Time 13:00 Sent To  
Notes
2013-09-18 13:01:33ENGINEERING PERMIT ISSUED
 PER EMAIL FROM MANNY GONZALEZ 9/18/13, OK TO REMOVE
 REVIEW
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-11-26 Cont ID  
Sent By wjolin Date 2013-11-26 Time 10:27 Rev Time 0.00
Received By wjolin Date 2013-11-22 Time 14:00 Sent To  
Notes
2013-11-22 16:07:47455 HIBISCUS STREET
 PERMIT #13070994
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: STILL COULD NOT LOCATE A FLOOR DRAIN
 IN THE PUMP ROOM.
 SHEET P2.1: NO FLOOR DRAIN PROVIDED IN FIRE PUMP ROOM.
  
 RESPONSE COMMENT: THIS REQUIREMENT IS TO BE COORDINATED
 BETWEEN THE ELECTRICAL ENGINEER AND THE FIRE PROTECTION
 ENGINEER, NOT THE ELEVATOR VENDOR.
 SHEET E2_15: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
  
 NEW COMMENTS:
  
 SHEET FP-1: HIGH-RISE BUILDINGS WITH REQUIRED FIRE
 PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF
 TWO WATER MAINS LOCATED IN DIFFERENT STREETS. SEPARATE
 SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH CONNECTION
 TO THE WATER MAIN AND THE PUMPS. EACH CONNECTION AND
 THE SUPPLY PIPING BETWEEN THE CONNECTION AND THE PUMPS
 SHALL BE SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED
 FOR THE PUMPS TO OPERATE. THE EXCEPTION INDICATES TWO
 CONNECTIONS TO THE SAME MAIN SHALL BE PERMITTED
 PROVIDED THE MAIN IS VALVED SUCH THAT AN INTERRUPTION
 CAN BE ISOLATED SO THAT THE WATER SUPPLY WILL CONTINUE
 WITHOUT INTERRUPTION THROUGH AT LEAST ONE OF THE
 CONNECTIONS.
  
 SHEET FP-1: HIGH-RISE BUILDINGS SHALL BE PROVIDED WITH
 TWO FIRE DEPARTMENT CONNECTIONS (FDC) REMOTELY LOCATED
 FROM EACHOTHER PER NFPA 14. FDCS SHALL BE LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT.
  
 SHEET FP-1: FOR COMBINATION FIRE LINE/DOMESTIC WATER
 LINE, INDICATE THE EXPECTED MAXIMUM DOMESTIC WATER
 DEMAND (PLUMBING & IRRIGATION) THAT MAY AFFECT THE FLOW
 AVAILABLE FOR THE FIRE PROTECTION SYSTEMS. ADJUST
 HYDRAULIC CALCULATIONS TO ACCOUNT FOR THIS REDUCTION IN
 FLOW.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-08 Cont ID  
Sent By wjolin Date 2013-08-08 Time 11:40 Rev Time 0.00
Received By wjolin Date 2013-08-03 Time 18:14 Sent To  
Notes
2013-08-03 19:41:25455 HIBISCUS STREET
 PERMIT #13070994
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS1_01: THE 90 SQ.FT. FIRE COMMAND ROOM #107 WILL
 NEED TO BE APPROXIMATELY 120 SQ.FT. OR LARGER TO
 ACCOMMODATE THE INCIDENT COMMAND STAFF, A WORK TABLE
 AND ALL THE STATUS INDICATORS. PER NFPA 1 SECTION
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER:
 (1) THE FIRE DEPARTMENT COMMUNICATION UNIT
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT, AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE
 (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS
 FOR THE BUILDING
 (6) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT
 (7) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT
 (8) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE
 ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (9) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS
 (10) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (11) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 (12) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (13) FIRE PUMP STATUS INDICATORS
 (14) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES
 (15) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (16) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 SHEET LS1_01: WE ADVISE FOR THE FIRE PUMP ROOM TO BE
 LOCATED ADJACENT TO FIRE COMMAND ROOM #107 AND
 ACCESSIBLE FROM HIBISCUS STREET.
  
