Plan Review Details - Permit 13070748
Plan Review Stops For Permit 13070748
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-19 Cont ID  
Sent By jwitmer Date 2013-10-19 Time 08:48 Rev Time 0.00
Received By jwitmer Date 2013-10-19 Time 08:28 Sent To  
Notes
2013-10-19 08:55:15BUILDING PLAN REVIEW
 PERMIT:
 13070748 UNIT # 1 2,564 SQ FT
 13070750 UNIT # 2 2,112 SQ FT
 13070752 UNIT # 11 1,868 SQ FT
 13070753 UNIT # 12 1,339 SQ FT
 13070754 UNIT # 14 1,434 SQ FT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-30 Cont ID  
Sent By jwitmer Date 2013-07-30 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2013-07-30 Time 07:02 Sent To  
Notes
2013-07-30 10:19:12BUILDING PLAN REVIEW
 PERMIT:
 13070748 UNIT # 1 2,564 SQ FT
 13070750 UNIT # 2 2,112 SQ FT
 13070752 UNIT # 11 1,868 SQ FT
 13070753 UNIT # 12 1,339 SQ FT
 13070754 UNIT # 14 1,434 SQ FT
  
 APPLY DATE: 7/19/2013
  
 ADD: 480 HIBISCUS ST
 CONT: BLUEWATER BUILDERS GROUP, INC
 TEL: (954)753-7233
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 30/2013
 ACTION: DENIED
  
 1) SHEET A.001 UNDER THE HEADING EXISTING BUILDING
 CONSTRUCTION DATA, PLANS INDICATE NO OCCUPANCY CHANGE,
 (NONE) A R2. UNDER THE ORIGINAL BUILDING PERMIT
 05091265 ALL OF THE FIRST FLOOR UNITS WERE BUILT AS
 COMMERCIAL UNITS, PLEASE BE AWARE THERE IS A OCCUPANCY
 CHANGE AND THIS REVIEW WILL BE FROM THE
 2010 FBC- EXISTING BUILDING CHAPTER 9 CHANGE OF
 OCCUPANCY SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY. PLEASE UPDATE PLANS.
  
 2A) SHEETS :
 A251A & A401A/ UNIT A
 A251B & A401B/ UNIT B
 A251D & A401D/ UNIT D
 A251E & A401E/ UNIT E
  
 THE ABOVE STATED PLANS INDICATE THE EXISTING WINDOWS IN
 THE BEDROOMS TO BE MODIFIED FOR EGRESS WINDOWS. THIS IS
 NOT A CODE REQUIREMENT, THE 2010 FBC-B
 1029.1 EMERGENCY ESCAPE & RESCUE OPENINGS PLEASE REVIEW
 EXCEPTION # 1. IN OTHER THAN GROUP R-3 OCCUPANCIES,
 BUILDINGS EQUIPPED THROUGHOUT WITH AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2.
  
 THE A401 SERIES OF PLANS INDICATES THE SLIDING WINDOW
 TO HAVE A CLEAR HEIGHT OF 22 INCHES, 2010 FBC-B
 1029.2.1 MINIMUM DIMENSIONS THE MINIMUM HEIGHT
 DIMENSION OF 24" WOULD BE REQUIRED. 24X 30= 720 SQ
 INCHES OR THE MINIMUM 5'-0" SQ FT AS REQUIRED FOR THE
 GROUND FLOOR.
  
 2B) IF THE WINDOWS AND MULLIONS ARE GOING TO BE
 REPLACED THEN THE FOLLOWING WIND DESIGN CRITERIA IS
 REQUIRED:
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 2B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2B)(5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) .
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-23 Cont ID  
Sent By dharvey Date 2013-10-23 Time 19:21 Rev Time 0.00
Received By albarran Date 2013-10-23 Time 19:21 Sent To I
Notes
2013-10-23 19:31:02THE ELECTRICAL PLAN REVIEW SHOWED NONCOMPLIANCE WITH
 THE REQUIREMENTS OF NEC 210.52 (A)(1) THROUGH (A)(3).
 FILE COPY OF THE PLANS HAVE BEEN MARKED ACCORDINGLY.
 THERE SHALL BE A FLOOR OUTLET ON THE FLOOR LINE ALONG
 THE RAIL AS WELL AS ON THE AREAS OF THE POT SHELVING,
 AND ANY OTHER AREA FOUND TO BE MISSING SUCH BY THE
 FIELD INSPECTOR.
 AS PER NEC 210. 12(B) ACFI IS REQUIRED THROUGH OUT.
 AS PER NEC 406.11 TAMPER-RESISTANT RECEPTACLE ARE
 REQUIRED
 AS PER FBC 314 & 315 SMOKE DETECTORS SHALL BE REQUIRED

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-30 Cont ID  
Sent By dharvey Date 2013-08-30 Time 15:36 Rev Time 0.00
Received By dharvey Date 2013-08-30 Time 15:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-09 Cont ID  
Sent By wjolen Date 2013-10-09 Time 15:32 Rev Time 0.00
Received By scaldero Date 2013-10-09 Time 15:32 Sent To  
Notes
2013-10-09 15:38:17PERMIT # 13070748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***REPEAT COMMENTS***
 ***PROVISO***
  
 TO MINIMIZE NUISANCE ALARMS FOR THE BUILDING, THE SMOKE
 ALARMS AND/OR CARBON MONOXIDE DETECTORS WITHIN THE
 INDIVIDUAL RESIDENTIAL SPACES SHALL NOT BE TIED INTO
 THE BUILDINGS FIRE ALARM SYSTEM, PER SECTION 9.6.2.10.4
 OF NFPA 101.
  
