Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2013-07-18 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-07-18 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-07-18 |
Time |
17:08 |
Sent To |
|
|
Notes |
2013-07-18 17:08:21 | AS NOTED ON PLANS | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2013-07-10 |
|
|
Cont ID |
|
Sent By |
dharvey |
Date |
2013-07-10 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
dharvey |
Date |
2013-07-10 |
Time |
13:01 |
Sent To |
Z |
|
Notes |
2013-07-10 14:22:03 | 13070254 | | 701 57TH STREET | | NEW ELECTRIC SERVICE | | | | THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR. | | THE PROPERTY IS SHOWN AS A SINGLE FAMILY AND NOT A TWO | | FAMILY. | | | | PROVIDE A DETAILED ELECTRICAL PLAN WHICH SHOWS THE | | CONDUIT AND CONDUCTORS FEEDING EACH UNIT. NEC 215.5 | | | | SHOW LOCATION OF SERVICE AND MAINS. MAIN DISCONNECTS | | MUST BE SERVICE RATED, WEATHER RESISTANT IF LOCATED | | OUTSIDE AND GROUPED IN ONE LOCATION. NEC 110.20, | | 230.66, 230.79, 230.71 | | | | GROUNDING AND BONDING OF PANEL BOARDS AT SEPARATE | | BUILDINGS SHALL INCLUDE AN EQUIPMENT GROUNDING | | CONDUCTOR AND A GROUNDING ELECTRODE. NEC 250.32 (A) AND | | (B) | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS. FBC R313 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2013-07-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2013-07-17 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2013-07-08 |
Time |
15:52 |
Sent To |
|
|
Notes |
2013-07-08 15:52:25 | ROUTED TO ELECTRICAL < THEN 5000 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2013-07-15 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2013-07-15 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2013-07-12 |
Time |
15:07 |
Sent To |
E |
|
Notes |
|
|
|