 SHEET LS1_01: THE MEETING ROOMS (#135, #136 & #137)
 INDICATE AN OCCUPANT LOAD FACTOR OF 7 SQ.FT. PER
 PERSON; HOWEVER, THE ACTUAL NUMBER OF OCCUPANTS
 INDICATED AS EXITING THROUGH THE DOORS IS FIGURED USING
 AN OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON.
 SEVERAL OF THE ASSEMBLY ROOMS DISCHARGE TO THE FENCED
 POOL AREA. WHEN USING THE OCCUPANT LOAD FACTOR OF 7
 SQ.FT. PERSON THERE ARE APPROXIMATELY 227 PERSONS (17,
 15, 87, 60 AND 48 ) BEING ROUTED TO THE SWINGING GATE
 THAT HAS A CAPACITY OF 194 PERSONS. THIS DOES NOT
 INCLUDE ANY OF THE OCCUPANTS FROM THE POOL AREA EXITING
 THIS ROUTE. EGRESS DOES NOT APPEAR TO BE WIDE ENOUGH TO
 ACCOMODATE THE WORST CASE CAPACITY.
  
 SHEET LS01_02: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS. MIXED USED DESIGN SHALL
 CONFORM TO CHAPTER 28 (HOTELS) AND CHAPTER 30
 (APARTMENTS).
  
 SHEET LS01_02: PER THE LIFE SAFETY CODE, WHERE GUEST
 ROOMS OR GUEST SUITES HAVE INDIVIDUAL COOKING
 FACILITIES, THE APPROPRIATE OCCUPANCY CLASSIFICATION IS
 AS AN APARTMENT BUILDING.
  
 SHEET LS01_02: GUEST LAUNDRY #205 - PER NFPA 101 TABLE
 28.3.2.2.2, LAUNDRY ROOMS LARGER THAN 100 SQ.FT. SHALL
 BE SEPARATED FROM ADJACENT AREAS WITH A 1-HOUR FIRE
 RATING AND AUTOMATIC SPRINKLERS.
  
 SHEET C-9: HIGH-RISE BUILDINGS WITH REQUIRED FIRE PUMPS
 SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO
 WATER MAINS LOCATED IN DIFFERENT STREETS. SEPARATE
 SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH CONNECTION
 TO THE WATER MAIN AND THE PUMPS. EACH CONNECTION AND
 THE SUPPLY PIPING BETWEEN THE CONNECTION AND THE PUMPS
 SHALL BE SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED
 FOR THE PUMPS TO OPERATE. THE EXCEPTION INDICATES TWO
 CONNECTIONS TO THE SAME MAIN SHALL BE PERMITTED
 PROVIDED THE MAIN IS VALVED SUCH THAT AN INTERRUPTION
 CAN BE ISOLATED SO THAT THE WATER SUPPLY WILL CONTINUE
 WITHOUT INTERRUPTION THROUGH AT LEAST ONE OF THE
 CONNECTIONS.
  
 SHEET C-11: HIGH-RISE BUILDINGS SHALL BE PROVIDED WITH
 TWO FIRE DEPARTMENT CONNECTIONS (FDC) REMOTELY LOCATED
 FROM EACHOTHER PER NFPA 14. FDCS SHALL BE LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT.
  
 GENERAL: PER SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET A1_12: DOOR SCHEDULE INDICATES UNSPECIFIED
 HARDWARE GROUP 24 AND GROUP 27 FOR ENTRY LOBBY DOORS
 #100A AND #100B. IS PANIC HARDWARE INTENDED FOR THESE
 DOORS?
  
 RESIDENTIAL UNIT DOORS: DOORS THAT OPEN ONTO EXIT
 ACCESS CORRIDORS SHALL HAVE NOT LESS THAN A 20-MINUTE
 FIRE PROTECTION RATING AND SHALL BE SELF-CLOSING AND
 SELF-LATCHING PER NFPA 101 SECTION 30.3.6.2.3.
  
 SHEET P2.1: NO FLOOR DRAIN PROVIDED IN FIRE PUMP ROOM.
  
 SHEET E2_15: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 SHEET E4_1: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE
 ELEVATOR.
  
