2013-07-20 09:01:07 | BUILDING PLAN REVIEW |
| PERMIT: 13070567 |
| ADD: 700 S ROSEMARY AVE. # 112 |
| CONT: TBD (TO BE DETERMINED) |
| TEL: (407)492-7639 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 20/ 2013 SATURDAY |
| ACTION: DENIED |
| |
| 1) NEW RESTROOM LOCATION ON SHEET A1.0 AND DETAIL SHEET |
| A1.1 DO NOT MEET THE 2010 ACCESSIBILITY CODE. 2010 FL |
| ACCESSIBILITY CODE 202.3.1 PROHIBITED REDUCTION IN |
| ACCESS. |
| AN ALTERATION THAT DECREASES OR HAS THE EFFECT OF |
| DECREASING THE ACCESSIBILITY OF A BUILDING OR FACILITY |
| BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME |
| OF THE ALTERATION IS PROHIBITED. |
| |
| 1A) 2010 FL ACCESSIBILITY CODE 604.1 WATER CLOSETS AND |
| TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH |
| 604.8. |
| |
| 1B) 2010 FL ACCESS. 604.8.1.6 LAVATORY. (FL GRAY BOX |
| FLORIDA SPECIFIC REQUIREMENT) IN NEW CONSTRUCTION, THE |
| WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT SHALL CONTAIN |
| AN ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE AT |
| LEAST 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL SIZE, |
| AND WALL-MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS |
| NOT TO OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY |
| SECTION 604 FOR THE WHEELCHAIR ACCESSIBLE TOILET |
| COMPARTMENT AND SHALL COMPLY WITH SECTION 606. SUCH |
| LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| FIXTURE COUNT FOR THE BUILDING. ALSO SEE FIGURE |
| 604.8.1.6, (FL GRAY BOX FLORIDA SPECIFIC REQUIREMENT). |
| |
| 2A) A1.1 BREAK ROOM DETAIL # 11, THE ELEVATION DETAIL |
| OF THE COUNTER W/ BREAK ROOM SINK DOES NOT INDICATE THE |
| HEIGTH, ASSUMED 34" PLEASE CONFIRM COMPLIANCE WITH 2010 |
| FL ACCESS CODE 606.3 FOR HEIGTH. |
| |
| 2B) THE OTHER ISSUE IS THE SINK HAS A BOTTOM CABINET |
| THAT DOES NOT ALLOW FOR A FRONTAL APPROACH. THE SINK IS |
| CENTERED IN A CABINET 2'-10" ADJACENT TO A WALL OR THE |
| CENTERLINE OF THE SINK FROM THE WALL IS 17 INCHES FROM |
| THE WALL LINE. FL ACCESS CODE 606.2 CLEAR FLOOR SPACE |
| EX # 1 A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| BARS OR A 30 X 48 SPACE THAT WOULD REQUIRE THE SINK |
| CENTERLINE TO BE A MIIMUM OF 24 INCHES FROM THE WALL SO |
| THE SINK CENTER LINE AND CENTER LINE FOR THE CLEAR |
| FLOOR SPACE TO ALIGN. |
| |
| 3) SHEET A1.0 NOTE # A1.03 & SHEET A4.0B DETAILS 14 & |
| 15, NEW WOOD FLOORS TO MATCH EXISTING. THIS IS A TYPE |
| II BUILDING AND MUST MEET THE REQUIREMENT 2010 FBC-B |
| SECTION 603.2 EXCEPTION 2 WOOD FLOORS INSULATION |
| INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING |
| WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 200. ALSO REVIEW |
| 805.1 IF FLOORING SUBFLOOR IS SOLIDLY FILLED OR ON |
| SLEEPERS OR FIRE BLOCKED. |
| |
| 4) SHEET A4.0B; DETAILS 16,19 & 20 DO NOT PROVIDE WHAT |
| MATERIAL IS GOING TO BE INSTALLED? PLEASE PROVIDE |
| COMPLIANCE WITH 2010 FBC-B 806.5 INTERIOR TRIM. |
| MATERIAL, OTHER THAN FOAM PLASTIC USED AS INTERIOR |
| TRIM, SHALL HAVE A MINIMUM CLASS C FLAME SPREAD AND |
| SMOKE-DEVELOPED INDEX WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 84 OR UL 723, AS DESCRIBED IN SECTION 803.1.1. |
| COMBUSTIBLE TRIM, EXCLUDING HANDRAILS AND GUARDRAILS, |
| SHALL NOT EXCEED 10 PERCENT OF THE SPECIFIC WALL OR |
| CEILING AREA IN WHICH IT IS ATTACHED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |