Plan Review Details - Permit 13070174
Plan Review Stops For Permit 13070174
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-01-07 Cont ID  
Sent By jgomez Date 2014-01-07 Time 16:53 Rev Time 0.00
Received By jgomez Date 2014-01-07 Time 16:53 Sent To  
Notes
2014-01-07 17:11:24BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 2- SHUTTERS: PROVIDE COMPLETE AND CORRECT INSTALLATION
 SCHEDULE. CLEARLY IDENTIFY MOUNTING CONDITION TO BE
 USED. SEE SHEET 4 OF 7. SEC. 107.2.1 CITY AMENDMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2013-12-12 Cont ID  
Sent By jgomez Date 2013-12-11 Time 16:22 Rev Time 0.00
Received By jgomez Date 2013-12-11 Time 16:22 Sent To  
Notes
2013-12-11 16:23:56RESIDENTIAL (R3) GARAGE CONVERSION, FIFTH CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. (REPEAT
 COMMENT).
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
 (REPEAT COMMENT).
  
 3- REVISE SHUTTER INSTALLATION SCHEDULE. CLEARLY
 SPECIFY MOUNTING CONDITION AT TOP AND BOTTOM TO VERIFY
 ANCHOR SPACING REQUIRED TO MEET THE DESIGN PRESSURES OF
 SEC. R301.1 OF 2010 FBC-RESIDENTIAL. (SEE SHEET 4 OF 7
 AND 5 OF 7 OF DRAWINGS SUBMITTED).
  
 4- ENERGY CALCULATIONS SUBMITTED: OWNER/AGENT TO
 CERTIFY AND DATE BOTTOM OF FORM AS REQUIRED BY SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE WINDOW AND DOOR MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS AS REQUIRED BY
 SEC. 405.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 ***NOTE:
 INFORMATION SUBMITTED IS FOR PGT WINDOWS AND DOORS, BUT
 PRODUCT APPROVAL SUBMITTED IS FOR JELD-WEN DOORS AND
 WINDOWS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-11-25 Cont ID  
Sent By jgomez Date 2013-11-25 Time 17:46 Rev Time 0.00
Received By jgomez Date 2013-11-25 Time 17:46 Sent To  
Notes
2013-11-25 18:46:38RESIDENTIAL (R3) GARAGE CONVERSION, FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. (REPEAT
 COMMENT. THREE TIMES).
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. DRAWINGS FOR
 FLORIDA PRODUCT APPROVAL FL 11120-R8 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES SHOWN ON PLANS.
  
 ***NOTE: ENGINEER OF RECORD APPROVED THIS PRODUCT
 APPROVAL, BUT IT DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY HIM.
  
 B) HURRICANE SHUTTERS. PROVIDE TWO CLEAR COPIES. SECOND
 COPY SUBMITTED IS NOT CLEAR. DRAWINGS ARE INCOMPLETE.
 (NOA 12-0320.26).
  
 C) FRENCH DOORS. PROVIDE TWO COPIES. SECOND COPY
 SUBMITTED IS NOT CLEAR. DRAWING S ARE INCOMPLETE. (NOA
 09-0608.16).
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. (REPEAT COMMENT).
  
 4- REVISE SHUTTER INSTALLATION SCHEDULE. DESIGN
 PRESSURES TO MATCH THOSE SPECIFIED BY THE ENGINEER OF
 RECORD. AND, CLEARLY SPECIFY MOUNTING CONDITION AT TOP
 AND BOTTOM TO VERIFY ANCHOR SPACING REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 5- ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE
 ENTIRE HOUSE. INFORMATION SUBMITTED ON THE ENERGY
 CALCULATIONS WILL NEED TO BE VERIFIED IN THE FIELD.
 OTHERWISE, INSPECTIONS WILL BE FAILED. PROVIDE WINDOW
 AND DOOR SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS AND
 SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE WALLS AND
 CEILING WILL MEET THE R-VALUE INSULATION SHOWN ON THE
 ENERGY CALCULATIONS.. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 6- TYPICAL WALL SECTION DETAIL WAS REVISED. THE R VALUE
 FOR THE WALL IS ONLY FOR THE R VALUE OF THE INSULATION
 INSTALLED. CONCRETE BLOCK SHALL NOT BE INCLUDED. SEC.
 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. REVISE AS
 REQUIRED. NOTE: PLANS AND ENERGY CALCULATIONS NEED TO
 MATCH.
  
 7- PROVIDE MANUFACTURER CUT SHEETS FOR EGRESS WINDOW
 SIZE 36" X 50" SHOWN ON BEDROOM TO VERIFY COMPLIANCE
 WITH SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-11-05 Cont ID  
Sent By jgomez Date 2013-11-05 Time 13:51 Rev Time 0.00
Received By jgomez Date 2013-11-05 Time 11:54 Sent To  
Notes
2013-11-05 14:12:15RESIDENTIAL (R3) GARAGE CONVERSION, THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. (REPEAT
 COMMENT. THREE TIMES).
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS SHOWN ON PLANS. (REPEAT COMMENT. NO
 SUBMITTED).
  
 B) HURRICANE SHUTTERS. PROVIDE TWO COPIES. ONLY ONE WAS
 SUBMITTED. (NOA 12-0320.26).
  
 C) FRENCH DOORS. PROVIDE TWO COPIES. ONLY ONE SUBMITTED
 (NOA 09-0608.16).
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. (REPEAT COMMENT).
  
 ****NOTE:*****
 ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE ENTIRE
 HOUSE. INFORMATION SUBMITTED ON THE ENERGY CALCULATIONS
 WILL NEED TO BE VERIFIED IN THE FIELD. OTHERWISE,
 INSPECTIONS WILL BE FAILED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-26 Cont ID  
Sent By jgomez Date 2013-09-26 Time 11:11 Rev Time 0.00
Received By jgomez Date 2013-09-26 Time 11:11 Sent To  
Notes
2013-09-26 11:12:30RESIDENTIAL (R3) GARAGE CONVERSION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. AND,
 CLARIFY WHY THERE IS AN EXPIRATION DATE OF 2/28/13
 BELOW THE ENGINEER'S LICENSE NUMBER?. (REPEAT COMMENT).
  
 2- SPECIFY TYPE OF WINDOW ON BEDROOM TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS. SEC. R310 OF 2010
 FBC-RESIDENTIAL.
 ***COMMENTS TO RESPONSE:
 A)INFORMATION SUBMITTED DOESN'T SPECIFY TYPE OF WINDOW.
  
 B) PROVIDE MANUFACTURER SPECS SHOWING THAT THE 36" X
 50" SPECIFIED WINDOW MEETS THE EGRESS REQUIREMENTS.
 NEED TO VERIFY MIN. CLEAR WIDTH, MIN. CLEAR HEIGHT AND
 MIN. TOTAL CLEAR OPENING.
  
 3- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 OBTAINING R-6 VALUE IN THE CONCRETE BLOCK WALLS.
 ***COMMENTS TO RESPONSE:
 TYPICAL WALL DETAIL SUBMITTED SHOWS "REFLECTIX FOIL
 INSUL. R-3.79". THIS DOESN'T MEET THE R-6 VALUE. NEED
 TO USE ONLY THE R-VALUE OF THE INSTALLED INSULATION.
 SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 4- ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME AND OWNER'S NAME. (SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE ROOF TYPE ON PAGE 3 OF 6 TO ADD THE FLAT ROOF
 AREA OF THE ADDITION. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS SHOWN ON PLANS. (REPEAT COMMENT. NO
 SUBMITTED).
 ***NOTE: PLEASE MAKE SURE PRODUCT APPROVAL MEETS THE
 CALCULATED DESIGN PRESSURES.
  
 B) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE HURRICANE
 IMPACT GLAZING AND FOR FRENCH DOORS (FRENCH DOORS NOA
 09-0608.16 SUBMITTED IS FOR NON-IMPACT DOOR).
 ***COMMENTS TO RESPONSE: NOA 09-0114.02 SUBMITTED WAS
 CLOSED BY MIAMI-DADE. NEED CURRENT NOA.
  
 C) FRENCH DOORS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. NOA 09-0415.08
 SUBMITTED DOESN'T MEET THOSE DESIGN PRESSURES.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 7- REVISE THE HURRICANE SHUTTERS INSTALLATION SCHEDULE.
 COORDINATE WITH NEW PRODUCT APPROVAL SUBMITTED. SEE
 ITEM #5(B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- PROVIDE MANUFACTURER'S INFORMATION FOR DOORS AND
 WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM
 #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. NOT
 ADDRESSED).
  
