Plan Review Details - Permit 13070299
Plan Review Stops For Permit 13070299
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2014-04-09 Cont ID  
Sent By jwitmer Date 2014-04-09 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2014-04-09 Time 15:02 Sent To  
Notes
2014-04-09 15:04:19ENGINEERED PRODUCT APPROVALS, WINDOWS, DOORS, LOUVERS
 FOR ALL BUILDINGS AT THE IBIS SPORTS CENTER. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-03-22 Cont ID  
Sent By jwitmer Date 2014-03-22 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2014-03-22 Time 09:30 Sent To  
Notes
2014-03-22 09:58:45ENGINEERED STEEL SHOP DRAWINGS FOR ALL BUILDINGS AT THE
 IBIS SPORTS CENTER. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-03-18 Cont ID  
Sent By jwitmer Date 2014-03-18 Time 14:33 Rev Time 0.00
Received By jwitmer Date 2014-03-18 Time 12:31 Sent To  
Notes
2014-03-18 14:33:35MASTER PERMIT # 13070299
 3/18/2014 # 13070293 POOL LOCKER BUILDING ENGINEERED
 WOOD TRUSS DRAWINGS
 3/18/2014 # 13070299 BRISTO & FITNESS BUILDING,
 ENGINEERED WOOD TRUSS DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-02-20 Cont ID  
Sent By jwitmer Date 2014-02-20 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2014-02-20 Time 12:28 Sent To  
Notes
2014-02-20 12:28:312/20/2014 CALLED CONTRACTOR, TRUSS SHOP DRAWING ARE
 READY FRO PICK-UP, FILED UNDER "T" SMALL PLANS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-10-02 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2013-10-02 Time 13:56 Sent To  
Notes
2013-10-02 13:59:37BUILDING PLAN REVIEW
 PERMIT: 13070299
 ADD: 8100 IBIS BLVD
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE:10/02/2013
 ACTION:PROVISO
  
 1) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) NOTE TO DATE NO PRODUCT APPROVALS WERE SUBMITTED.
 THE PRESSURES ARE OK, THE CONTRACTOR MAY ELICT TO
 SUBMIT THE PRODUCT APPROVALS AFTER THE PERMIT ISSUANCE,
 BUT THIS WOULD BE CONSIDERED A REVISION FOR EACH
 REVIEW, WITH ASSOCIATED FEES. E-MAIL SENT BY LARRY
 ZABIK 9/26/13 PRODUCT APPROVALS TO BE SUBMITTED AS A
 REVISION WITH ASSOCIATED FEES.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 14:45 Sent To  
Notes
2013-09-25 15:45:48BUILDING PLAN REVIEW
 PERMIT: 13070299
 ADD: 8100 IBIS BLVD
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: 9/25/2013
 ACTION: DENIED
  
 1) THE PHASE 1 SPORTS VILLAGE AT IBIS GOLF & COUNTRY
 CLUB IS BEING REVIEWED UNDER A MASTER PERMIT. ONCE THE
 MASTER PLAN IS READY TO ISSUE, PERMIT APPLICATIONS FOR
 EACH BUILDING AND THE POOL DECK WILL BE REQUIRED FOR
 RECORD KEEPING, AND INSPECTIONS TRACKING FOR EACH
 STRUCTURE.
  
 2-5) COMPLIED
  
 6) 2ND REQUEST, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) NOTE TO DATE NO PRODUCT APPROVALS WERE SUBMITTED.
 THE PRESSURES ARE OK, THE CONTRACTOR MAY ELICT TO
 SUBMIT THE PRODUCT APPROVALS AFTER THE PERMIT ISSUANCE,
 BUT THIS WOULD BE CONSIDERED A REVISION FOR EACH
 REVIEW, WITH ASSOCIATED FEES.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) COMPLIED.
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-02 Cont ID  
Sent By jwitmer Date 2013-08-02 Time 10:21 Rev Time 0.00
Received By jwitmer Date 2013-07-29 Time 12:31 Sent To  
Notes
2013-07-30 16:17:01BUILDING PLAN REVIEW
 PERMIT: 13070299
 ADD: 8100 IBIS BLVD
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: 7/30/2013
 ACTION: DENIED
  
 1) THE PHASE 1 SPORTS VILLAGE AT IBIS GOLF & COUNTRY
 CLUB IS BEING REVIEWED UNDER A MASTER PERMIT. ONCE THE
 MASTER PLAN IS READY TO ISSUE, PERMIT APPLICATIONS FOR
 EACH BUILDING AND THE POOL DECK WILL BE REQUIRED FOR
 RECORD KEEPING, AND INSPECTIONS TRACKING FOR EACH
 STRUCTURE.
  
