Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-16 Cont ID  
Sent By rmcdouga Date 2013-07-16 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2013-07-16 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-15 Cont ID  
Sent By rmcdouga Date 2013-07-15 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2013-07-15 Time 10:32 Sent To  
Notes
2013-07-15 10:33:492010 FBC
  
 DENIED BY BUILDING
  
 1) THE TAMKO MODIFIED ROOF SYSTEM ON PAGE 13 OF NOA
 NO.12-0716.18 HAS A MAXIMUM EDESIGN PRESSURE OF -52.5
 PSF. THIS PRESSURE IS TOO LOW FOR THE PERIMETER AND
 CORNER AREAS OF THE ROOF. SUBMIT TWO SETS OF SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AS
 SPECIFIED IN LIMITATION NUMBER 7 ON PAGE 15 OF THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-16 Cont ID  
Sent By rmcdouga Date 2013-07-16 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2013-07-15 Time 15:58 Sent To  
Notes
2013-07-15 15:59:23INCOMING SENT TO R MCDOUGALS DESK. JW