  
 *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS...
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-01 Cont ID  
Sent By jgomez Date 2013-08-01 Time 10:33 Rev Time 0.00
Received By jgomez Date 2013-08-01 Time 10:32 Sent To  
Notes
2013-08-01 10:56:47RESIDENTIAL (R3) GARAGE CONVERSION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE"
 INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. AND,
 CLARIFY WHY THERE IS AN EXPIRATION DATE OF 2/28/13
 BELOW THE ENGINEER'S LICENSE NUMBER?.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- SPECIFY SIZE AND TYPE OF WINDOW ON BEDROOM TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS. SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 4- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW
 OBTAINING R-15 VALUE IN THE CONCRETE BLOCK WALLS AND
 R-30 VALUE IN THE FLAT CEILING AS SHOWN ON THE A/C
 EQUIPMENT SIZING CALCULATIONS. AND, COORDINATE THE
 EQUIPMENT SIZING CALCULATIONS INFORMATION WITH THE
 INFORMATION GIVEN IN THE ENERGY CALCULATIONS. SEC.
 405.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 5- ENERGY CALCULATIONS SUBMITTED;
  
 A) COORDINATE THE ENERGY CALCULATIONS WITH THE
 EQUIPMENT SIZING CALCULATIONS (SEE A/C COMMENTS) AND
 FLOOR PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE ROOF TYPE. ADDITION IS A FLAT ROOF NOT
 SHINGLES. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) REVISE THE NAME OF THE BUILDER. SEE PERMIT
 APPLICATION. AND COMPLETE ALL THE INFORMATION ON TOP OF
 FORM, INCLUDING THE OWNER'S NAME. SEC. 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 6- ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR DOORS
 AND WINDOWS. ***NOTE; ACCORDING TO SEC. R301.2.1.4.3 OF
 2010 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN
 EXPOSURE "C".
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS SHOWN ON PLANS.
  
 B) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE HURRICANE
 IMPACT GLAZING AND FOR FRENCH DOORS (FRENCH DOORS NOA
 09-0608.16 SUBMITTED IS FOR NON-IMPACT DOOR).
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE (SEE SHUTTERS INSTALLATION SCHEDULE SAMPLE ON
 THE CITY OF WEST PALM BEACH WEBSITE). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- PROVIDE MANUFACTURER'S INFORMATION FOR DOORS AND
 WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM
 #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 11- DRAWING SUBMITTED SHOW TWO EXISTING COLUMNS IN THE
 "GARAGE FLOOR RAISED" PLAN. WHERE ARE THESE COLUMNS ON
 THE "GARAGE FLOOR PLAN CONVERSION" PLAN?. WHERE THEY
 REMOVED?. IF SO, HOW WAS THE STRUCTURE REINFORCED TO
 TRANSFER THE LOADS. SEC. 301.1 OF 2010 FBC-RESIDENTIAL.
  
 12- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUE TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND PROFESSIONAL DESIGN FEES. REVISE VALUE AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 17:58 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 17:58 Sent To  
Notes
2014-01-08 18:00:07APPROVED WITH EXCEPTION. REDLINED CORRECTIONS ON PLANS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2013-12-04 Cont ID  
Sent By rmcdouga Date 2013-12-04 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2013-12-04 Time 13:43 Sent To B
Notes
2013-12-04 13:46:232010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) THE ENGINEER'S SEAL ON THE DRAWINGS IS NOT
 ACCEPTABLE. SEE 61G15-23.001 SEALS ACCEPTABLE TO THE
 BOARD. HTTPS://WWW.FLRULES.ORG/GATEWAY/RULENO.ASP?ID=61
 G15-23.001
 THIS COMMENT HAS NOT YET BEEN ADDRESSED.
  
 2) THE RESUBMITED PLAN IS MISSING THE FOLLOWING
 INFORMATION THAT WAS ADDRESSED ON THE PREVIOUS PLAN
 SUBMITTAL:
  
 2.1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU
 CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC
 TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1
  
 2.2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING REQUIREMENT.
  