 SHEET E4_2: NO FIRE ALARM NOTIFICATION APPLIANCES
 LOCATED IN GUEST LAUNDRY #205.
  
 ELEVATOR: CONFIRM ONE ELEVATOR WILL BE PROVIDED WITH A
 PROTECTED POWER SUPPLY AND SHALL BE AVAILABLE FOR USE
 BY THE FIRE DEPARTMENT IN CASE OF EMERGENCY PER NFPA
 101 SECTION 28.5.3.2. "PROTECTED POWER SUPPLY MEANS A
 SOURCE OF ELECTRICAL ENERGY OF SUFFICIENT CAPACITY TO
 ALLOW PROPER OPERATION OF THEELEVATOR AND ITS
 ASSOCIATED CONTROL AND COMMUNICATIONS SYSTEMS. THE
 POWER SUPPLY?S POINT OF ORIGIN, SYSTEM OF DISTRIBUTION,
 TYPE AND SIZE OF OVERCURRENT PROTECTION, DEGREE OF
 ISOLATION FROM OTHER PORTIONS OF THE BUILDING
 ELECTRICAL SYSTEM, AND DEGREE OF MECHANICAL PROTECTION
 SHOULD BE SUCH THAT IT IS UNLIKELY THAT THE SUPPLY
 WOULD BE DISRUPTED AT ANY BUT THE ADVANCED STAGES OF
 BUILDING FIRE INVOLVEMENT OR BY STRUCTURAL COLLAPSE.
 APROTECTED POWER SUPPLY MIGHT CONSIST OF, AND SHOULD
 PROVIDE, NOT LESS THAN THE LEVEL OF RELIABILITY
 ASSOCIATED WITH AN ELECTRICAL DISTRIBUTION SYSTEM WITH
 SERVICE EQUIPMENT LOCATED AND INSTALLED IN ACCORDANCE
 WITH 230.72(B) AND 230.82(5) OF NFPA 70, NATIONAL
 ELECTRICAL CODE. THE DISTRIBUTION SYSTEM IS NOT TO HAVE
 ANY OTHER CONNECTION TO THE BUILDING ELECTRICAL
 DISTRIBUTION SYSTEM. A PROTECTED POWER SUPPLY IS NOT
 REQUIRED TO INCORPORATE TWO SOURCES OF ENERGY OR
 AUTOMATIC TRANSFER CAPABILITY FROM A NORMAL TO AN
 EMERGENCY SOURCE; FOR EXAMPLE, AN ALTERNATE SET OF
 SERVICE CONDUCTORS."
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. SMOKING SHALL BE PROHIBITED
 EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL OTHER
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS (AND AUTOMATIC STANDPIPE
 SYSTEM). PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, STANDPIPE
 SYSTEMS, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 PLEASE PROVIDE THE FOLLOWING OPERATING FEATURES (NFPA
 101 SECTION 28.7) ON A DRAWING:
  
 (1) HOTEL EMERGENCY ORGANIZATION.
 (A) EMPLOYEES OF HOTELS SHALL BE INSTRUCTED AND DRILLED
 IN THE DUTIES THEY ARE TO PERFORM IN THE EVENT OF FIRE,
 PANIC, OR OTHER EMERGENCY.
 (B) DRILLS OF THE EMERGENCY ORGANIZATION SHALL BE HELD
 AT QUARTERLY INTERVALS AND SHALL COVER SUCH POINTS AS
 THE OPERATION AND MAINTENANCE OF THE AVAILABLE FIRST
 AID FIRE APPLIANCES, THE TESTING OF DEVICES TO ALERT
 GUESTS, AND A STUDY OF INSTRUCTIONS FOR EMERGENCY
 DUTIES.
 (C) EMERGENCY DUTIES. UPON DISCOVERY OF A FIRE,
 EMPLOYEES SHALL CARRY OUT THE FOLLOWING DUTIES:
 -ACTIVATION OF THE FACILITY FIRE PROTECTION SIGNALING
 SYSTEM
 - NOTIFICATION OF THE PUBLIC FIRE DEPARTMENT
 - OTHER ACTION AS PREVIOUSLY INSTRUCTED
  
