Plan Review Details - Permit 13070133
Plan Review Stops For Permit 13070133
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-28 Cont ID  
Sent By JWITMER Date 2013-08-28 Time 15:49 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-16 Cont ID  
Sent By jwitmer Date 2013-07-16 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2013-07-16 Time 07:16 Sent To  
Notes
2013-07-16 07:38:44BUILDING PLAN REVIEW
 PERMIT: 13070133
 ADD: 400 N FLAGLER # 801
 CONT: ULTIMATE ENVIROMENTS
 TEL: (561) 998-3643
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 REVIEW
 DATE:
 ACTION: DENIED
  
 1) SHEET A1.1 & A1.2 MISSING WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10 EXPOSURE "D"
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. 24
 STORIES APPROX 250 FT.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) . IS UNIT # 801 A END ZONE (5) BEING
 LOCATED ON THE CORNER OF THE BUILDING, HIGHER PRESSURES
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 4))FLOOR INSULATIONS:
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 4C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 16:24 Rev Time 0.00
Received By dharvey Date 2013-08-15 Time 16:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-07-13 Cont ID  
Sent By wjolin Date 2013-07-13 Time 17:22 Rev Time 0.00
Received By wjolin Date 2013-07-13 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-28 Cont ID  
Sent By jwitmer Date 2013-08-28 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2013-08-19 Time 10:04 Sent To  
Notes
2013-08-20 10:04:21SENT TO B11 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-16 Cont ID  
Sent By shill Date 2013-08-16 Time 10:12 Rev Time 0.00
Received By shill Date 2013-07-03 Time 09:29 Sent To  
Notes
2013-08-15 16:25:05PLACED IN DENIED UNDER "T" DH
2013-07-09 09:30:02SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-28 Cont ID  
Sent By jwitmer Date 2013-08-28 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2013-08-28 Time 15:48 Sent To  
Notes
2013-08-28 15:49:33REVISION REQUIRED: 2010 FBC-M 603.17 PROVIDE GRILLE
 SIZES FOR NEW WORK BEFORE INSPECTION. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-16 Cont ID  
Sent By hmoser Date 2013-07-16 Time 14:17 Rev Time 0.00
Received By hmoser Date 2013-07-16 Time 13:49 Sent To  
Notes
2013-07-16 14:17:03PLAN DENIED
 1) PROVIDE CHANGE OUT FORM WITH APPLICATION.
 2) MARK THE DUCT SIZE ON THE PLANS FOR
 DUCT BEING WORKED ON. PER SECTION 107 2010 FBC
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-10 Cont ID  
Sent By lwagner Date 2013-07-10 Time 14:38 Rev Time 0.00
Received By lwagner Date 2013-07-10 Time 13:22 Sent To  
Notes
***NONE***