Plan Review Details - Permit 13070011
Plan Review Stops For Permit 13070011
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-07 Cont ID  
Sent By rmcdouga Date 2013-11-07 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2013-11-07 Time 17:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-03 Cont ID  
Sent By shill Date 2013-07-03 Time 13:06 Rev Time 0.00
Received By shill Date 2013-07-03 Time 13:06 Sent To  
Notes
2013-07-03 13:11:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ASSEMBLY SELECTED DOES NOT MEET DESIGN PRESSURE
 REQUIREMENTS FOR ZONES 2 AND 3. EXPOSURE D, 20' MRH
 REQUIRES -81.4, -122.5 FOR ZONE 2 AND 3 RESPECTIVELY.
 THE ASSEMBLY SELECTED HAS A LIMITATION OF -60, FBC 2010
 RESIDENTIAL 301.
  
 2. PROVIDE THE COMPLETE FLORIDA STATE PRODUCT APPROVAL
 INCLUDING COVER SHEET, FAC9N-3.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-03 Cont ID  
Sent By shill Date 2013-07-03 Time 13:11 Rev Time 0.00
Received By shill Date 2013-07-02 Time 07:24 Sent To  
Notes
2013-07-02 07:24:38TO RM DESK
  