 (2) EMERGENCY INSTRUCTIONS FOR RESIDENTS OR GUESTS.
 (A) A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS, AND ROOM IDENTIFICATION
 SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO
 THE AUTHORITY HAVING JURISDICTION ON, OR IMMEDIATELY
 ADJACENT TO, EVERY GUEST ROOM DOOR IN HOTELS AND IN
 EVERY RESIDENT ROOM IN DORMITORIES.
 (B) FIRE SAFETY INFORMATION SHALL BE PROVIDED TO ALLOW
 GUESTS TO MAKE THE DECISION TO EVACUATE TO THE OUTSIDE,
 TO EVACUATE TO AN AREA OF REFUGE, TO REMAIN IN PLACE,
 OR TO EMPLOY ANY COMBINATION OF THE THREE OPTIONS.
  
 (3) EMERGENCY PLANS SHALL BE PROVIDED. EMERGENCY PLANS
 SHALL INCLUDE THE FOLLOWING:
 (A) PROCEDURES FOR REPORTING OF EMERGENCIES
 (B) OCCUPANT AND STAFF RESPONSE TO EMERGENCIES
 (C) EVACUATION PROCEDURES APPROPRIATE TO THE BUILDING,
 ITS OCCUPANCY, AND EMERGENCIES (SEE SECTION 4.3)
 (D) APPROPRIATENESS OF THE USE OF ELEVATORS
 (E) DESIGN AND CONDUCT OF FIRE DRILLS
 (F) TYPE AND COVERAGE OF BUILDING FIRE PROTECTION
 SYSTEMS
 (G) REQUIRED EMERGENCY PLANS SHALL BE SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION FOR REVIEW.
 (H) EMERGENCY PLANS SHALL BE REVIEWED AND UPDATED AS
 REQUIRED BY THE AUTHORITY HAVING JURISDICTION
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By lwagner Date 2013-11-12 Time 13:53 Rev Time 0.00
Received By lwagner Date 2013-11-12 Time 12:43 Sent To  
Notes
2013-11-12 13:53:08 
 ***PROVISO***
 5" REQUIRED 402.4(2) LONGEST DISTANCE METHOD - SEE PLAN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2014-01-23 Time 06:19 Rev Time 0.00
Received By jwitmer Date 2014-01-22 Time 16:04 Sent To  
Notes
2014-01-22 16:04:12SHORING SHOPS TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-23 Cont ID  
Sent By jwitmer Date 2013-10-20 Time 06:19 Rev Time 0.00
Received By jwitmer Date 2013-10-18 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-01 Cont ID  
Sent By rbrown Date 2013-10-01 Time 15:52 Rev Time 0.00
Received By rbrown Date 2013-08-02 Time 12:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-12-02 Cont ID  
Sent By jwitmer Date 2013-12-02 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2013-12-02 Time 15:55 Sent To  
Notes
2013-12-02 15:57:18IMPACT FEE ASSESSMENT
 MU-2013-025178-0000
 $282,972.32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-16 Cont ID  
Sent By jwitmer Date 2013-11-16 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2013-11-16 Time 15:26 Sent To  
Notes
2013-11-16 15:27:10PRODUCE AN IMPACT FEE RECEIPT THAT IMPACT FEES WERE
 PAID UNDER THE FOUNDATION PERMIT OR BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By jwitmer Date 2013-08-29 Time 06:41 Rev Time 0.00
Received By jwitmer Date 2013-08-29 Time 06:39 Sent To  
Notes
2013-08-29 06:41:17PRODUCE AN IMPACT FEE RECEIPT THAT IMPACT FEES WERE
 PAID UNDER THE FOUNDATION PERMIT OR BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-31 Cont ID  
Sent By rregueir Date 2013-10-31 Time 09:38 Rev Time 0.00
Received By rregueir Date 2013-10-31 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-14 Cont ID  
Sent By rregueir Date 2013-09-14 Time 16:32 Rev Time 0.00
Received By rregueir Date 2013-09-12 Time 14:54 Sent To  
Notes
2013-09-14 16:31:25REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010 CODE FAMILY W/ 2012 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M2.1 EXERCISE ROOM 142, TWO OF THE SIX SUPLY
 REGISTERS DO NOT SHOW THE DUCTS THAT FEED THEM. PLEASE
 CORRECT. FBC-M 603.1.
  