 PER NFPA 72 SECTION 7.4.41, SLEEPING AREA NOTIFICATION
 APPLICANCES SHALL HAVE A SOUND LEVEL OF AT LEAST 15 DB
 ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE
 MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60
 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, WHICHEVER
 IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE SERVED BY THE SYSTEM USING THE
 A-WEIGHTED SCALE (DBA).
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-30 Cont ID  
Sent By wjolin Date 2013-07-30 Time 14:42 Rev Time 0.00
Received By wjolin Date 2013-07-30 Time 13:03 Sent To  
Notes
2013-07-30 14:42:10480 HIBISCUS STREET
 PERMIT #13070748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TO MINIMIZE NUISANCE ALARMS FOR THE BUILDING, THE SMOKE
 ALARMS AND/OR CARBON MONOXIDE DETECTORS WITHIN THE
 INDIVIDUAL RESIDENTIAL SPACES SHALL NOT BE TIED INTO
 THE BUILDINGS FIRE ALARM SYSTEM PER SECTION 9.6.2.10.4
 OF NFPA 101.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER NFPA 72 SECTION 7.4.41, SLEEPING AREA NOTIFICATION
 APPLICANCES SHALL HAVE A SOUND LEVEL OF AT LEAST 15 DB
 ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE
 MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60
 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, WHICHEVER
 IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE SERVED BY THE SYSTEM USING THE
 A-WEIGHTED SCALE (DBA).
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-19 Cont ID  
Sent By jwitmer Date 2013-12-19 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2013-12-19 Time 12:42 Sent To  
Notes
2013-12-19 12:42:51TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-24 Cont ID  
Sent By shill Date 2013-10-24 Time 17:10 Rev Time 0.00
Received By shill Date 2013-09-26 Time 16:00 Sent To  
Notes
2013-09-26 16:01:11B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-30 Cont ID  
Sent By dharvey Date 2013-08-30 Time 15:37 Rev Time 0.00
Received By dharvey Date 2013-07-20 Time 14:35 Sent To  
Notes
2013-08-30 15:37:21TO S HILL
2013-07-20 14:36:07INCOMING SENT TO B26 . JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2013-12-19 Cont ID  
Sent By jwitmer Date 2013-12-19 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2013-12-19 Time 15:15 Sent To  
Notes
2013-12-19 15:17:03MU-2013-24329
 2626 SQ FT
 $2499.72

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-10-29 Cont ID  
Sent By jwitmer Date 2013-10-29 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2013-10-29 Time 11:28 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-10-19 Cont ID  
Sent By jwitmer Date 2013-10-19 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2013-10-19 Time 08:56 Sent To  
Notes
2013-10-19 08:56:26BUILDING PLAN REVIEW
 PERMIT: 13070748 UNIT # 1 2,564 SQ FT
 13070750 UNIT # 2 2,112 SQ FT
 13070752 UNIT # 11 1,868 SQ FT
 13070753 UNIT # 12 1,339 SQ FT
 13070754 UNIT # 14 1,434 SQ FT
 ADD: 480 HIBISCUS ST
 CONT: BLUEWATER BUILDERS GROUP, INC
 TEL: (954)753-7233
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 30/2013
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-30 Cont ID  
Sent By jwitmer Date 2013-07-30 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2013-07-30 Time 10:25 Sent To  
Notes
2013-07-30 10:26:11BUILDING PLAN REVIEW
 PERMIT: 13070748 UNIT # 1 2,564 SQ FT
 13070750 UNIT # 2 2,112 SQ FT
 13070752 UNIT # 11 1,868 SQ FT
 13070753 UNIT # 12 1,339 SQ FT
 13070754 UNIT # 14 1,434 SQ FT
 ADD: 480 HIBISCUS ST
 CONT: BLUEWATER BUILDERS GROUP, INC
 TEL: (954)753-7233
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 30/2013
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-14 Cont ID  
Sent By hmoser Date 2013-08-14 Time 10:24 Rev Time 0.00
Received By hmoser Date 2013-08-13 Time 13:44 Sent To  
Notes
2013-08-14 10:24:27PASS PROVISO
 1) REFER TO SECTION 304.1 GENERAL. PROVIDE
 MANUFACTURER'S INSTALLATION
 INSTRUCTIONS ON THE DRYER AND AIR CONDITIONING
 EQUIPMENT.
 2010 FBC (M) AT FIRST INSPECTION.
 2) REFER TO SECTION 602.2.1 MATERIALS WITH IN PLENUM'S.
 ( DON'T INSTALL WOOD DOORS ON A/C CLOSET )
 2010 FBC (M)
 3) REFER TO SECTION 713.3.1.1 FIRE RESISTANCE RATED
 ASSEMBLIES
 2010 FBC. ( PROVIDE A LISTED DETAIL FROM THE ENGINEER
 ON HOW THE
 REFRIGERANT LINES LEAVE THE SHAFT.AT FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-24 Cont ID  
Sent By lwagner Date 2013-07-24 Time 12:53 Rev Time 0.00
Received By lwagner Date 2013-07-24 Time 09:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-15 Cont ID  
Sent By aaponte Date 2013-08-15 Time 14:29 Rev Time 0.00
Received By aaponte Date 2013-08-15 Time 14:29 Sent To  
Notes
2013-08-15 14:29:52RESIDENTIAL UNITS ALLOWED ALONG HIBISCUS STREET AND
 IRIS STREET.
2013-07-22 11:03:157/22/13