 2.3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE
 REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A)
 (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN
 COUNTER TOPS TO BE GFCI.
  
 2.4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY
 SHED IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A)
 (2)
  
 2.5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED
 SMOKE ALARMS.
  
 2.6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR
 REQUIRED OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE
 DWELLING.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2013-11-16 Cont ID  
Sent By rmcdouga Date 2013-11-16 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2013-11-16 Time 08:32 Sent To  
Notes
2013-11-16 09:23:082010 FBC
  
 DENIED BY ELECTRICAL
  
 1) THE ENGINEER'S SEAL ON THE DRAWINGS IS NOT
 ACCEPTABLE. SEE 61G15-23.001 SEALS ACCEPTABLE TO THE
 BOARD. HTTPS://WWW.FLRULES.ORG/GATEWAY/RULENO.ASP?ID=61
 G15-23.001
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2013-10-31 Cont ID  
Sent By rmcdouga Date 2013-10-31 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2013-10-31 Time 07:54 Sent To  
Notes
2013-10-31 07:55:31COMMENTS FROM THE LAST REVIEW WERE NOT ADDRESSED
  
 2010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU
 CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC
 TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1
  
 2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING REQUIREMENT.
  
 3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE
 REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A)
 (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN
 COUNTER TOPS TO BE GFCI.
  
 4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY SHED
 IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A) (2)
  
 5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED SMOKE
 ALARMS.
  
 6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR REQUIRED
 OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE DWELLING.
  
 7) PLEASE SEE BUILDING REVIEW COMMENTS REGARDING THE
 REQUIRED SEALS THAT ARE ACCEPTABLE TO THE BOARD OF
 FLORIDA ENGINEERS. FAC 61G15-23.001 & SECTION 471.025
 F.S.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-10-22 Cont ID  
Sent By rmcdouga Date 2013-10-22 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2013-10-22 Time 10:53 Sent To  
Notes
2013-10-22 11:37:012010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU
 CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC
 TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1
  
 2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING REQUIREMENT.
  
 3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE
 REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A)
 (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN
 COUNTER TOPS TO BE GFCI.
  
 4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY SHED
 IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A) (2)
  
 5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED SMOKE
 ALARMS.
  
 6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR REQUIRED
 OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE DWELLING.
  
 7) PLEASE SEE BUILDING REVIEW COMMENTS REGARDING THE
 REQUIRED SEALS THAT ARE ACCEPTABLE TO THE BOARD OF
 FLORIDA ENGINEERS. FAC 61G15-23.001 & SECTION 471.025
 F.S.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2013-09-26 11:20:52NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-02 Cont ID  
Sent By rmcdouga Date 2013-08-02 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2013-08-02 Time 09:47 Sent To  
Notes
2013-08-02 11:17:38APPROVED WITH EXCEPTIONS. DEFICIENCIES LISTED ON THE
 ELECTRICAL PLANS ARE REQUIRED TO BE CORRECTED PRIOR TO
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2013-12-26 Time 16:01 Sent To  
Notes
2013-12-26 16:01:56RESUBMITTAL SENT TO R19 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-12-11 Cont ID  
Sent By jgomez Date 2013-12-11 Time 17:11 Rev Time 0.00
Received By jgomez Date 2013-12-04 Time 12:56 Sent To  
Notes
2013-12-04 12:56:33SENT TO MACDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-11-25 Cont ID  
Sent By jgomez Date 2013-11-25 Time 18:58 Rev Time 0.00
Received By jgomez Date 2013-11-07 Time 15:12 Sent To  
Notes
2013-11-08 15:13:25SENT TO R6 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-07 Cont ID  
Sent By jgomez Date 2013-11-05 Time 14:19 Rev Time 0.00
Received By jgomez Date 2013-10-30 Time 07:56 Sent To  
Notes
2013-11-05 16:00:1911/5/13 SENT TO R6 SHELF FOR REVIEW. JG.
2013-10-31 07:57:03SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-22 Cont ID  
Sent By rmcdouga Date 2013-10-22 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 07:49 Sent To  
Notes
2013-09-26 16:46:439/26/13. SENT TO MCDOUGAL'S DESK. NEW SHEETS SUBMITTED.
 JG.
2013-09-20 07:49:47SENT TO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-02 Cont ID  
Sent By jgomez Date 2013-08-02 Time 14:13 Rev Time 0.00
Received By jgomez Date 2013-07-03 Time 10:52 Sent To  
Notes
2013-07-08 10:52:53SENT TO R6 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-09-26 Cont ID  
Sent By jgomez Date 2013-09-26 Time 13:15 Rev Time 0.00
Received By jgomez Date 2013-09-26 Time 13:15 Sent To  
Notes
2013-09-26 13:16:17NO FEES DUE. MU2013-19896. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-01 Cont ID  
Sent By jgomez Date 2013-08-01 Time 16:34 Rev Time 0.00
Received By jgomez Date 2013-08-01 Time 16:34 Sent To  
Notes
2013-08-01 16:34:351- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2014-01-07 Cont ID  
Sent By jgomez Date 2014-01-07 Time 18:38 Rev Time 0.00
Received By jgomez Date 2014-01-07 Time 18:38 Sent To  
Notes
2014-01-07 18:43:23MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE INFORMATION UNDER A SEPARATE A/C
 PERMIT. PROVIDE A/C PLANS AND EQUIPMENT SIZING
 CALCULATIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2013-12-11 Cont ID  
Sent By jgomez Date 2013-12-11 Time 17:05 Rev Time 0.00
Received By jgomez Date 2013-12-11 Time 17:05 Sent To  
Notes
2013-12-11 17:11:21RESIDENTIAL (R3) GARAGE CONVERSION, FIFTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS.
 COMPLETE CALCULATIONS NEED TO BE DONE BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. ALSO, NEED TO SHOW THE MANUFACTURER AND
 MODEL NUMBERS (INDOOR AND OUTDOOR).
  