 2) SOILS REPORT. MISSING SOILS REPORT BY ECS FLORIDA,
 LLC #25-2169. 2010 FBC-B 1803.6 REPORTING. WHERE
 GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A WRITTEN
 REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED TO THE
 BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED AGENT AT
 THE TIME OF PERMIT APPLICATION.
  
 3) SHEET AE 401 ADA SHOWER ROOM # F117G MEASURES 3'X3'.
 THE 2010 FL ACCESSIBILITY CODE SECTION 608.2 DEALS WITH
 SIZES AND CLEARANCES THAT WILL COMPLY WITH 608.2.
 PLEASE REVIEW 608.2.1 3'X3' TRANSFER TYPE SHOWER
 COMPARTMENTS. NO SEAT IS INDICATED, PLEASE PROVIDE
 COMPLIANCE WITH 608.4 SEATS.
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A
 FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS
 REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY
 FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH
 610.
  
 4) SHEET AE 401 ADA SHOWER ROOM F124J MEASURES 3'X3.5'.
 THE 2010 FL ACCESSIBILITY CODE SECTION 608.2 DEALS WITH
 SIZES AND CLEARANCES THAT WILL COMPLY WITH 608.2.
 PLEASE REVIEW 608.2.1 3'X3' TRANSFER TYPE SHOWER
 COMPARTMENTS. NO SEAT IS INDICATED, PLEASE PROVIDE
 COMPLIANCE WITH 608.4 SEATS.
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A
 FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS
 REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY
 FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH
 610.
  
 5) SHEET AE101F THE FIRST FLOOR FITNESS CENTER, THE
 LOBBY ROOM F101 INDICATES THAT IT IS OPEN TO ABOVE,
 SHEET AE102F INDICATES THE AREA ABOVE THE LOBBY IS OPEN
 TO ABOVE, ADJACENT TO THE SPIN CLASS F203. PLEASE
 CLARIFY IF THIS AREA COMMUNICATES WITH THE SECOND FLOOR
 OR NOT? IT APPEARS THERE MAY BE A HANDRAIL OR
 A GLASS ENCLOSURE THAT SEPERATES THIS AREA FROM THE 2ND
 FLOOR. PLEASE REVIEW 2010 FBC-B 404.6 ENCLOSURES AT
 ATRIUMS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) SHEETS SR004 & SR005 BOTH APPEAR THE NEGATIVE
 PRESSURES APPEAR TO BE A LITTLE LOW, PLEASE PROVIDE
 WHAT THE MEAN ROOF HEIGHT IS FOR EACH BUILDING AND THE
 MULTIPLIER FOR THE HEIGHT, 2010 FBC-B 1609.7(2).
 NEGATIVE PRESSURES ARE TAKEN FROM TOP OF THE BUILDING,
 THE MEAN ROOF HEIGTH, MEAN ROOF HEIGHT. THE AVERAGE OF
 THE ROOF EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST
 POINT ON THE ROOF SURFACE, EXCEPT THAT EAVE HEIGHT
 SHALL BE USED FOR ROOF ANGLE OF LESS THAN OR EQUAL TO
 10 DEGREES.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 12:01 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 06:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-02 Cont ID  
Sent By wjolin Date 2013-10-02 Time 15:10 Rev Time 0.00
Received By wjolin Date 2013-10-02 Time 12:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-06 Cont ID  
Sent By wjolin Date 2013-08-06 Time 16:02 Rev Time 0.00
Received By wjolin Date 2013-07-30 Time 11:39 Sent To  
Notes
2013-08-01 15:56:238100 IBIS BOULEVARD
 PERMIT #13070299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL BUILDINGS SHALL BE PROPERLY IDENTIFIED EITHER BY
 NAME ("FITNESS BLD", "SPA BLD" ETC.) OR NUMERICAL
 ADDRESS. PROVIDE BUILDING ADDRESS VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 SHEET EP101B: INSUFFICIENT NUMBER OF NOTIFICATION
 APPLIANCES SHOWN IN DINING AREA AND NO DEVICES SHOWN IN
 KITCHEN AREA. NO PULL STATION PROVIDED NEAR SECONDARY
 EXIT (DOUBLE DOORS).
  
