Plan Review Details - Permit 13070764
Plan Review Stops For Permit 13070764
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2013-07-27 Cont ID  
Sent By jwitmer Date 2013-07-27 Time 06:40 Rev Time 0.00
Received By jwitmer Date 2013-07-27 Time 06:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-30 Cont ID  
Sent By dharvey Date 2013-07-26 Time 10:05 Rev Time 0.00
Received By dharvey Date 2013-07-30 Time 16:11 Sent To  
Notes
2013-07-30 16:19:17BASED ON ADDITIONAL RECEIVED FROM CONTRACTOR REGARDING
 THE RATED CEILING EXISTING ABOVE THE NEW DROP CEILING,
 PLAN IS BEING APPROVED WITH NOTES REGARDING PROTECTION
 OF ANY PENETRATION OF RATED CEILING. PLACED BACK IN
 DENIED UNDER "C" DUE TO MECHANICAL NOT SIGNING OFF. DH
 7/30/13
2013-07-26 10:05:12PUT IN DENIED UNDER "C" DH
  
 PROVIDE DETAILS OF RATED PENETRATIONS, INCLUDING
 CEILING BOXES AND OTHER ITEMS, 300.22. PROVIDE DETAILS
 OF CEILING FIXTURE SUPPORT AND ATTACHMENT SHOWING FIRE
 RATING DESIGN NUMBER. 410.36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-31 Cont ID  
Sent By hmoser Date 2013-07-31 Time 10:23 Rev Time 0.00
Received By hmoser Date 2013-07-30 Time 18:00 Sent To  
Notes
2013-07-30 18:00:53SENT TO H MOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-30 Cont ID  
Sent By rmcdouga Date 2013-07-30 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2013-07-22 Time 15:51 Sent To  
Notes
2013-07-22 15:51:29SENT TO B18 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-31 Cont ID  
Sent By hmoser Date 2013-07-31 Time 10:23 Rev Time 0.00
Received By hmoser Date 2013-07-31 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-26 Cont ID  
Sent By hmoser Date 2013-07-26 Time 09:12 Rev Time 0.00
Received By hmoser Date 2013-07-26 Time 08:30 Sent To E
Notes
2013-07-26 09:12:13REVISION DENIED
 ALL MECHANICAL PLANS MUST HAVE A
 MECHANICAL ENGINEER SEAL ON THE PLANS.
 PER FLORIDA STATUTES 407.003 QUALIFICATIONS
 FOR PRACTICE; EXEMPTIONS.
 ALL MECHANICAL PLANS MUST BE SEALED BY A
 MECHANICAL ENGINEER .
 PLAN REVIEW BY HAROLD MOSER
 HMOSER@ WPB.ORG
 OFFICE 561-805-6732
 FAX 561-805-6676