 ***REPEAT COMMENT. CALCULATIONS WERE NOT SUBMITTED
  
 2- BEDROOM TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2013-11-25 Cont ID  
Sent By jgomez Date 2013-11-25 Time 18:47 Rev Time 0.00
Received By jgomez Date 2013-11-25 Time 18:47 Sent To  
Notes
2013-11-25 18:58:02RESIDENTIAL (R3) GARAGE CONVERSION, FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS.
 COMPLETE CALCULATIONS NEED TO BE DONE BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. ALSO, NEED TO SHOW THE MANUFACTURER AND
 MODEL NUMBERS (INDOOR AND OUTDOOR).
  
 ***NOTE: EQUIPMENT TO MATCH EQUIPMENT LISTED ON
 DRAWINGS SUBMITTED.
  
 ***EQUIPMENT SHOWN ON THE CALCULATIONS DOESN'T MATCH
 PLANS SUBMITTED AND CALCULATIONS ARE NOT DONE BASED ON
 THE ORIENTATION OF THE BUILDING.
  
 B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE
 DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER
 AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT).
  
 ****NOTE: THIS TO BE DONE ON A SEPARATE PERMIT. THIS
 PERMIT APPLICATION IS FOR THE GARAGE CONVERSION ONLY.
  
  
  
 2- BEDROOM TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
 3- EQUIPMENT LISTED ON THE A/C PLAN, EQUIPMENT LISTED
 ON THE EQUIPMENT SIZING CALCULATIONS AND INFORMATION ON
 THE ENERGY CALCULATIONS NEED TO MATCH. CHECK SIZE AND
 SEER, ETC. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2013-11-06 Cont ID  
Sent By jgomez Date 2013-11-06 Time 13:21 Rev Time 0.00
Received By jgomez Date 2013-11-06 Time 13:21 Sent To  
Notes
2013-11-06 13:22:58RESIDENTIAL (R3) GARAGE CONVERSION, THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- A)PROVIDE EQUIPMENT SIZING CALCULATIONS SHOWING THE
 MANUFACTURER AND MODEL NUMBERS (INDOOR AND OUTDOOR) AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE: EQUIPMENT TO MATCH EQUIPMENT LISTED ON
 DRAWINGS SUBMITTED. (REPEAT COMMENT).
  
 B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE
 DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER
 AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT).
  