 SHEET ES101: MONITOR FIRE SPRINKLER BACKFLOW PREVENTER
 WITH FIRE ALARM TAMPER SWITCHES.
  
 SHEET F203: THE SAME FIRE ALARM SYSTEM APPEARS TO
 PROTECT BOTH THE FITNESS AREA AND THE BISTRO AREA. IF
 THESE AREAS ARE TRULY CONSIDERED THE SAME BUILDING THEN
 PROVIDE SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING
 300 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. REFERENCE
 SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE -
 NFPA 101.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 SHEET F203: NO FIRE ALARM NOTIFICATION APPLIANCE IN
 SPIN CLASS #203.
  
 SHEET EP101P: COULD NOT LOCATE ANY MANUAL PULL
 STATIONS.
  
 SHEET EP101S: COULD NOT LOCATE THE FIRE ALARM CONTROL
 PANEL FOR THE SPA BUILDING.
  
 SHEET FP001: COULD NOT REVIEW THIS PLAN BECAUSE ALL THE
 TEXT WAS ILLEGIBLE (LETTERS IN THE SAME WORD ARE
 DIFFERENT SIZES THROUGHOUT).
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-09-27 Cont ID  
Sent By lwagner Date 2013-09-27 Time 15:17 Rev Time 0.00
Received By lwagner Date 2013-09-27 Time 14:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-08-12 Cont ID  
Sent By lwagner Date 2013-08-12 Time 10:40 Rev Time 0.00
Received By lwagner Date 2013-08-12 Time 10:40 Sent To  
Notes
2013-08-12 10:41:53PAGE 182 BISTRO BLDG. PLEASE ADD THE FOLLOWING
 INFORMATION:
 GAS PERMIT APPLICATION REQUIREMENTS
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-03-22 Cont ID  
Sent By jwitmer Date 2014-03-22 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2014-02-28 Time 11:46 Sent To  
Notes
2014-02-28 11:48:30WINDOWS SHOP DRAWINGS SENT TO J. WITMER'S DESK FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-03-22 Cont ID  
Sent By jwitmer Date 2014-03-22 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2014-02-25 Time 14:41 Sent To  
Notes
2014-02-25 14:41:11TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-20 Cont ID  
Sent By jwitmer Date 2014-02-20 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2014-02-12 Time 11:27 Sent To  
Notes
2014-02-13 11:28:27TRUSS PACKAGE SENT TO J. WITMER'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-10-02 Time   Rev Time 0.00
Received By rregueir Date 2013-09-17 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-18 Cont ID  
Sent By shill Date 2013-09-16 Time 13:33 Rev Time 0.00
Received By shill Date 2013-07-16 Time 14:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-09-23 Cont ID  
Sent By jwitmer Date 2013-09-23 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2013-09-23 Time 11:22 Sent To  
Notes
2013-09-23 11:24:23IMPACT FEES
 RECEIPT # 2013-0920-221
 MU-2013-020358-0000
 FEES: $4,745.25.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-02 Cont ID  
Sent By jwitmer Date 2013-08-02 Time 10:21 Rev Time 0.00
Received By jwitmer Date 2013-08-02 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-27 Cont ID  
Sent By rregueir Date 2013-08-27 Time 15:09 Rev Time 0.00
Received By rregueir Date 2013-08-26 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-30 Cont ID  
Sent By lwagner Date 2013-09-30 Time 09:48 Rev Time 0.00
Received By lwagner Date 2013-09-27 Time 14:50 Sent To  
Notes
2013-09-30 09:48:52***NOTE***
 1. THE ITEMS IN #1REVIEW COMMENTS (PAGE 059 FITNESS
 BUILDING & 064 SPA BUILDING: A UNISEX TOILET ROOM WILL
 BE REQUIRED
 403.5 UNISEX TOILET AND BATHING ROOMS.) ARE NOT
 REQUIRED. SPA BUILDING IS TYPE B AND THE FITNESS
 BUILDING REQUIRED WATER CLOSETS AND URINALS DO NOT
 EQUAL 6.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-12 Cont ID  
Sent By lwagner Date 2013-08-12 Time 11:34 Rev Time 0.00
Received By lwagner Date 2013-07-24 Time 13:00 Sent To  
Notes
2013-08-12 10:20:42FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 GENERAL NOTE:
 PAGE 177 THE ELKAY BOTTLE FILLING STATION LZWSMDK DOES
 NOT APPEAR TO MEET THE REQUIREMENTS OF FBC
 ACCESSIBILITY 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.6 WATER FLOW.
 THE SPOUT SHALL PROVIDE A FLOW OF WATER 4 INCHES (100
 MM) HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES (125 MM)
 MAXIMUM FROM THE FRONT OF THE UNIT. THE ANGLE OF THE
 WATER STREAM SHALL BE MEASURED HORIZONTALLY RELATIVE TO
 THE FRONT FACE OF THE UNIT. WHERE SPOUTS ARE LOCATED
 LESS THAN 3 INCHES (75 MM) OF THE FRONT OF THE UNIT,
 THE ANGLE OF THE WATER STREAM SHALL BE 30 DEGREES
 MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3 INCHES (75
 MM) AND 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE
 UNIT, THE ANGLE OF THE WATER STREAM SHALL BE 15 DEGREES
 MAXIMUM.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 1. PAGE 059 FITNESS BUILDING & 064 SPA BUILDING: A
 UNISEX TOILET ROOM WILL BE REQUIRED
 403.5 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. PAGE 185: PLEASE ADD THE FOLLOWING INFORMATION:
 GAS PERMIT APPLICATION REQUIREMENTS:
  
