Plan Review Details - Permit 13070442
Plan Review Stops For Permit 13070442
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-08 Cont ID  
Sent By dharvey Date 2013-10-08 Time 07:29 Rev Time 0.00
Received By dharvey Date 2013-09-26 Time 16:59 Sent To  
Notes
2013-09-26 17:22:06ADDED AS PROVISOS ON PLANS:
 ENGINEERED LETTER FOR WINDLOAD CERTIFICATION REQUIRED
 BY FIRST INSPECTION
 POLE BASES ARE SPECIFIED TO BE DETERMINED BY BY
 STRUCTURAL ENGINEER - PROVIDE DETERMINATION FOR
 INSPECTION
 ALL FIXTURES AND COMPONENTS TO BE LISTED FOR THE USE
 AND USED WITHIN THEIR RESPECTIVE LISTING
 NOTE 3 ON 2A SE-1 IS CONFUSING. IT ADDRESSES A 39 FOOT
 POLE BEING CUT TO 32'AND THE LISTED POLES ARE 35' AND
 25'
 PROVIDE SEPARATION OF CAMERA, NETWORK, PHONE AND OTHER
 WIRING FROM POWER IN THE POLE (FOUND NOTE ON PLANS)
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-08 Cont ID  
Sent By dharvey Date 2013-10-08 Time 07:29 Rev Time 0.00
Received By dharvey Date 2013-07-13 Time 12:48 Sent To  
Notes
2013-07-15 13:21:04SPOKE TO ELECTRICAL ENGINEER 7/15/13 1:15 PM. HE IS OK
 WITH NOTES BEING PLACED ON PLANS. HE WILL SEND IN A
 SECOND COPY FOR NOTES. SENDING PLANS TO ZONING FOR
 REVIEW IN INTERIM.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-12-10 Cont ID  
Sent By skennedy Date 2013-12-10 Time 11:10 Rev Time 0.00
Received By skennedy Date 2013-11-13 Time 18:42 Sent To  
Notes
2013-11-13 18:43:05SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-23 Cont ID  
Sent By shill Date 2013-10-23 Time 10:43 Rev Time 0.00
Received By shill Date 2013-10-09 Time 08:46 Sent To  
Notes
2013-10-09 08:47:02SENT TO ZONING. GAVE TO LINDA LOUIE. RM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-08 Cont ID  
Sent By dharvey Date 2013-10-08 Time 07:29 Rev Time 0.00
Received By dharvey Date 2013-09-19 Time 18:33 Sent To  
Notes
2013-10-08 07:30:39TO S HILL
2013-09-19 18:33:52GAVE TO D HARVEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-19 Cont ID  
Sent By rmcdouga Date 2013-09-19 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2013-07-12 Time 09:58 Sent To  
Notes
2013-07-12 09:59:10ROUTED TO ELECTRICAL

Review Stop POLICE POLICE
Rev No 2 Status N Date 2013-10-08 Cont ID  
Sent By dharvey Date 2013-10-08 Time 07:30 Rev Time 0.00
Received By dharvey Date 2013-10-08 Time 07:48 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2013-08-20 Time   Rev Time 0.00
Received By   Date 2013-08-20 Time   Sent To  
Notes
2013-08-29 08:13:19PLEASE SUBMIT THE LIGHTING PLAN SHOWN IN OUR PRIOR
 MEETING AND AN UPDATED SECURITY PLAN

Review Stop Z ZONING
Rev No 3 Status P Date 2013-12-09 Cont ID  
Sent By ESCHNEID Date 2013-12-09 Time 18:19 Rev Time 0.50
Received By eschneid Date 2013-11-15 Time 07:45 Sent To PC
Notes
2013-12-09 18:37:35PASSED
  
 THE LIGHTING ENGINEER SHALL CERTIFY, IN WRITING, PRIOR
 TO THE APPROVAL OF THE FINAL INSPECTION (104) THAT THE
 AREAS CIRCLED IN RED ON THE PLAN DO NOT EXCEED 1.0 FOOT
 CANDLES AT THE PROPERTY LINE. THE PHOTOMETRIC NUMBERS
 SEEM TO INDICATE AN EXCESS OF THIS STANDARD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-11-15 07:45:2311/15/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL

Review Stop Z ZONING
Rev No 2 Status F Date 2013-10-23 Cont ID  
Sent By eschneid Date 2013-10-23 Time 08:47 Rev Time 0.75
Received By eschneid Date 2013-10-23 Time 08:47 Sent To B
Notes
2013-10-23 09:53:47FAILED
  
 1) REPEAT COMMENT: THE PALM BEACH OUTLETS DESIGN
 GUIDELINES AND THE CITY CODE LIMIT THE FOOT CANDLE
 LEVELS AT THE PROPERTY LINE (NOT AT VEHICULAR ACCESS
 POINTS) TO A MAXIMUM OF 1 FOOT CANDLE. THE PHOTOMETRIC
 PLANS SHOWS AREAS WHERE STAFF CAN NOT VERIFY THAT THIS
 STANDARD IS BEING MET ON SHEETS 2A SL-1, 2A SL-3 AND 2A
 SL-5. THE LOCATIONS ARE ALONG I-95 AND PALM BEACH LAKES
 BOULEVARD IN FRONT OF THE WHOLE FOODS BUILDING. THE
 PLAN SHOWS VALUES IN EXCESS OF 1.0 FOOT CANDLES WITHIN
 THE PROPERTY LINE AND BELOW 1.0 FOOT CANDLES OUTSIDE OF
 THE PROPERTY LINE, BUT DOES NOT PROVIDE THE FOOTCANDLE
 VALUE AT THE PROPERTY LINE. STAFF DOES NOT HAVE THE
 EXPERTISE TO EXTRAPOLATE THE REDUCTION IN FOOTCANDLE
 STRENGTH BETWEEN THE TWO POINTS IN RELATIONSHIP TO THE
 PROPERTY LINE; THEREFORE, IT SHALL BE PROVIDED BY THE
 LIGHTING ENGINEER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2013-07-29 Cont ID  
Sent By eshnied Date 2013-07-29 Time 10:41 Rev Time 0.50
Received By eschneid Date 2013-07-29 Time 10:41 Sent To E
Notes
2013-07-29 10:47:52FAILED
  
 1) THE PALM BEACH OUTLETS DESIGN GUIDELINES AND THE
 CITY CODE LIMIT THE FOOT CANDLE LEVELS AT THE PROPERTY
 LINE (NOT AT VEHICULAR ACCESS POINTS) TO A MAXIMUM OF 1
 FOOT CANDLE. THE PHOTOMETRIC PLANS SHOWS MULTIPLE
 EXAMPLES OF THIS STANDARD BEING EXCEEDED.
  
 2) THE PALM BEACH OUTLETS DESIGN GUIDELINES REQUIRE
 THAT ALL PARKING LOT AND STREET LIGHTING SHALL HAVE
 FLAT GLESS LENSES AND BE FULL CUT OFF. THE SUBMITTED
 PLANS DO NOT VERIFY THIS REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.