Plan Review Details - Permit 13070446
Plan Review Stops For Permit 13070446
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-27 Cont ID  
Sent By jwitmer Date 2013-07-27 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2013-07-27 Time 09:00 Sent To  
Notes
2013-07-27 09:54:36BUILDING PLAN REVIEW
 PERMIT: 13070446
 ADD: 1801 PALM BEACH LAKES BLVD TEMP TRAILER JC PENNEY
 CONT: TO BE DETERMINED
 TEL: (954)818-6478
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 27/ 2013
 ACTION: DENIED
  
 1) SITE PLAN IS OF POOR QUALITY, UNABLE TO DETERMINE
 LOCATION OF PROPOSED INSTALATION.
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 2) THE STATE APPROVED PLANS COVER SHEET UNDER THE
 HEADING GENERAL NOTES INDICATES THESE ITEMS WERE TO BE
 SITE BUILT BY OTHERS AND SUBJECT TO LOCAL
 JURISDICTIONAL REVIEW.
 2A) MISSING DETAILS FOR STAIRS AND RAMP, AN ACCESSIBLE
 ENTRANCE NOTE # 1. 2010 FL ACCESSIBILITY CODE 201.1.1
 VERTICAL ACCESSIBILITY.
  
 2B) EITHER STORM PANELS OR OR WOOD STRUCTURAL PANELS,
 NOTES 12 & 17. 2010 FBC-B 1609.1.2.
  
 2C) A FIRE SEPERATION DISTANCE OF GREATER THAN OR EQUAL
 TO 30'-0". NOTE 15. 2010 FBC-B TABLE 602
  
 2D) GUTTERS AND DOWN SPOUTS. NOTE 16. 2010 FBC-B 1503.7
 & 1503.4.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By dharvey Date 2013-08-29 Time 16:49 Rev Time 0.00
Received By dharvey Date 2013-08-29 Time 16:49 Sent To  
Notes
2013-08-29 16:50:128-29-13
 IS THE SERVICE OVER HEAD DROP OR UG? PLEASE INCLUDE
 FEEDER RISER DIAGRAM.
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By wjolin Date 2013-09-05 Time 17:58 Rev Time 0.00
Received By wjolin Date 2013-09-05 Time 17:50 Sent To  
Notes
2013-09-05 17:58:521801 PALM BEACH LAKES BOULEVARD
 PERMIT #13070446
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A LEGIBLE SITE. INDICATE THE ORIENTATION AND
 DISTANCE OF THE TEMPORARY TRAILER IN REGARDS TO
 ADJACENT STRUCTURES.
  
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2
 TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM
 ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL
 BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS
 SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH
 OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-13 Cont ID  
Sent By shill Date 2013-09-13 Time 17:00 Rev Time 0.00
Received By shill Date 2013-07-12 Time 08:01 Sent To  
Notes
2013-07-15 08:01:48C13

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-07-23 Cont ID  
Sent By lwagner Date 2013-07-23 Time 13:32 Rev Time 0.00
Received By lwagner Date 2013-07-23 Time 13:18 Sent To  
Notes
2013-07-23 13:33:10PLUMBING PERMIT REQUIRED IF CONNECTING TO SEWER AND
 WATER.

Review Stop POLICE POLICE
Rev No 1 Status N Date 2013-09-03 Cont ID  
Sent By shill Date 2013-09-03 Time 07:43 Rev Time 0.00
Received By shill Date 2013-09-03 Time 07:43 Sent To  
Notes
2013-09-03 07:44:19NO POLICE REVIEW REQUIRED FOR TEMPORARY TRAILER PER K
 TUCKER-CARSILLO
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-07-29 Cont ID  
Sent By eschneid Date 2013-07-29 Time 11:21 Rev Time 0.25
Received By eschneid Date 2013-07-29 Time 11:21 Sent To  
Notes
2013-07-29 11:23:09FAILED
  
 1) UNABLE TO TELL THE PROPOSED TRAILER LOCATION FROM
 THE SITE PLAN PROVIDED.
  
 2) COMMENTS MAY BE GENERATED BASED ON THE PROVISION OF
 AN ACCURATE SITE PLAN.
  
 3) NO ISSUES WITH THE TRAILER ITSELF.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-07-16 14:28:527/16/13