 2. PAGE M2.1 FIRE PUMP ROOM 141 WALLS CARRY A 2-HOUR
 FIRE RATING. SHOW HOW DUCT PENETRATION OF THIE REATED
 WALL IS TO BE PROTECTED PER FBC-M 607.5.
  
 3. PAGE M2.1 TERMINATION ROOM 131 WALLS CARRY A 1-HOUR
 FIRE RATING. SHOW HOW DUCT PENETRATION OF THIS REATED
 WALL IS TO BE PROTECTED PER FBC-M 607.5.
  
 4. PAGE M2.1 FIRE ROOM 131 WALLS CARRY A 1-HOUR FIRE
 RATING. SHOW HOW DUCT PENETRATION OF THIS REATED WALL
 IS TO BE PROTECTED PER FBC-M 607.5.
  
 5. PAGE M2.1 PREP ROOM 113 COMMERCIAL KITCHEN GREASE
 EXHAUST SYSTEM REQUIRES SEPARATE PLANS AND PERMIT.
  
 6. PAGE M2.2 THROUGH M2.6: ALL DUCT PENETRATIONS OF
 RATED SHAFT ENCLOSURES SHALL BE PROTECTED WITH FIRE AND
 SMOKE DAMPERS PER FBC-M 607.5.5.
  
 7. PAGE M2.2 THROUGH M2.6: PENETRATIONS OF RATED
 CORRIDOR SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS
 PER FBC-M 607.5.4.
  
 8. PAGE M4.1 PLAN NOTE M18 CALL FOR CONDENSATE TO
 DISCHARGE INTO SINK P-TRAP. CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE.
  
 9. PAGE M4.1 PLAN NOTE M34 CALLS FOR DOOR UNDERCUT FOR
 RETURN AIR. BALANCED RETURN IS REQUIRED IN ALL
 HABITABLE ROOMS PER FBC-M 601.4.
  
 10. PROVIDE COOLING AND HEATING LOAD CLACULATIONS.
  
 11. PROVIDE RATIONAL ANALYSIS FOR SMOKE CONTROL SYSTEM
 PER FBC-B 909.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-11-12 Cont ID  
Sent By lwagner Date 2013-11-12 Time 13:56 Rev Time 0.00
Received By lwagner Date 2013-10-30 Time 14:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By lwagner Date 2013-09-05 Time 15:14 Rev Time 0.00
Received By lwagner Date 2013-08-15 Time 09:47 Sent To  
Notes
2013-09-04 14:37:25FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P1.1 THE MINIMUM HOT WATER SCHEDULE
 TEMPRATURES SHOWN ARE ABOVE THAT ALLOWED IN THE FLORIDA
 ENEGRY CODE:
 504.3 TEMPERATURE CONTROLS.
 SERVICE WATER-HEATING EQUIPMENT SHALL BE PROVIDED WITH
 CONTROLS TO ALLOW A SETPOINT OF 110?F (43?C) FOR
 EQUIPMENT SERVING DWELLING UNITS AND 90?F (32?C) FOR
 EQUIPMENT SERVING OTHER OCCUPANCIES. THE OUTLET
 TEMPERATURE OF LAVATORIES IN PUBLIC FACILITY REST ROOMS
 SHALL BE LIMITED TO 110?F (43?C).
  
 FBC PLUMBING 424.3 INDIVIDUAL SHOWER VALVES:
 INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION VALVES
 SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR ASME A112.18.1/CSA
 B125.1 AND SHALL BE INSTALLED AT THE POINT OF USE.
 SHOWER AND TUB-SHOWER COMBINATION VALVES REQUIRED BY
 THIS SECTION SHALL BE EQUIPPED WITH A MEANS TO LIMIT
 THE MAXIMUM SETTING OF THE VALVE TO 120?F (49?C), WHICH
 SHALL BE FIELD ADJUSTED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS. IN-LINE THERMOSTATIC
 VALVES SHALL NOT BE UTILIZED FOR COMPLIANCE WITH THIS
 SECTION.
  