 2A. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 2B. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 2C. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 3. PAGE 191 FITNESS:
 SEE PLAN FOR VENTING REQUIREMENT 901.2.1
  
 4. PAGE 192 POOL BLDG.:
 SEE PLAN FOR VENTING REQUIREMENTS 905.4 & 911.2
  
 5. PAGE 193 POOL BLDG:
 SEE PLAN FOR HOSE BIBB / WALL HYDRANT REQUIREMENT 606.2
  
 6. PAGE 194 SPA:
 SEE PLAN FOR VENTING REQUIREMENT 901.2.1
  
 7. PAGE 197 & 059 THE ELEVATOR IS REQUIRED TO DRAIN TO
 THE SANITARY INDIRECTLY.
 CITY ORD. SEC. 90-203 PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-10-15 Cont ID  
Sent By rregueir Date 2013-10-15 Time 16:33 Rev Time 0.00
Received By rregueir Date 2013-10-15 Time 16:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-09-27 Cont ID  
Sent By ajones Date 2013-09-27 Time 14:03 Rev Time 0.00
Received By ajones Date 2013-09-27 Time 14:03 Sent To  
Notes
2013-10-03 12:10:029/27/13- THIS APPROVAL DOES NOT INCLUDE LANDSCAPING OR
 TREE RELOCATION PERMITS. THE WILL BE APPROVED UNDER A
 SEPERATE PERMIT.
  
 ANGELLA VANN,
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By avann Date 2013-08-28 Time 09:11 Rev Time 0.00
Received By ajones Date 2013-08-28 Time 09:11 Sent To  
Notes
2013-08-28 09:19:398/28/13- FAILED-
 1.THE FOLLOWING CONDITION OF ORDINANCE NO. 4468-13
 REQUIRED THAT PRIOR TO THE ISSUANCE OF THE FIRST
 BUILDING PERMIT, THE APPLICANT/OWNER SHALL:
  WORK WITH THE CITY SURVEYOR TO PROCESS AND RECORD A
 UNITY OF TITLE APPLICATION. AS OF 8/28/13 THIS HAS NOT
 BEEN DONE. ZONING CAN NOT APPROVE THIS PERMIT UNTIL
 THIS CONDITION IS SATISFIED.
 2. AN BUILDING PERMIT APPLICATION SHALL BE SUBMITTED
 INORDER FOR A LANDSCAPE PERMIT TO BE ISSUED FOR THE
 LANDSCAPING INCLUDED IN THIS PERMIT.
  
  
 ANGELLA VANN
 561-822-1441
 [email protected]
  
  