 2- PLANS TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
 3- EQUIPMENT LISTED ON THE A/C PLAN TO MATCH ENERGY
 CALCULATIONS. CHECK SIZE AND SEER AND REVISE AS
 REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-09-26 Cont ID  
Sent By jgomez Date 2013-09-26 Time 16:19 Rev Time 0.00
Received By jgomez Date 2013-09-26 Time 16:19 Sent To  
Notes
2013-09-26 16:30:36RESIDENTIAL (R3) GARAGE CONVERSION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- A)PROVIDE EQUIPMENT SIZING CALCULATIONS SHOWING THE
 MANUFACTURER AND MODEL NUMBERS (INDOOR AND OUTDOOR) AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 ***NOTE; EQUIPMENT TO MATCH EQUIPMENT LISTED ON
 DRAWINGS SUBMITTED.
  
 B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE
 DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER
 AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT).
  
 2- PLANS TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
 3- PROVIDE DOCUMENTATION SHOWING HOW OBTAINING THE R
 VALUE AND U VALUES SHOWN FOR THE WALLS, WINDOWS, ETC.
 ON THE EQUIPMENT SIZING CALCULATIONS SUBMITTED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATIONS.
 ***NOTE: COORDINATE INFORMATION WITH PLANS AND ENERGY
 CALCULATIONS SUBMITTED.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-01 Cont ID  
Sent By jgomez Date 2013-08-01 Time 11:33 Rev Time 0.00
Received By jgomez Date 2013-08-01 Time 11:33 Sent To  
Notes
2013-08-01 12:02:48RESIDENTIAL (R3) GARAGE CONVERSION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED (SEC.
 403.6 OF 2010 FBC-ENERGY CONSERVATION) :
 A) DESIGN CONDITIONS TO COMPLY WITH SEC. 302.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) SPECIFY OUTDOOR AND INDOOR UNITS (MODEL AND
 MANUFACTURER) SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2 PROVIDE COMPLETE A/C PLANS. SHOW EQUIPMENT SPECIFIED
 ON THE EQUIPMENT SIZING CALCULATIONS, ALL DUCTWORK
 LOCATION AND SIZES, EQUIPMENT LOCATION, ETC. SEC.
 107.3.5.3 (10) OF CITY AMENDMENTS TO FBC.
  
 3- PLANS TO SHOW COMPLIANCE WITH THE RETURN AIR AND
 BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010
 FBC-RESIDENTIAL.
  
 4- HOW GETTING R-15 VALUE ON CONCRETE BLOCK WALLS, AND
 R-30 IN CEILING ON A FLAT ROOF AS SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 5- CLARIFY IF CALCULATIONS ARE FOR THE CONVERTED GARAGE
 AREA ONLY OR FOR ENTIRE HOUSE. IF CHANGING THE A/C SIZE
 FOR ENTIRE HOUSE, THEN THE CALCULATIONS NEED TO TAKE
 INTO CONSIDERATION THE WHOLE HOUSE NOT JUST THE GARAGE
 AREA. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 6- COORDINATE EQUIPMENT SIZING CALCULATIONS WITH THE
 ENERGY CALCULATIONS. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-02 Cont ID  
Sent By jgomez Date 2013-08-01 Time 11:32 Rev Time 0.00
Received By jgomez Date 2013-08-01 Time 11:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-12-30 Cont ID  
Sent By dkittred Date 2013-12-30 Time 08:10 Rev Time 0.00
Received By dkittred Date 2013-12-30 Time 07:58 Sent To  
Notes
2013-12-30 08:10:1812/30/13
 RE-STAMPED NEW SHEETS APPROVED. REVISIONS DID NOT
 AFFECT ZONING'S ORIGINAL REVIEW. SENT BACK TO BOX R19.
 DK
  
2013-12-26 15:59:45NEW SHEETS SUBMITTED. NEED TO RE-STAMP. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-11-13 Cont ID  
Sent By dkittred Date 2013-11-13 Time 09:22 Rev Time 0.00
Received By dkittred Date 2013-11-13 Time 09:21 Sent To  
Notes
2013-11-08 15:11:34NEW SHEETS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By avann Date 2013-07-11 Time 11:25 Rev Time 0.00
Received By dkittred Date 2013-07-10 Time 15:56 Sent To  
Notes
2013-07-10 15:11:417/10/13