 FOR PUBLIC HAND WASHING:
 FBC PLUMBING 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM PUBLIC
 HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
  
 2. SHEET P4-1:
 A. THE RISERS SHOWN APPEAR TO BE WASTE STACK VENTS.
 WATER CLOSETS ARE NOT PERMITTED ON WASTE STACK VENTS.
 910.2 STACK INSTALLATION.
 THE WASTE STACK SHALL BE VERTICAL, AND BOTH HORIZONTAL
 AND VERTICAL OFFSETS SHALL BE PROHIBITED BETWEEN THE
 LOWEST FIXTURE DRAIN CONNECTION AND THE HIGHEST FIXTURE
 DRAIN CONNECTION. EVERY FIXTURE DRAIN SHALL CONNECT
 SEPARATELY TO THE WASTE STACK. THE STACK SHALL NOT
 RECEIVE THE DISCHARGE OF WATER CLOSETS OR URINALS.
  
 B. THE VENTS ARE NOT PERMITTED TO BE LESS THAN THE SIZE
 OF THE WASTE STACK.
 910.3 STACK VENT.
 A STACK VENT SHALL BE PROVIDED FOR THE WASTE STACK. THE
 SIZE OF THE STACK VENT SHALL BE NOT LESS THAN THE SIZE
 OF THE WASTE STACK. OFFSETS SHALL BE PERMITTED IN THE
 STACK VENT, SHALL BE LOCATED AT LEAST 6 INCHES (152 MM)
 ABOVE THE FLOOD LEVEL OF THE HIGHEST FIXTURE AND SHALL
 BE IN ACCORDANCE WITH SECTION 905.2. THE STACK VENT
 SHALL BE PERMITTED TO CONNECT WITH OTHER STACK VENTS
 AND VENT STACKS IN ACCORDANCE WITH SECTION 903.5.
  
 C. THE TWO INCH SINK STACKS ON RISER DETAIL #5 & #7
 WOULD BE UNDERSIZED.
 TABLE 910.4
 WASTE STACK VENT SIZE 2" = 4 FIXTURE UNITS
  
 D. THE WATER RISER AND DOWNFEED PIPES REQUIRE SEPARATE
 SHUTOFF VALVES.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ON THE BASE OF EVERY WATER RISER PIPE IN OCCUPANCIES
 OTHER THAN MULTIPLE-FAMILY RESIDENTIAL OCCUPANCIES THAT
 ARE TWO STORIES OR LESS IN HEIGHT AND IN ONE-AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
 ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
  
 3. SHEET P3.2 THE KITCHEN HAND SINKS CONNECTED TO 140
 DEGREE HOT WILL REQUIRE MIXING VALVES.
 424.7 TEMPERATURE-ACTUATED, FLOW REDUCTION VALVES FOR
 INDIVIDUAL FIXTURE FITTINGS.
 TEMPERATURE-ACTUATED, FLOW REDUCTION DEVICES, WHERE
 INSTALLED FOR INDIVIDUAL FIXTURE FITTINGS, SHALL
 CONFORM TO ASSE 1062. SUCH VALVES SHALL NOT BE USED
 ALONE AS A SUBSTITUTE FOR THE BALANCED PRESSURE,
 THERMOSTATIC OR COMBINATION SHOWER VALVES REQUIRED IN
 SECTION 424.3.
  
 ***PROVISO***
 1. SHEET C-8 THE 12" PVC LINE UNDER THE BUILDING SHALL
 BE OF A MATERIAL ALLOWED BY FBC PLUMBING TABLE 702.2
 SECTION 1102
 MATERIALS
 1102.1 GENERAL.
 THE MATERIALS AND METHODS UTILIZED FOR THE CONSTRUCTION
 AND INSTALLATION OF STORM DRAINAGE SYSTEMS SHALL COMPLY
 WITH THIS SECTION AND THE APPLICABLE PROVISIONS OF
 CHAPTER 7.
 1102.3 UNDERGROUND BUILDING STORM DRAIN PIPE.
 UNDERGROUND BUILDING STORM DRAIN PIPE SHALL CONFORM TO
 ONE OF THE STANDARDS LISTED IN TABLE 702.2.
  
