Plan Review Details - Permit 13070333
Plan Review Stops For Permit 13070333
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-12 Cont ID  
Sent By dharvey Date 2013-08-12 Time 15:26 Rev Time 0.00
Received By dharvey Date 2013-08-12 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-29 Cont ID  
Sent By dharvey Date 2013-07-29 Time 15:19 Rev Time 0.00
Received By dharvey Date 2013-08-12 Time 15:26 Sent To G
Notes
2013-07-29 15:19:06PROVIDE CONDUCTORS FOR 200 AMP (310.15). PANEL TO BE
 RATED 200 AMP OR PROVIDE OVERCURRENT THAT COINCIDES
 WITH PANEL RATING (408.36). PROVIDE INTERSYSTEM BONDING
 POINT PER 250.94. PROVIDE LOAD CALCULATION AND LOADS
 PER PANEL.
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-07-31 Cont ID  
Sent By lwagner Date 2013-07-31 Time 14:11 Rev Time 0.00
Received By lwagner Date 2013-07-31 Time 14:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-12 Cont ID  
Sent By dharvey Date 2013-08-12 Time 15:26 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 16:08 Sent To  
Notes
2013-08-12 15:26:36TO S HILL
2013-08-07 16:09:31INCOMING SENT TO <$5K ELECTRIC BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-31 Cont ID  
Sent By lwagner Date 2013-07-31 Time 14:11 Rev Time 0.00
Received By lwagner Date 2013-07-10 Time 11:54 Sent To  
Notes
2013-07-10 11:55:15ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-19 Cont ID  
Sent By ajones Date 2013-07-19 Time 09:55 Rev Time 0.00
Received By ajones Date 2013-07-12 Time 15:55 Sent To E
Notes
***NONE***