 2. ALL HOSE BIBBS/ WALL HYDRANTS REQUIRE SEPARATE
 SHUTOFF VALVES.
 606.2 LOCATION OF SHUTOFF VALVES.
 SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-12-06 Cont ID  
Sent By rregueir Date 2013-12-06 Time 11:33 Rev Time 0.00
Received By rregueir Date 2013-12-06 Time 11:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-11-26 Cont ID  
Sent By aaponte Date 2013-11-25 Time 12:04 Rev Time 0.00
Received By aaponte Date 2013-11-25 Time 12:04 Sent To  
Notes
2013-11-26 11:21:41PROVISO: THE FOLLOWING COMMENTS SHALL BE ADDRESSED:
 1.BASE PLANTING SHALL BE INSTALLED BETWEEN THE PROPERTY
 LINE AND THE BUILDING FACADE ALONG HIBISCUS STREET (DAC
 APPROVAL).
 2. PRIVATE OPEN SPACE AND PUBLIC OPEN SPACE SHALL
 COMPLY WITH OPEN SPACE REGULATIONS AND TABLE IV-7 AND
 IV-8 OF THE ZONING CODE. PLEASE PROVIDE A FULL TABLE
 THAT DEMONSTRATE COMPLIANCE FOR EACH TYPE.
 3.FENCE ON SOUTH SIDE OF POOL CAN NOT BE MORE THAN 4
 FEET IN HEIGHT.
 4. PROPOSED FENCE ON NORTH SIDE OF PUBLIC OPEN SPACE IS
 NOT PERMITTED. BUILDING FACADE SHALL BE ADJACENT TO
 PUBLIC OPEN SPACE.
 5. LANDACAPE DRAWINGS STILL SHOW LIGHT POLE IN THE
 MIDDLE OF THE HIBISCUS SIDEWALK.
 6. SPECIMEN TREE WAS REMOVED FROM PUBLIC OPEN SPACE.
 TREE CANOPY REQUIREMENT SHALL BE MET.
 7. METAL AWNING ON HIBISCUS STREET SHALL PROJECT A
 MINIMUM OF 3 FEET.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2013-10-30 15:05:1210/29/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-09-11 Cont ID  
Sent By aaponte Date 2013-09-10 Time 13:14 Rev Time 0.00
Received By aaponte Date 2013-09-10 Time 13:14 Sent To  
Notes
2013-09-11 09:07:121. FINAL CONFIGURATION OF HIBISCUS STREET STREETSCAPE
 IS CONTINGENT TO SUBMITTAL OF REVISED STREET SURVEY AND
 DISCUSSIONS WITH THE ENGINEERING DEPARTMENT.
 2. STREET LIGTHS SHALL BE THE CITY STANDARD, AND
 LOCATED TWO FEET FROM THE BACK OF THE CURB TO TEH
 CENTER OF THE POLE ("LUMEC" CAT
 #175MH-L50-PCFC-SE3-OTA/240V-SFO-1-BKTX BLACK). THE
 FIXTURE SHALL BE LED.
 3. PARKING SPACES ON THE WEST SIDE OF THE DROP-OFF-AREA
 SHALL BE COMPACT SPACES TO ALLOW FOR THE REQUIRED 5
 FEET LANDSCAPE BUFFER.
 4. PLANTING AREA ALONG THE ALLEY SHALL BE PROTECTED
 WITH A CURB OR BOLLARDS.
 5. BASE PLANTING SHALL BE INSTALLED ALONG THE BUILDING
 AS REQUIRED IN CONDITION OF APPROVAL FROM DAC, AND
 PRESENTED FOR THE SITE PLAN APPROVAL.
 6. ROOT BARRIERS ARE REQUIRED AROUND STREET TREET, AND
 10 FEET OF STRUCTURAL SOIL SHALL BE INSTALLED AROUND
 THE TREE GRATES PROPOSED ALONG THE SIDEWALK.
 7.THE NORTH PORTION OF THE ENTRY PLAZA CANNOT BE
 SEPARATED WITH THE PROPOSED FENCE AND GATE.THE ENTRY
 PLAZA SHALL BE MAINTAINED AS A PUBLIC OPEN SPACE.
 8. EXISTING DROP CURB ON DIXIE HWAY (CLOSER TO GARDENIA
 STREET) SHALL BE REMOVED AND REPLACED BY A REGULAR
 CURB. PLEASE DISCUSS WITH THE ENGINEERIGN DEPARTMENT
 THE REQUIRED CURB TYPE.
 9. A NEW LIVE OAK SHALL BE PLANTED IN A TREE GRATE
 ALONG DIXIE HWAY, 30 FEET NORTH OF THE EXISTING TREE IN
 FRONT OF THE SURFACE PARKING LOT.
 10.PROPOSED LIGHT POLES IN MIDDLE ISLANDS MAY CONFLICT
 WITH PROPOSED LANDSCAPE. PLEASE RELOCATE LIGHT POLES OR
 DEMONSTRATE THERE IS NO CONFLICT.
 11. ALL FENCES AND GATES ALONG THE FRONTAGE LINE WITHIN
 THE FRONT SETBACK SHALL BE A MAXIMUM OF 4 FEET. FENCES
 WITHIN THE SIDE OR REAR SETBACK SHALL NOT BE MORE THAN
 6' IN HEIGHT.
 12. PLEASE INCLUDE A DIAGRAM INDICATING THE AREAS
 CALCULATED FOR THE PRIVATE OPEN SPACE AND HOW IT
 COMPLIES WITH THE MINIMUM 30% VEGETATED AREA, AND 20%
 TREE CANOPY REQUIRED. SYNTETHIC TURF IS NOT CONSIDERED
 VEGETATED AREA.
 13. PLANTING AREA ADJACENT TO DROP OFF ENTRANCE IS ONLY
 20". PLEASE VERIFY THAT WIDTH IS SUFFICIENT TO
 ACCOMODATE AND ALLOW HEALTHY GROWTH OF PROPOSED
 LANDSCAPE.
 14. PORTE COCHERE ROOF TREATMENT SHALL INCLUDE
 ADDITIONAL TREATMENT AS PRESENTED IN RENDERS FOR THE
 DAC SPECIAL REVIEW APPROVAL.
 15.PLEASE INCLUDE PROPERTY LINE IN ALL FLOOR PLANS,
 ELEVATIONS, AND SECTIONS.
 16. ANY MECHANICAL EQUIPMENT ON ROOF TOP SHALL BE
 SCREENED FROM VIEW. PLEASE PROVIDE INFORMATION TO
 CONFIRM COMPLIANCE.
 17. ALL ROOF MEMBRANES SHALL INCLUDE A SOLAR
 REFLECTANCE INDEX (SRI) GREATER THAN OR EQUAL TO 78.
 PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE.
 18. . BUILDING AREA INCLUDED IN SHEET C-06 IS
 104,549SF, WHILE BUILDING AREA INCLUDED IN SHEET A1-01
 IS 107,996SF. PLEASE VEFIRY ALL THE INFORMATION AND
 CREATE ONE SINGLE TABLE BASED ON THE DEFINITION OF
 GROSS BUILDING AREA IN THE ZONING CODE.PLEASE INCLUDE
 DIAGRAMS INDICATING THE AREAS INCLUDED IN THE TOTAL
 GROSS BUILDING AREA IN EACH FLOOR, AND THE TOTAL
 MECHANICAL AREA. PLEASE INCLUDE THE FAR CALCULATION AND
 THE TOTAL AMOUNT OF TDRS NEEDED.
 19. PLEASE INCLUDE A NOTE IN THE DRAWINGS INDICATING
 THE PARKING IS PROVIDED OFF-SITE BASED ON DAC APPROVAL
 (DAC CASE NO. 13-04).
 20. PLEASE INCLUDE A TABLE TO CONFIRM COMPLIANCE FOR
 THE MINIMUM 15% FENESTRATION REQUIREMENT ON EACH
 ELEVATION(TABLE IV-4:FACADE ARTICULATION REQUIREMENTS).
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
  
 3.
 LANDSCPAE PERMTI SHALL BE SUBMITTEDAS A SEPARATE PERMIT
 FOR REVIEW.